Carrier GA7T Installation Instructions Manual Download Page 7

GA7T: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

7

Compressor Operation

The  basic  scroll  design  has  been  modified  with  the  addition  of  an

internal  unloading  mechanism  that  opens  a  by-pass  port  in  the  first

compression pocket, effectively reducing the displacement of the scroll. 

The opening and closing of the by-pass port is controlled by an internal

electrically operated solenoid. The modulated scroll uses a single step of

unloading  to  go  from  full  capacity  to  approximately  67%  capacity. A

single  speed,  high  efficiency  motor  continues  to  run  while  the  scroll

modulates between the two capacity steps. Modulation is  achieved by

venting a portion of the gas in the first suction pocket back to the low

side of the compressor, thereby reducing the effective displacement of

the compressor. Full capacity is achieved by blocking these vents, thus

increasing the displacement to 100%. 

A DC solenoid in the compressor controlled by a rectified 24 volt AC

signal in the external solenoid plug moves the slider ring that covers and

uncovers these vents. The vent covers are arranged in such a manner that

the  compressor  operates  at  approximately  67%  capacity  when  the

solenoid  is  not  energized  and  100%  capacity  when  the  solenoid  is

energized. The loading and unloading of the two step scroll is done “on

the fly” without shutting off the motor between steps. 

NOTE: 

    67%  compressor  capacity  translates  to  approximately  75%

cooling capacity at the indoor coil. 

Check Charge

NOTE: CHARGE IN HIGH STAGE ONLY

Factory charge amount and desired subcooling are shown on unit rating

plate.  Charging  method  is  shown on  information  plate  inside  unit. To

properly  check  or  adjust  charge,  conditions  must  be  favorable  for

subcooling  charging.  Favorable  conditions  exist  when  the  outdoor

temperature is between 70°F and 100°F (21.11°C and 37.78°C), and the

indoor temperature is between 70°F and 80°F (21.11°C and 26.67°C).

Follow the procedure below:
Unit is factory charged for 15ft  (4.57 m) of lineset. Adjust charge by

adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15ft (4.57

m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow system

to operate in high-stage cooling mode at least 15 minutes. If conditions

are  favorable,  check  system  charge  by  subcooling  method.  If  any

adjustment  is  necessary,  adjust  charge  slowly  and  allow  system  to

operate for 15 minutes to stabilize before declaring a properly charged

system. 
If  the  indoor  temperature  is  above  80°F  (26.67°C),  and  the  outdoor

temperature is in  the  favorable range, adjust system charge  by weight

based on line length and allow the indoor temperature to drop to 80°F

(26.67°C)  before  attempting  to  check  system  charge  by  subcooling

method as described above. 
If  the  indoor  temperature  is  below  70°F  (21.11°C),  or  the  outdoor

temperature is not in the favorable range, adjust charge for line set length

above  or  below  15ft  (4.57  m)  only.  Charge  level  should  then  be

appropriate  for  the system to achieve  rated capacity. The charge level

could then be checked at another time when the both indoor and outdoor

temperatures are in a more favorable range.

NOTE: 

  If line length is beyond 80 ft (24.38 m) or greater than 20 ft

(6.10  m)  vertical  separation,    See  Long  Line  Guideline  for  special

charging requirements.

Final Checks

IMPORTANT: 

Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet metal

edges to prevent rub-through or wire pinching. 

2. Ensure that all wiring  and  tubing  is  secure  in  unit  before adding

panels and covers. Securely fasten all panels and covers. 

3. Tighten service valve stem caps to 1/12-turn past finger tight.

4. Leave Owner’s Manual with owner. Explain system operation and

periodic maintenance requirements outlined in manual. 

5. Fill out Dealer Installation Checklist and  place in customer file.

TROUBLESHOOTING

If the compressor fails to operate with a cooling call, 

Table 3

 can be used

to  verify  if  there  is  any  damage  to  the  compressor  windings  causing

system malfunction. 

Troubleshooting for proper switching between low- 

and high-stages

Check  the  suction  pressures  at  the  service  valves.  Suction  pressure

should be reduced by 3-10% when switching from low to high stage.

NOTE: 

The liquid pressures are very similar between low-  and high-

stage  operation,  so  liquid  pressure  should  not  be  used  for

troubleshooting.
Compressor current should increase 20 to 45% when switching from low

to  high stage. The compressor  solenoid  when energized in high  stage,

should measure 24vac at the leads inside control box.
When the compressor is operating in low stage, the 24v DC compressor

solenoid coil is de-energized. When the compressor is operating in high

stage, the 24v DC solenoid coil is energized. 
The solenoid plug harness  that is  connected  to the compressor has an

internal rectifier that converts the 24v AC signal to 24v DC. 

DO  NOT  INSTALL  A  PLUG  WITHOUT  AN  INTERNAL

RECTIFIER

.

Unloader Test Procedure:

The unloader is the compressor internal mechanism, controlled by the

DC  solenoid,  that  modulates  between  high-  and  low-stage.    If  it  is

suspected that the unloader is not working, the following methods may

be used to verify operation:

1. Operate the system and measure compressor amperage. Cycle the

unloader  on and off  at 30  second plus intervals  at the thermostat

(from low- to high-stage and back to low-stage). Wait 10 seconds

after  staging  to  high  before  taking  a  reading.  The  compressor

amperage should go up or down at least 20 percent.

2. If step one does not give the expected results, remove the solenoid

plug  from  the  compressor  and,  with  the  unit  running  and  the

Thermostat calling for high-stage, test the voltage output at the plug

with a DC voltmeter. The reading should be 24 volts DC.

3. If  the  correct  DC  voltage  is  at  the  control  circuit  molded  plug,

measure  the  compressor  unloader  coil  resistance.  The  resistance

should be approximately 1640 milliohms. If the coil resistance is

infinite or is grounded, the compressor must be replaced.

Table 3 – Winding Resistance

Winding

Winding resistance at 70°F +/- 20°F

(21.11°C +/- 11.11°C)

Unit Size

24 

 36 

 48 

 60 

Start (S-C)

1.652

1.587

1.299

1.203

Run (R-C)

1.065

0.751

0.477

0.383

Summary of Contents for GA7T

Page 1: ...city 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tubes through the wall seal opening with RTV or other pliable silicon based caulk See Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7 Do not suspend refrige...

Page 2: ...edown Knockout Locations Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Rated tubing diameters shown in Table 1 are recommended up to 80 ft 24 38 m See Product Data for acceptable alternate vapor diameters and associated capacity losses For tubing requirements beyond 80 ft 24 38 m substantial ...

Page 3: ...uum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes See Fig 4 A95424 Fig 4 Deep Vacuum Graph Final Tubing Check IMPORTANT ...

Page 4: ...ass 2 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power requirement Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required Final Wiring Check IMPO...

Page 5: ...e R 410A refrigerant Air Conditioner A09278 A09279 Fig 7 Generic Wiring Diagrams See thermostat Installation Instruction for specific unit combinations A09306 Thermidistat w Variable Speed Fan Coil 2 Stage Air Conditioner Thermidistat w Variable Speed Furnace 2 Stage Air Conditioner Single Stage Furnace with 2 Stage Air Conditioner 2 Stage Thermostat with Single Stage Furnace and 2 Stage Air Condi...

Page 6: ...o the furnace Installation Instructions for details of how to use this feature Airflow Selection for FV4C Fan Coils The FV4C provides high and low stage blower operation to match the capacities of the compressor at high and low stage To select recommended airflow refer to the FV4C Installation Instructions The FV4C utilizes a control board that allows the installing technician to select proper air...

Page 7: ...d then be appropriate for the system to achieve rated capacity The charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range NOTE If line length is beyond 80 ft 24 38 m or greater than 20 ft 6 10 m vertical separation See Long Line Guideline for special charging requirements Final Checks IMPORTANT Before leaving job be sure to do...

Page 8: ... an internal pressure relief IPR which relieves discharge gas into compressor shell when differential between suction and discharge pressures exceed 550 625 psi The compressor is also protected by an internal overload attached to motor windings Compressor Control Contactor The contactor has a 24 volt coil and is controlled by Y1 input from the thermostat CARE AND MAINTENANCE For continuing high pe...

Reviews: