background image

24VNA6 / 25VNA4: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

36

The  service  valve  cannot  be  field  repaired;  therefore,  only  a  complete
valve or valve stem and service-port caps are available for replacement.
If the  service  valve  is to  be  replaced,  a metal  barrier  must  be  inserted
between  the  valve  and  the  unit  to  prevent  damaging  the  unit  exterior
from the heat of the brazing operations.

Pumpdown & Evacuation

If  this  system  requires  either  a  Pump  Down  or  Evacuation  for  any
reason, the procedures below must be followed:

Pump Down

Because  this  system  has  an  inverter  controlled,  compressor,  suction

pressure transducer and EXV, conventional procedure cannot be used to
“pump down” and isolate the refrigerant into the outdoor unit.  The UI
(User Interface) has provisions to assist in performing this function.  

1. Connect gages to outdoor unit liquid and vapor or suction capillary

service  ports  to  monitor  operating  pressures  during  and  at
completion of the procedure.

2. In  the  "installation  and  service"  menu  of  the  wall  control,  go  to

"refrigerant charging" and then "pump down

3. Select  mode  to  pump  down  in  (COOL  or  HEAT),  COOL  mode

allows refrigerant to be isolated in outdoor unit. HEAT mode allows
the refrigerant to be isolated in indoor coil and lineset. Set desired
time period. Default time period for the procedure is 120 minutes.

4. Select ”Start” on wall control to begin the pumpdown process. Unit

will begin running in selected mode after a brief delay and a status
screen will be displayed.

5. Close the liquid service valve.
6. The unit will run in selected mode with the low pressure protection

set  to  indicate  pumpdown  is  complete  when  the  suction  pressure

drops  below  20  psig.  Compressor  protections  are  still  active  to
prevent damage to the compressor or inverter (high pressure, high
current, etc.).

7. Once system indicates pumpdown complete or failure to complete

shutdown, close vapor service valve.  

8. A  recovery  system  will  be  required  to  remove  final  quantity  of

refrigerant from indoor coil and line set.

9. Remove power from indoor and outdoor unit prior to servicing unit.

NOTE: 

A small quantity of charge remains in the OD unit that must be

manually recovered if isolating refrigerant to indoor coil and lineset via
HEAT mode PUMP DOWN.

Evacuation and Recovery of Refrigerant from 25VNA4

NOTE: 

All outdoor unit coils will hold only factory-supplied amount of

refrigerant.  Excess  refrigerant,  such  as  in  long-line  applications,  may
cause  unit  to  relieve  pressure  through  internal  pressure-relief  valve
(indicated  by  sudden  rise  of  suction  pressure)  before  suction  pressure

reaches 5 psig (35kPa). If  this occurs, shut unit off  immediately,  front
seat  suction  valve,  and  recover  remaining  pressure.  connection  to  the
suction port of the compressor.

Reversing Valve (25VNA4)

In  heat  pumps,  changeover  between  heating  and  cooling  modes  is
accomplished  with  a  valve  that  reverses  flow  of  refrigerant  in  system.
This  reversing  valve  device  is  easy  to  troubleshoot  and  replace.  The
reversing  valve  solenoid  can  be  checked  with  power  off  with  an
ohmmeter.  Check  for  continuity  and  shorting  to  ground.  With  control
circuit (24v) power on, check for correct voltage at solenoid coil. Check
for overheated solenoid.

NOTE: 

Reversing valve diagnostic can only detect an open coil when

reversing  valve  is  not  energized,  thus  a  damaged  coil  during  cooling
operation will not trigger diagnostic.  In this case the HP will operate in
heating  mode  when  wall  controller  is  requesting  cooling  operation.
Manual troubleshooting of coil will be required to confirm failure. 
With  unit  operating,  other  items  can  be  checked,  such  as  frost  or
condensate water on refrigerant lines.
The sound made by a reversing valve as it begins or ends defrost is a
"whooshing"  sound,  as  the  valve  reverses  and  pressures  in  system
equalize. An experienced service technician detects this sound and uses
it as a valuable troubleshooting tool.
Using  a  remote  measuring  device,  check  inlet  and  outlet  line
temperatures.  DO  NOT  touch  lines.  If  reversing  valve  is  operating
normally,  inlet  and  outlet  temperatures  on  appropriate  lines  should  be
close  to each other. Any difference would be due to heat loss  or gain
across valve body. Temperatures are best checked with a remote reading
electronic-type thermometer with multiple probes. Route thermocouple
leads  to  inside  of  coil  area  through  service  valve  mounting  plate  area
underneath coil. 

Fig. 34

 and 

Fig. 35

 show test points (TP) on reversing

valve  for  recording  temperatures.  Insulate  points  for  more  accurate
reading.If valve is defective:

1. Shut off all power to unit and remove charge from system.
2. Remove solenoid coil from valve body. Remove valve by cutting it

from system with tubing cutter. Repair person should cut in such a
way that stubs can be easily re-brazed back into system. Do not use
hacksaw. This introduces chips into system that cause failure. After
defective valve is removed, wrap it in wet rag and carefully unbraze
stubs.  Save  stubs  for  future  use.    Because  defective  valve  is  not
overheated,  it  can  be  analyzed  for  cause  of  failure  when  it  is
returned.

3. Braze  new  valve  onto  used  stubs.  Keep  stubs  oriented  correctly.

Scratch corresponding matching marks on old valve and stubs and
on new valve body to aid in lining up new valve properly. When
brazing stubs into valve, protect valve body with wet rag to prevent
overheating.

4. Use slip couplings to install new valve with stubs back into system.

Even  if  stubs  are  long,  wrap  valve  with  a  wet  rag  to  prevent
overheating.

5. After  valve  is  brazed  in,  check  for  leaks.  Evacuate  and  charge

system.  Operate  system  in  both  modes  several  times  to  be  sure
valve functions properly.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear  safety  glasses,  protective  clothing,  and  gloves  when  handling
refrigerant.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental damage.
Federal  regulations  require  that  you  do  not  vent    refrigerant  to  the
atmosphere. Recover during system repair or final unit disposal.

Summary of Contents for Infinity 24VNA6

Page 1: ...ons 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Status Light 10 Comm Light 10 VFD Comm Ligh...

Page 2: ...et the HP unit achieves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technolog...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wirin...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 24VNA6 25VNA4 Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...nding on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crankcase heater band inst...

Page 6: ...P Swtich Settings IMPORTANT The R Rc signal on the PCM comes from the transformer in the equipment The phase of this transformer connection is not controlled relative to the phase of the transformer i...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...valve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...eceived within the last 2 minutes and the equipment is operating in emergency communicating mode VFD Comm Light The VFD Comm light blinks every time there is a message received from the VFD If a messa...

Page 11: ...IOR TO TOUCHING ELECTRICAL COMPONENTS Verify less than zero 0 vdc voltage at VFD connections shown on cover Table 2 VFD LED Indicator Functions LED Identification Color Function R1 Red Used to indicat...

Page 12: ...emand is present and until pressure equalization is complete if necessary and the fan has successfully started Diagnostic Code Recall The Diagnostic Code Recall mode will be enabled if the Forced Defr...

Page 13: ...hutdown occurs the next operating cycle will operate at 25 less capacity Each fault after that will reduce capacity by an additional 25 Each hour of operation without a fault will increase the availab...

Page 14: ...at the bottom of the control box with the sensing element protruding through the bottom of the control box to be in contact with the outside air The OAT thermistor location is illustrated in Fig 13 A...

Page 15: ...are displayed as critical faults even during cooling operation so that service may be performed before heating is required Pressure Sensors The equipment contains two pressure transducers Suction Pres...

Page 16: ...VI valve bodies are different for different models the stator for all valves have the same electrical properties The EXV coil resistance should fall between 43 and 49 ohms when measured from common t...

Page 17: ...d on board header Also inspect and repair any wire damage on harness If no green or red led is present on the Bluetooth module disconnect harness at the Bluetooth module and check for 18 30 VAC betwee...

Page 18: ...ed with new undamaged part LLS are field installed accessories Check LLS wiring for shorts See wiring diagram for fuse size and location Code 31 11 Compressor High Pressure Limiting Code 31 58 Compres...

Page 19: ...sor The PEV is included to ensure compressor will never start against a high pressure differential This fault will become active if a demand exists and the PEV is not successful in lowering pressure d...

Page 20: ...f OAT thermistor is higher than the electrical circuit is capable of measuring this fault will be generated Measure resistance value of thermistor at the PCM connector If value is above 465kohm look f...

Page 21: ...Code 57 42 P1 Shorted Lockout Code 58 02 P2 Shorted Fault Code 58 42 P2 Shorted Lockout Pressure transducers are dynamically assigned based on their relative values within PCM software This feature a...

Page 22: ...day the EXV VI will test itself by operating to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count whe...

Page 23: ...PCM reset the VFD and restart if demand is still present The system should resume operation after 5 minute compressor protection time delay expires 4 occurrences of code 82 15 within a 1 hour period w...

Page 24: ...t in 86 46 malfunction which has a 1 hour lockout When code 86 06 is set VFD will shut down compressor and fan and re initialize in an attempt to re establish communication between VFD and PCM Inspect...

Page 25: ...res Three occurrences of code 88 36 within a 4 hour period will result in 88 76 malfunction and 4 hour lockout While this fault or malfunction is active the unit is inoperable This malfunction once se...

Page 26: ...e 33 15 55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting E...

Page 27: ...12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shut...

Page 28: ...nd designs without notice and without obligations 28 A200187 Fig 19 2T 3T Control Box A200188 Fig 20 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 29: ...otice and without obligations 29 A200191 Fig 23 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 30: ...192 Fig 24 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 31: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 31 A200193 Fig 25 PCM used on all models...

Page 32: ...designs without notice and without obligations 32 A200194 Fig 26 Bluetooth Module used on all models A200195 Fig 27 Fan Motor used on all models A200196 Fig 28 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 33: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200199 Fig 31 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 32 VF...

Page 34: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A200201 Fig 33 PCM Wiring Diagram...

Page 35: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 36: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 37: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 38: ...ventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 38 This fusible element will m...

Page 39: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 41 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 40: ...idential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with y...

Reviews: