background image

Cancels: New

IIK 548-36-14

9/1/94

Installation and Operating Instructions

Part Number CRSTATUS001A00

PACKAGE USAGE AND CONTENTS

PART NUMBER

QUANTITY

ITEM

LF32GF097

1

Plastic Cap

AL48AM217

2

Screws

50HJ500288

1

Control Tube (16 in.)

50HJ500301

1

Control Tube (32 in.)

HK06WC027

1

Pressure Switch

IMPORTANT: Read these instructions completely be-
fore attempting to install the accessory fan/filter status
switch.

INSTALLATION

NOTE: The fan/filter status switch can be installed to moni-
tor indoor fan status (ON/OFF) or filter status (CLEAN/
DIRTY). Follow the procedure below and perform the steps
necessary to install the pressure switch for the desired
application (as either a fan status switch or a filter status
switch, but not both).

Turn off unit power. Electrical shock and personal in-
jury could result.

1. Remove the filter access door. No tools are required. Save

door.

2. Remove the pressure switch assembly from the carton.

Attach the 32-in. plastic control tube to the pressure switch
on the port nearest to the electrical connections. See
Fig. 1.

3. Filter Switch

Attach the 16-in. plastic control tube to the pressure switch
on the port nearest to the mounting bracket. See Fig. 1.
Fan Switch
Attach the plastic cap to the pressure switch on the port
nearest to the mounting bracket. See Fig. 1.

4. Attach the pressure switch assembly to the uppermost

portion of the inner flange of the corner post with 2 screws
provided. See Fig. 1.

5. Route the 32-in. control tube through the slot in the coil

baffle next to the harness assembly. The end should be
loose in the indoor fan area. See Fig. 1.

6. Filter Switch

Suspend the 16-in. tube over the return air opening. See
Fig. 1.

7. Connect the 2 gray wires routed with the economizer

wiring harness assembly to the terminals on the pres-
sure switch. See Fig. 2.

Fig. 1 — Fan/Filter Status Switch Installation

(Top View of Typical Rooftop Unit Shown)

Small Rooftop Units

Gas Heating/Electric Cooling

and Electric Cooling Units

3 to 12

1

2

Tons (50/60 Hz)

Accessory Fan/Filter Status Switch

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

1

1

4

4

4

Tab

1a 1b 5a 5a 6a 6b

PC 111

Catalog No. 564-809

Form 48/50-28SI

Pg 1

9-94

Replaces: New