1 - PRECAUTIONS

1.1 - Operating limits

1.1.1 - Cooling mode

Minimum  blowing  temperature  12°C  when  the  apparatus  is 

installed in an atmosphere of 27°C DB (dry bulb) and 65% RH 

(relative humidity).

1.1.2 - Heating mode

The  blowing  temperature  must  not  exceed  60°C.  Carrier 

recommends not to exceed a temperature of 35°C for blowing so 

as to avoid any risk of layering, cause of discomfort.

1.1.3 - Operating environment

42GR ATM  has  been  designed  to  operate  in  a  non-corrosive, 

“urban”  internal  atmosphere,  free  of  dust,  in  a  non-marine 

environment. The levels of the chemical compounds below must 

in no case be exceeded: 

 

-

SO

2

  

<   0,02 ppm

 

-

H

2

S  

<   0,02 ppm

 

-

NO, NO

2

   <   1 ppm

 

-

NH

3

  

<   6 ppm

 

-

N

2

O  

<   0,25 ppm

Do  not  install  the  unit  in  atmospheres  comprising  inflammable 

gases,  or  acidic  or  alkaline  products.  The  copper/  aluminium 

battery and the internal components could undergo irreversible 

corrosion.

1.1.4 - Quality of water recommended for the water 

coils

On receiving the installation, and then periodically every year, it 

is recommended to carry out a bacteriological (detection of ferro-

bacteria, H

2

S producing bacteria and sulfate reducing bacteria) 

and chemical analysis of water (in order to avoid the problems of 

scaling and corrosion). The water circuit must include components 

required for the treatment of water: filters, additives, intermediate 

exchangers, purges, vents, isolating valves, etc. depending on 

the results of the analysis.

The results of analysis must correspond to the values mentioned 

below:

 

-

Total hardness in mmol/l:   1   < mmol/l  

< 1,5

 

-

Chloride [CL

-

]  

  < 10 mg/l

 

-

Sulphate [SO

4

2-

]  

  < 30 mg/l

 

-

Nitrate [NO

3

-

]  

  = 0 mg/l

 

-

Dissolved iron:  

  < 0,5 mg/l

 

-

Dissolved oxygen:  

4   < [O

2

] < 9 mg/l

 

-

Carbon dioxide [CO

2

]  

  < 30 mg/l

 

-

Resistivity:  

20 Ω·m   < Resistivity < 50 Ω·m

 

-

pH:  

6,9  < pH < 8

1.2 - Reservation for maintenance

42GR ATM requires some place to carry out its
maintenance. Changing the filter is done through the filter
access door (Fig. 6c) of the air treatment module (ATM).

1.3 - Reception - Place of installation

Upon reception, check the condition of the equipment, identify any 

possible damage owing to transportation and send any complaint 

regarding this to the transporter in writing. Do not unpack until the 

final installation, as close as possible to the place of installation, 

and do not place heavy tools on the packaging during the waiting 

period.

1.4 - Supply voltage 230V ± 10% - 50 Hz

Check whether the supply voltage and frequency correspond to 

those required for the unit to be installed.

CAUTION: Carrier suspends the effect of the warranty if these 

points are not followed, or if electrical changes have been 

made to the original connections.

11

Summary of Contents for Idrofan 42GR ATM

Page 1: ...I N S TA L L AT I O N I N S T R U C T I O N S Original document AIR TREATMENT MODULE 42GR ATM...

Page 2: ......

Page 3: ...ONSIDERATIONS 12 2 1 General points 12 2 2 Protection against electrocution 12 2 3 General recommendations for installation 12 2 4 Recommendation regarding the regulation 12 2 5 Regulations 12 3 INSTA...

Page 4: ...B C D 4a 4b 4c E 2000 125 12 5 250 480 518 480 11 19 9 500 500 500 250 5a 125 F 4...

Page 5: ...6k 6f 6f 6f 6e 6i 6d 6b 6a 6g 6h 6c E B A C D 6j 6e A B C D E F 42 GR T19 334 585 895 1138 805 12 5 42 GR T29 416 585 895 1138 805 12 5 G 7b 7c 7a 22 17 50 15 50 30 50 100 mm H 5...

Page 6: ...B A D 8a C L E G H I J F K J A B C D E F G H I J K L 42 GR T19 90 107 137 125 230 159 93 58 250 93 177 250 42 GR T29 90 147 267 125 230 199 122 170 420 120 160 250 B A D 9a C L E G H I J F K A C E F...

Page 7: ...E F G H I J 42 GR T19 250 402 198 674 128 742 344 600 183 75 125 42 GR T29 420 402 198 674 128 742 344 600 183 75 125 11a 11b 11c L B C 450 max J H G F I D E C L 12c 12b 12d 12a M 0 10 V 230 V N E B...

Page 8: ...P 15a 15b O 14c 14b 14a 16b 16c 16e 16d 16a 16f Q 17c 17b 17a 17d R 8...

Page 9: ...MR60 17 60 4 4 4 4 MR75 21 75 4 3 4 3 MR85 24 85 3 3 3 2 MR90 25 90 3 2 2 2 MR100 28 100 2 1 2 1 MR105 29 105 2 1 1 1 MR110 31 110 1 1 1 1 MR120 33 120 3 3 MR130 36 130 2 1 MR140 39 140 1 1 MR160 44...

Page 10: ...12d Fan motor N LEC vitesse variable wires nus 1 Phase 230 V brown wire 2 Neutral 230 V blue wire 3 Earthing green and yellow wire 4 0 10 V yellow wire 5 GND blue wire O Replacement of the electric b...

Page 11: ...ling and corrosion The water circuit must include components required for the treatment of water lters additives intermediate exchangers purges vents isolating valves etc depending on the results of t...

Page 12: ...blue brown green yellow and its cross section and type must comply with the specifications set out by the applicable EN or IEC standard Refer to the selection sheet or the name plate to determine the...

Page 13: ...Then connect the hydraulic hoses Connect the condensate drains of the ATM Fig 7 using a fastener for exible tube of inner 16 mm Fig 7a To avoid the emergence of odour it is MANDATORY to install a siph...

Page 14: ...ded with check valves provide a container making it possible to drain the battery Disconnect the condensate drain pipes Disconnect the fresh air supply in the case where it is xed to the ATM See 3 2 2...

Page 15: ...the Size 19 42GR ATM the electric battery is located in the suction eye of the fan motor CAUTION Before any intervention on this product it is imperative to cut the electrical power supply of the unit...

Page 16: ...of regulator enables bringing in fresh air ow from 30 m3 h 8 3 l s 10 20 Procedure for replacement of the xed constant fresh air ow regulator Disconnect the exible fresh air duct Fig 11a from the fer...

Page 17: ...e body on the battery put new seals Reinstall the servomotors taking care to see that they are correctly calamped onto the valve body Reconnect the hydraulic hoses by screwing back the G 1 2 rotating...

Page 18: ...t A TOR 230V C 3 pts 230V Digit 13 Without Probe C Change over Digit 16 W WC VARIABLE Digit 14 A F5 K F6 P F7 Active carbon S Filter UVPCO Digit 15 Without X SPECIAL J Only ferrule without regulator K...

Page 19: ......

Page 20: ...2021 replaces No 14243 03 2014 The manufacturer reserves the right to modify the product specifications without prior notice Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Printed in th...

Reviews: