Introduction
MPC Open XP
MPC Open XPIO48/816
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
6
Protection
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power is protected by 2 replaceable 3 Amp Pico
®
fuses. The power,
network, input, and output connections are protected against transient excess
voltage/surge events lasting no more than 10 msec.
Status indicators
LEDs indicate status of communications, running, errors, and outputs.
Environmental operating
range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
NOTE
Install in a UL Listed enclosure only.
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged aluminum cover, removable screw-type terminal blocks
Overall dimensions
A:
B:
9 in. (22.9 cm)
4-13/16 in. (12.2 cm)
Mounting dimensions
(in a panel)
C:
D:
E:
F:
8-5/8 in. (21.8 cm)
1 in. (2.5 cm)
2-13/16 in (7.1 cm)
1/4 in. (.6 cm)
Depth
1-7/16 in. (3.7 cm)
Weight
13.3 oz. (.377 kg)
Listed by
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
Safety considerations
WARNING
Disconnect electrical power to the MPC Open XP before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.