background image

8                                                                 

Specifications subject to change without notice.                                                                         IM-KSAIC03-03

SCENARIO 4: SINGLE ZONE OUTDOOR 
UNIT 38MA*R WITH APPROVED MULTI-
FAMILY 24V FAN COILS FMA/FMC/FMU 

For the correct combinations, review the compatibility chart in “APPENDIX 

1 - COMPATIBILITY AND FAN SPEED WIRING” on page 15.

Installation Steps:

1. Remove the TXV/Piston on the indoor unit.
2. Run the interconnecting piping from the outdoor unit to the indoor 

unit using the outdoor piping size and brazing to the adapter for the 

mechanical fitting from which the TXV was removed (Part number 

331831-701) (available through RCD). If required, use the 

Bushing/Reducers data (review “APPENDIX 2 - PIPING 

ADAPTER BUSHINGS/REDUCERS” on page 16).

3. Suction and liquid refrigerant lines must be properly insulated and

separated from each other to prevent condensation and energy loss.

4. Disconnect and remove the 24V transformer from the 24V interface

kit. Run a 2-conductor wire from the 24 volt side of the indoor unit

transformer to CN16 and CN17.

5. Run the interconnecting wiring from the outdoor unit to the 24V 

interface using terminal connections L1, L2, S and G. Separate 

power supplies are required for the outdoor unit and the indoor unit.

6. Run the thermostat wiring from the thermostat to the 24V interface 

using connection R and C on CN15 and Y, W, G on CN19.

7. Run the thermostat wiring from the 24V interface to the indoor unit 

using output connections G1 (Low), G1+G2 (Medium), 

G1+G2+G3 (High) on the 24V interface and connect according to 

the installation manual for these fan coils.

8. Install the T1 sensor on CN5 on the 24V interface and place on the

return of the indoor unit.

9. Configure the dip switches on the 24V interface accordingly.

10. Configure the thermostat to operate as a single stage cooling and

heating (

DO NOT

 configure the thermostat as Heat Pump).

NOTES: 

Follow the indoor and outdoor unit's general installation

instructions.
The T1 (Return air temperature) sensor should be near or on the unit

on the air inlet side. The thermistor should be installed pointing down

into the duct between 2.5ft. (0.762m) and 4ft. (1.2m) from the return

side of the fan coil. Use a 1/2” drill and insert the thermistor no less

than 6 in. (15.24cm) into the duct and seal air tight around cable.

Auxiliary Heater on an FMA/FMC/FMU:

Refer to and follow the steps of the FMA/FMC/FMU Fan Coil 

Installation Instructions manual and wiring diagram:

1. Wire W2 from the thermostat directly to the FMA/FMC/FMU fan

coil as listed on the indoor unit wiring diagram.

2. Re-configure the wall thermostat to control the electric heat as a

2nd stage heat W2.

3. Follow the standard wiring practices of the FMA/FMC/FMU to

connect the Auxiliary Electric Heater element.

NOTE:

 When an auxiliary electric heater is connected and active by

W2 from the thermostat, the fan coil keeps blowing air regardless if

the outdoor unit is operating under 

DEFROST

 mode.

Fig. 12 — Wiring Diagram for Conventional 24V Fan Coil Indoor Unit

When the outdoor unit is matched with a Multi-Family or Residential fan
coil and brazing the piping on the fan coil side is required, it is
NECCESSARY to flow nitrogen into the system while brazing the line
set since a filter drier is not recommended for use with these condensing

CAUTION

The conventional thermostat must be configured for use with a single
stage air conditioner (Y output ONLY) and a single stage heating (W)
system.

CAUTION

Thermostat

70

Transformer

L1

L2

Red dash means
disconnect
transformer

Power supply from outdoor unit disconnect. 
Two wires are line voltage and the other is a ground wire.

Power supply from indoor unit

1   2   3   4   5

N G

L

C

GROUND

NOTE: Dashed Lines indicate
OPTIONAL COMPONENTS

BUS BAR

G

G

Summary of Contents for KSAIC0301230

Page 1: ...y Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which may result in severe personal injury or de...

Page 2: ...refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING INSTALLATION Entrust a licensed contractor to install the unit Installation by unskilled...

Page 3: ...ble 3 24V Interface Clearance Dimensions NOTE 24 in 610mm minimum for service access or use local code Fig 3 Clearances Clearances Unit Minimum Value In mm Sides 5 9 150 Front 24 610 Top and Bottom 3...

Page 4: ...er the screw SYSTEM CONFIGURATION NOTES The thermostat should be configured for use with a as a single stage Cooling and Heating DO NOT configure the thermostat as a Heat Pump The wireless remote cont...

Page 5: ...ndoor to the outdoor unit until the static pressure settings are complete refer to the Ducted unit installation manual On selected indoor units the Up Down Swing Louver functions as a control to turn...

Page 6: ...general installation instructions For Ducted units in order to initially setup the static pressure the 24V interface must be bridged Temporarily connect the communication wires S1 and S2 from the indo...

Page 7: ...it until the static pressure settings are complete see the Ducted unit installation manual When static pressure is adjusted reconnect L1 L2 S and G wires to the terminal blocks In the AUTO mode the sy...

Page 8: ...a single stage cooling and heating DO NOT configure the thermostat as Heat Pump NOTES Follow the indoor and outdoor unit s general installation instructions The T1 Return air temperature sensor should...

Page 9: ...oor unit s general installation in the next column 9 Configure the dip switches on the 24V Interface for proper operation For Heat Pump all switches OFF except SW1 1 ON For Cooling Only all switches O...

Page 10: ...he Teflon gasket on the brass tip of the Piping Adapter and insert into the aluminum distributor head Thread the piping adapter brass nut onto the distributor line and tighten finger tight 1 2 turn Fi...

Page 11: ...Using a Conventional Fan Coil The following steps should be taken when using this device with a conventional fan coil unit scenarios 4 and 5 1 Indoor coil metering device TXV Piston must be removed 2...

Page 12: ...il only available on scenarios 1 through 3 Table 11 DIP Switch 2 2 NOTE Applicable only to the Ductless Style Indoor Heat Pump units in the HEATING mode DIP Switch 3 1 On Ductless systems Dry is used...

Page 13: ...emperature sensor T5 malfunction Outdoor Service Manual F4 Outdoor unit EEPROM parameter error Outdoor Service Manual F5 Outdoor fan speed has been out of control Outdoor Service Manual F6 T2b sensor...

Page 14: ...opens and closes based on the system s alarm status This is normally a an open dry contact Work Output CN6 This contact is a dry contact that opens and closes based on the system s running or not run...

Page 15: ...minal System Size MBTUH Indoor Model Number Outdoor Model Number Recommended Maximum Indoor Fan Speed Tap Number FMA4 Vertical Fan Coil 208 230 1 KSAIC0301230 12 FMA4X1800AL 38MAQB12R 3 Tap 1 18 FMA4X...

Page 16: ...door coil s size No refrigerant addition is necessary for the FV4 any size All the outdoor units are shipped from the factory pre charged for 25ft of piping length See the outdoor unit s installation...

Reviews: