13
Table 1 — Drive Assembly and Power Module Ratings (LF-2 VFD)
*110% output current capability for one minute, 150% output current for 5 seconds.
Table 2 — Drive Assembly and Power Module Ratings (Std Tier VFD)*
*All voltage and current combinations listed may not be available for sale. Please review Carrier Marketing literature for latest offering.
†110% output current capability for one minute, 150% output current for 5 seconds.
** Last character 0 indicates refrigerant-cooled; last digit A indicates air-cooled.
CARRIER PART NUMBER
VFD
FRAME SIZE
ENCLOSURE
TYPE
INPUT
VOLTAGE (V)
RANGE
MAX INPUT
CURRENT
(AMPS)
MAX OUTPUT
CURRENT* AT 4 kHz
(AMPS)
23XRA2AA_ _ _ _ _ _ _ _ _ _ _
Frame 2AA
NEMA 1
380 to 460
440
440
23XRA2BA_ _ _ _ _ _ _ _ _ _ _
Frame 2BA
NEMA 1
380 to 460
520
440
23XRA2BB_ _ _ _ _ _ _ _ _ _ _
Frame 2BB
NEMA 1
380 to 460
520
520
23XRA2CC_ _ _ _ _ _ _ _ _ _ _
Frame 2CC
NEMA 1
380 to 460
608
608
CARRIER PART NUMBER
ENCLOSURE
TYPE
INPUT VOLTAGE
(DIGIT Y OF PART
NUMBER)
MAX INPUT
CURRENT
(AMPS)
MAX OUTPUT
CURRENT† AT 2 kHz
(AMPS)
Y
VOLTAGE/HZ
23XVR0_ _ _00Y _ _ F0**
(R = ROCKWELL)
NEMA 1
3
4
5
7
9
380v / 60 Hz
416v / 60 Hz
416v / 60 Hz
575v / 60 Hz
400v / 50 Hz
230
335
445
230
335
445
23XVE0_ _ _00Y _ _ F0
(E = EATON)
485
550
605
485
550
605
Summary of Contents for EVERGREEN 23XRV
Page 53: ...53 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown NOTE See Notes for Fig 60 on page 56 ...
Page 54: ...54 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown cont a23 1585 ...
Page 55: ...55 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown cont a23 1586 ...
Page 60: ...60 Fig 63 23XRV Controls Schematic LF 2 ...
Page 64: ...64 FROM PREVIOUS PAGE Fig 67 23XRV Controls Schematic Rockwell Standard Tier VFD Shown cont ...