Caution!! For the following applications, use the minimum vertical vent heights as specified below. For all other applications,
follow exclusively the National Fuel Gas Code.
FURNACE
ORIENTATION
VENT ORIENTATION
FURNACE INPUT
(BTUH/HR)
MIN. VENT
DIAMETER
IN (MM)*
MIN. VERTICAL VENT
HEIGHT
FT. (M)**
Downflow
Vent elbow left, then up Fig.
132,000
5 (127 )
12 (4)
Horizontal Left
Vent elbow right, then up Fig.
132,000
5 (127 )
7 (2)
Horizontal Left
132,000
5 (127 )
7 (2)
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC
*4 in. (102 mm) inside casing or vent guard
**Including 4 in. (102 mm) vent section(s)
SEE NOTES: 1,2,4,7,8,9
on the page following
these figures
A03208
Fig. 27
−
Upflow Application
−
Vent Elbow Up
SEE NOTES: 1,2,3,4,7,8,9
on the pages following
these figures
A03209
Fig. 28
−
Upflow Application
−
Vent Elbow Right
SEE NOTES:1,2,3,4,5,7,8,9
on the page following
these figures
A03210
Fig. 29
−
Downflow Application
−
Vent Elbow Up then Left
SEE NOTES: 1,2,4,5,7,8,9
on the page following
these figures
A03211
Fig. 30
−
Downflow Application
−
Vent Elbow Up