CRTWOPOS007A00

CRTWOPOS008A00

Installation Instructions

48/50PD05–06, 48/50PG03–14

TWO---POSITION DAMPER ACCESSORY

SINGLE PACKAGE ROOFTOP UNITS

IMPORTANT

: Read these instructions completely before

attempting to install the accessory two--position damper

SAFETY CONSIDERATIONS

Installation and servicing of air--conditioning equipment can be

hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or

service air--conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations

should be performed by trained service personnel. When working
on air--conditioning equipment, observe precautions in the

literature, tags and labels attached to the unit, and other safety

precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use

quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and

CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies a hazard
which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

PACKAGE CONTENTS

QTY

CONTENTS

1

Hardware Bag

1

Bottom Panel

1

Top Panel/Damper Assembly

PACKAGE USAGE

UNIT

48/50PD

48/50PG

PART NUMBER

SHIPPING

WEIGHT (lb)

03-07

CRTWOPOS007A00

65

08-14

CRTWOPOS008A00

85

GENERAL

The accessory two-position damper is designed for use on units
without economizers.
The two-position damper accessory allows the unit to control the
outside-air dampers by opening the dampers whenever the indoor

fan is operating and closing the dampers when the indoor fan is off.

There is no modulation associated with the two-position damper
assembly.

INSTALLATION

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Turn off unit power supply and install lockout tag.

!

WARNING

To install the two-position damper, perform the following:

1. Make sure power supply is turned off and lockout tag is

installed.

2. Unscrew and remove the front cover panel on the return end

of the unit to expose the return section of the unit. (See Fig.

1.) Discard panel and save screws.

3. Install the bottom panel over the return air compartment.

Use screws saved from Step 2. (See Fig. 1.)

4. Connect the plug from the two-position damper actuator to

the 6-pin economizer/two-position damper plug in the

return air compartment of the unit. (See Fig. 1 and 2.)

5. Adjust two-position damper to desired setting. Two-

position damper performance is shown in Fig. 3 and 4. To

adjust damper, locate the adjustable stop on the actuator.
Loosen but do not remove the screw. Align pointer with

desired setting based on the return duct static pressure and
airflow. Tighten screw.

6. Install the top panel assembly over the top section of the

return air compartment. The top panel assembly should
overlap the bottom panel installed in Step 3. Use screws

provided. (See Fig. 1.)

7. Remove lockout tag and restore power to unit.