background image

1

Low--Ambient

Pressure Switch

Installation Instructions

KSALA0201R22

KSALA0301410

NOTE

: Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Improper

installation,

adjustment,

alteration,

service,

maintenance, or use can cause explosion, fire, electrical shock or

other conditions which may cause personal injury or property

damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified

installer or agency must use factory authorized kits or accessories
when modifying products.
Follow all safety codes. Installation must be in compliance with
local and national building codes. Wear safety glasses, protective

clothing, and work gloves. Have fire extinguisher available. Read

these instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit.

Recognize safety information.

This is the safety--alert symbol

. When you see this symbol on

the unit and in instructions or manuals, be alert to the potential

for personal injury.
These words are used with the safety--alert symbol. DANGER

identifies the most serious hazards, which

will

result in severe

personal injury or death. WARNING signifies a hazard, which

could

result in personal injury or death. CAUTION is used to

identify unsafe practices, which

may

result in minor personal

injury or product and property damage. NOTE is used to

highlight suggestions which

will

result in enhanced installation,

reliability, or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before beginning any installation or modification, be sure

the main electrical disconnect is in the OFF position. Tag

the disconnect switch with a suitable warning label.

!

WARNING

INTRODUCTION

These instructions cover the installation of low--ambient pressure
switch Part No. KSALA0201R22 and KSALA0301410 in all

single--speed air conditioners or heat pumps using R--22 or

R--410A. Refer to Table 1 for kit usage. This device is a long life
pressure switch that maintains head pressure by turning the fan

off and on. Other accessories may be required. Refer to the
Required Changes for Cooling Units and Heat Pump Units

section.

DESCRIPTION AND USAGE

The low--ambient pressure switch kit is a long life pressure switch

which turns the fan on and off as shown in Table 1. It is wired in
series with black fan lead. Sleeve--bearing motors can be used

with this control.

INSTALLATION

The pressure switch is mounted inside the outdoor unit cabinet by

using adapter tube supplied. The adapter tee is mounted to liquid
service valve and tube is routed through one of the knockout

holes in unit cabinet. From inside cabinet, the flare nut is attached

to extender tube. (See Fig. 1.) The pressure switch is wired in
series with black or common fan lead.

PROCEDURE 1—WIRING FOR ALL VOLTAGES OF

COOLING UNITS

For all voltages of cooling units, refer to Fig. 2 and wire

low--ambient pressure switch as follows:

1. Disconnect black fan lead from contactor and connect this

lead to yellow or violet wire from low--ambient pressure
switch using connector supplied.

2. Connect blue wire from low--ambient pressure switch to

contactor terminal from which black fan lead was
removed.

PROCEDURE 2—WIRING FOR HEAT PUMPS

Heat pumps require a normally closed isolation relay with the

24--v coil connected to the C and O terminals of defrost board.

A. 208/230v Applications

For 208/230--v heat pump applications, refer to Fig. 3 and wire

low--ambient pressure switch as follows:

1. Remove black fan lead from defrost board terminal OF2

and reconnect it to NC terminal of isolation relay. Connect
yellow or violet lead from low--ambient pressure switch to
same NC terminal of isolation relay.

2. Connect a wire from the other NC terminal of isolation

relay to OF2 terminal of defrost board. Connect blue lead

from low--ambient pressure switch to same NC terminal of
isolation relay.

B. 460v Applications

For 460--v heat pump applications, refer to Fig. 4 and wire

low--ambient pressure switch as follows:

1. Remove black fan lead from outdoor fan relay terminal

number 3 and reconnect it to NC terminal of isolation
relay. Connect yellow or violet lead from low--ambient
pressure switch to same NC terminal of isolation relay.

2. Connect a wire from outdoor fan relay terminal number 3

to other NC terminal of isolation relay. Connect blue lead

from low--ambient pressure switch to same NC terminal of
isolation relay.

Summary of Contents for KSALA0201R22

Page 1: ...sories may be required Refer to the Required Changes for Cooling Units and Heat Pump Units section DESCRIPTION AND USAGE The low ambient pressure switch kit is a long life pressure switch which turns the fan on and off as shown in Table 1 It is wired in series with black fan lead Sleeve bearing motors can be used with this control INSTALLATION The pressure switch is mounted inside the outdoor unit...

Page 2: ...ired to provide better airflow for moderate and high ambient temperatures Check pre sale literature for available support feet or unit risers CUT HAZARD Failure to follow this caution could result in personal injury To reduce risk of personal injury wear personal protective equipment when working with wind baffles Only experienced technicians should fabricate and install wind baffles CAUTION 5 For...

Page 3: ...ow room temperature 3 Wait for the unit to start There may be a 5 minute delay in the thermostat or in the outdoor unit 4 Observe unit operation as described below a The fan will be off when compressor starts b At outdoor temperatures around 0_F fan may not run at all c At summer temperatures fan will start after 10 to 30 sec of compressor operation and may not turn off until thermostat is satisfi...

Page 4: ...6 TYP G J K E D L 9 64 3 45 DIA HOLE 1 REQ D 7 32 5 56 DIA HOLE 3 REQ D 7 32 x 2 5 56 x 50 8 SLOT 1 4 6 3 TYP BAFFLE MAT L 20 GA STEEL SUPPORT MAT L 18 GA STEEL 9 64 3 45 DIA HOLE 2 REQ D OUTDOOR UNIT F AA SCREW 10 REQ D SUPPORT 4 REQ D BAFFLE 2 REQ D BAFFLE ASSEMBLY 1 4 6 3 TYP A95444 Fig 6 Carrier WeatherMaker Units KSALA ...

Page 5: ...5 3 16 42 15 15 16 35 3 4 36 1 2 50 7 16 35 11 16 36 7 16 35 5 8 22 11 16 17 7 8 7 1 16 Wind Baffle Dimensions for Carrier WeatherMaker Units with Silencer System Top In Unit Size AA Unit Height A B C D E F G H J K L M Small 27 1 2 23 13 16 17 25 1 4 10 3 8 19 3 4 20 1 2 34 19 11 16 20 7 16 19 5 8 0 0 6 1 8 27 13 16 17 25 1 4 10 3 8 23 3 4 24 1 2 34 23 11 16 24 7 16 23 5 8 0 11 7 8 6 1 8 33 13 16 ...

Page 6: ...L 1 8 3 45 DIA HOLE 1 REQ D 1 4 5 56 DIA HOLE 3 REQ D 1 4 x 2 5 56 x 50 8 SLOT 1 4 6 3 BAFFLE MAT L 20 GA STEEL SUPPORT MAT L 18 GA STEEL 1 8 3 45 DIA HOLE 2 REQ D 3 8 9 6 6 152 4 1 4 5 56 DIA HOLE 2 REQ D OUTDOOR UNIT BAFFLE ASSEMBLY SCREW 10 REQ D SUPPORT 4 REQ D BAFFLE 2 REQ D AA A95445 Fig 7 Bryant Reliant Units KSALA ...

Page 7: ... 14 7 8 37 7 8 25 5 16 39 3 4 10 1 4 35 3 4 36 1 2 50 9 16 35 5 8 36 3 8 35 5 8 21 11 16 17 7 8 Wind Baffle Dimensions for Bryant Reliant Units with AeroQuiet Top In Unit Size AA Unit Height A B C D E F G H J K L Small 26 3 16 23 13 16 17 1 4 24 5 16 10 1 4 19 3 4 20 1 2 34 1 2 19 5 8 20 3 8 19 5 8 0 0 27 13 16 17 1 4 24 5 16 10 1 4 23 3 4 24 1 2 34 1 2 23 5 8 24 3 8 23 5 8 0 11 7 8 33 13 16 17 1 ...

Page 8: ...5 56 DIA 2 REQ D 25 64 10 0 E 7 7 8 200 0 3 16 4 6 1 8 3 45 DIA 2 REQ D BAFFLE LEFT MAT L 20 GA STEEL F C 5 3 64 128 0 1 2 12 7 TYP E 7 29 32 200 8 BAFFLE RIGHT MAT L 20 GA STEEL A D 1 21 32 42 1 25Ú64 10 0 2 1 2 63 5 G 1 4 5 56 DIA 4 REQ D J C AA H J 1 4 6 4 23 64 9 2 1 2 12 7 TYP 8 5 64 205 3 TYP 4 57Ú64 124 2 TYP 2 5 64 52 6 4 9 64 105 2 45 TYP 1 8 3 45 DIA 4 REQ D 1 4 5 56 DIA 2 REQ D 23 64 9 ...

Page 9: ...1 16 24 3 4 16 3 16 8 1 4 25 13 16 23 13 16 29 15 16 27 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 27 13 16 25 13 16 31 15 16 29 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 29 13 16 27 13 16 33 15 16 31 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 31 13 16 29 13 16 37 15 16 33 7 8 18 5 16 32 5 8 10 11 16 24 3 4 16 3 16 8 1 4 33 13 16 31 13 16 39 15 16 35 7 8 18 5 16 32 5 8 10 11 16 ...

Page 10: ... 2 REQ D 1 8 3 45 DIA HOLE 3 REQ D WIND BAFFLE 1 2 12 7 1 25 4 5 5 16 134 2 7 16 11 8 3 8 10 3 G H 7 16 11 8 3 8 10 3 1 2 12 7 1 4 6 35 x 1 2 12 7 SLOT 2 REQ D 1 8 3 45 DIA HOLE 3 REQ D SUPPORT B RIGHT AND LEFT HAND REQ D J 3 76 2 1 25 4 x 3 76 2 NOTCH THIS SIDE BAFFLE SUPPORT B BAFFLE SUPPORT A WIND BAFFLE BAFFLE ASSEMBLY SUPPORT A A95447 Fig 9 Payne Units Models PA10 PA12 and PH10 PH12 KSALA ...

Page 11: ... 16 17 5 16 10 13 16 37 15 16 36 11 16 18 5 16 107 1 16 86 9 16 54 11 16 22 3 4 24 11 16 18 5 16 10 13 16 Wind Baffle Dimensions for Payne PH10 PH12 Heat Pump Units In Unit Size AA Unit Height A B C D E F G H J Medium 22 1 2 21 15 16 18 11 16 9 5 16 81 1 2 67 7 8 41 13 16 15 13 16 18 11 16 9 5 16 14 13 16 23 15 16 20 11 16 10 5 16 81 1 2 67 7 8 41 13 16 15 13 16 18 11 16 10 5 16 14 13 16 25 15 16 ...

Page 12: ...12 A06235 Fig 10 Base Comfortt Legacyt Units Baffle Assembly KSALA ...

Page 13: ...16 5 16 11 9 16 47 3 8 28 15 16 23 13 16 11 3 4 9 3 8 16 5 16 11 9 16 47 3 8 32 5 16 27 3 16 13 1 2 9 3 8 16 5 16 11 9 16 47 3 8 35 3 4 30 5 8 15 3 16 9 3 8 16 5 16 11 9 16 47 3 8 39 1 8 34 16 7 8 9 3 8 16 5 16 11 9 16 47 3 8 42 1 2 37 3 8 18 9 16 9 3 8 16 5 16 11 9 16 47 3 8 45 15 16 40 13 16 20 1 4 9 3 8 16 5 16 11 9 16 47 3 8 Large 35 25 1 2 20 3 8 10 1 16 13 3 16 20 1 8 15 3 8 51 1 8 28 15 16 ...

Page 14: ...14 BAFFLE 1 MATL 20 GA STEEL A06231 BAFFLE ASSEMBLY A06230 Fig 11 Performancet and Preferredt Series Baffle Assemblies KSALA ...

Page 15: ...15 BAFFLE 2 MATL 20 GA STEEL A06232 BAFFLE 3 MAT L 20 GA STEEL A06234 Fig 12 Performancet and Preferredt Series Baffle Assemblies continued KSALA ...

Page 16: ...16 SUPPORT MAT L 20 GA STEEL A06233 Fig 13 Performancet and Preferredt Series Baffle Assemblies continued KSALA ...

Page 17: ... 5 16 80 2 16 11 16 78 8 17 3 8 51 1 16 49 15 16 40 13 16 20 3 8 22 5 16 80 2 16 11 16 78 8 17 3 8 51 1 16 Wind Baffle Dimensions for Preferredt Series Units Unit Size AA Unit Height A In B In C In D degrees E In F degrees G In H In Medium 33 30 23 13 16 11 7 8 16 81 9 16 3 8 80 3 12 3 4 45 7 8 33 7 16 27 3 16 13 5 8 16 81 9 16 3 8 80 3 12 3 4 45 7 8 36 13 16 30 5 8 15 5 16 16 81 9 16 3 8 80 3 12 ...

Page 18: ...Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No AG SALA 07 Replaces AG SALA 05 Printed in U S A Edition Date 5 06 KSALA ...

Reviews: