Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53480393-01

Printed in U.S.A.

Form IIK-CRECOMZR87-01

Pg 1 

3-22

Replaces: NEW

Installation Instructions

Part No. CRECOMZR087A00

* The EconoMi$er2 assembly does not include an economizer controller.

SAFETY CONSIDERATIONS

Installation of this accessory can be hazardous due to system
pressures, electrical components, and equipment location (such as
a roof or elevated structure). Only trained, qualified installers and
service technicians should install, start-up, and service this
equipment. 
When installing this accessory, observe precautions in the
literature, labels attached to the equipment, and any other safety
precautions that apply:

Follow all safety codes

Wear safety glasses and work gloves

Use care in handling and installing this accessory

It is important to recognize safety information. This is the safety-
alert symbol: 

. When you see this symbol on the unit and in

instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the safety-
alert symbol. DANGER identifies the most serious hazards which

will

 result in severe personal injury or death. WARNING signifies

hazards which 

could

 result in personal injury or death. CAUTION

is used to identify unsafe practices, which 

may

 result in minor

personal injury or product and property damage. NOTE is used to
highlight suggestions which 

will

 result in enhanced installation,

reliability, or operation.

 GENERAL

The EconoMi$er2 system utilizes the latest technology available
for integrating the use of free cooling with mechanical cooling for
rooftop units.
This system utilizes gear-drive technology with a direct mount
spring return actuator that will close upon loss of power. The
EconoMi$er2 system comes standard with an outdoor air
temperature sensor. Field-installed CO

2

 sensors are available.

Separate barometric relief dampers provide natural building
pressurization control. An optional power exhaust system is
available for applications requiring even greater exhaust
capabilities.
EconoMi$er2 accessories require a 4 to 20 mA actuator signal
control. These accessories do not include a controller. The
EconoMi$er2 actuator is operated by a 4 to 20 mA signal from an
existing field-supplied DDC controller. See Table 1 for package
contents and Fig. 1 for EconoMi$er2 component locations. See
Table 2 for accessories list and Table 3 for sensor usage.

ACCESSORIES AND COMPLIANCE

Accessories List

The EconoMi$er2 system has several field-installed accessories
available to optimize performance. Refer to Table 2 for authorized
parts and power exhaust descriptions.

Table 1 — Package Contents

PART NUMBER

QTY

CONTENTS

CRECOMZR087A00

1

Hood Assembly

1

Filter Access Door

1

Aluminum Filter

18

Screws

1

EconoMi$er2 Assembly*

1

Barometric Relief Hood 

Assembly

1

Hood O/A Panel 

1

O/A Panel Access Door

1

O/A Small Blank Off

1

O/A Large Blank Off

1

R/A Small Blank Off

1

R/A Large Blank Off

IMPORTANT: Read these instructions completely before
attempting to install the horizontal EconoMi$er2 accessory.

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury and/
or death.
Disconnect power supply and install lockout tag before
attempting to install the accessory.

Table 2 — EconoMi$er2 Field-Installed Accessories

PART NUMBER

DESCRIPTION

CRPWREXH028A01

Small And Large Cabinet Power 
Exhaust 208-230v 1Ph

CRPWREXH029A01

Small And Large Cabinet Power 
Exhaust 460-v 3Ph

33ZCT55SPT

Return Air Dry Bulb

CRHUMDSN001B00

or

33CSENTHSW

Outdoor Air Enthalpy Sensor

CRHUMDSN001B00

or

33CSENTSEN

Return Air Enthalpy Sensor

33ZCSENCO2

CO

2

 Room Sensor

33ZCASPCO2

Aspirator Box For Duct Mount 
CO

2

 Sensor

33ZCT55CO2

Space Temperature And CO

2

 

Room Sensor With Override

33CZT56CO2

Space Temperature And CO

2

 

Room Sensor With Override 
And Setpoint

Small Rooftop Units

Accessory Horizontal Ultra-Low Leak

EconoMi$er2

7-1/2 to 12-1/2 Tons

Summary of Contents for EconoMiser2 CRECOMZR087A00

Page 1: ... outdoor air temperature sensor Field installed CO2 sensors are available Separate barometric relief dampers provide natural building pressurization control An optional power exhaust system is available for applications requiring even greater exhaust capabilities EconoMi er2 accessories require a 4 to 20 mA actuator signal control These accessories do not include a controller The EconoMi er2 actua...

Page 2: ...of the economizer then attach using provided screws See Fig 4 8 Remove and save the 12 pin jumper plug from the unit wir ing harness located in the upper left corner of the unit Insert the EconoMiSer2 plug into the unit wiring harness See Fig 5 Refer to page 5 for wiring diagram NOTE The 12 pin jumper plug should be saved for future use in the event that the EconoMiSer2 assembly is removed from th...

Page 3: ...rometric relief hood on field installed R A duct ensuring it is water tight See Fig 8 14 Check all wiring for safety then reapply power to the unit Verify correct operation and setting of the accessory Refer to page 5 for unit wiring diagram 15 Install the filter by opening the filter clips which are located underneath the hood top Insert the aluminum filter into the bottom filter rack hood divide...

Page 4: ...od Filler Panel Filter Access R A Blank Off Panel Attach R A blank off using 4 screws provided Ductwork not shown B A HOOD ALUMINUM FILTER FILTER CLIP Relief Air Outside Air Cleanable Aluminum Filter Wires Back To Economizer Right Hood Side Left Hood Side Economizer Hood Hole In Hood Side OAT Sensor RELOCATE OUTSIDE AIR TEMPERATURE SENSOR Sensor attaches to the right hood side on horizontal econom...

Page 5: ... Violet Pink Orange White Yellow Outside Air Temperature Sensor 500 Ohm Resistor White Green Black Red Actuator Assembly Direct Drive Actuator NOTE The control signal will come from the unit controller harness See specific unit controller documentation for its Installation or when using a relative humidity sensor EconoMi er Plug ...

Page 6: ...ation requirements Fig 12 Barometric Flow Capacity Fig 13 Return Air Pressure Drop 0 1000 2000 3000 4000 5000 6000 7000 8000 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Relief Flow cfm cfm RETURN DUCT STATIC PRESSURE in wg 0 1000 2000 3000 4000 5000 6000 7000 0 0 05 0 1 0 15 0 2 0 25 0 3 0 35 0 4 RETURN AIR FLOW cfm cfm RETURN AIR PRESSURE DROP in wg ...

Page 7: ......

Page 8: ...the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480393 01 Printed in U S A Form IIK CRECOMZR87 01 Pg 8 3 22 Replaces NEW Carrier 2022 ...

Reviews: