Nov-21
Page 36 of 132
59812-K001 Rev 10
Figure 20
Power connections
The Control Panel should be connected from the earth stud to a suitable earthing point.
Where permitted by the vessel approval authority only one power cable may be required. Connections
can be made to either power input 1 or power input 2.
Both the earth and the screen of the cable should be connected to earth at the 24v DC power supply.
2.6.2
Relay Cables
The connection to the Slowdown/Shutdown relays, Common Alarm relay, and Fault relay at the Control
Panel should be made using screened cable. For each of the relay connections strip the cable to the
required length to connect to the terminals in the Control Panel. Then remove approximately 1cm of the
outer sheath to expose the cable screen as shown below.
Cables should be segregated from high voltage cables and follow good installation practice
Figure 21
Control Panel relay cable assembly