Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
15
BATTERY VOLTAGE TOO HIGH
TRIGGER-ON: Voltage at the microprocessor is greater than 17 VDC.
UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON
still energized.
RESET CONDITION: Auto Reset after 15 minutes when the voltage at the microprocessor is between
11 and 14 VDC, or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Check Battery Voltage
a. Test voltage at battery with unit off. Must be between 12-16 VDC.
b. Test voltage at battery with unit
running.
Must be between 12-16 VDC.
2
Check Battery Charger Voltage
a. Test voltage at battery charger
output terminal with unit off.
Must be between 12-16 VDC.
b. Test voltage at battery charger
output terminal with unit running.
Must be between 12-16 VDC.
3
Check Voltage At Microprocessor
a. Check voltage reading at micro-
processor input (MPQC1+ to
MPQC2-.)
Energize circuit. (Refer to Note 2 Page 7-2)
Must be between 12-16 VDC.
b. Check voltage reading on micro-
processor display.
Must be within 0.5 VDC of reading obtained in 3a
(above.)
Summary of Contents for NDK33BN0KB
Page 2: ......
Page 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Page 4: ......
Page 14: ......
Page 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Page 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Page 30: ...62 61753 21 2 6...
Page 48: ......
Page 212: ......
Page 226: ......
Page 248: ......
Page 252: ......
Page 262: ......
Page 270: ......