
Installing the MPC Open XP
MPC Open XP
MPC Open XPIO48/816
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
19
To use the Auto-Off-On switches
You can control an output using the
Auto-Off-On
switch.
Set the switch to...
To...
On
Turn on the output.
Off
Turn off the output.
Auto
Let the control program control the output.
The potentiometer, located between the
Auto-Off-On
switch and the jumper, allows you to manually control the
output level of an analog output. Place the
Auto-Off-On
switch in the
On
position, then turn the potentiometer
counterclockwise to reduce the output, or clockwise to increase the output.
WARNING!
The output potentiometer is NOT used for binary output channels. For a binary output, turn the
potentiometer clockwise until it stops (maximum output) and leave it in this position. Failure to do so may result in
relay-chattering or failure of the relay to energize when the
Auto-Off-On
switch is in the
On
position.
Wiring devices to the MPC Open XP's Rnet port
The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain or hybrid configuration.
Supports up to
•
15 wireless and/or ZS sensors (5 per control program)
•
One Equipment Touch
•
One TruVu™ ET Display
NOTES
•
ZS sensors, a Wireless Adapter, and an Equipment Touch can share the Rnet, but not SPT sensors.
•
The Wireless Adapter, Equipment Touch, or TruVu™ ET Display must be powered by an external power source.