background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53480202-01

Printed in U.S.A.

Form IIK-CRECOMZR67-04

Pg 24 

11-18

Replaces: IIK-CRECOMZR67-03

© Carrier Corporation 2018

TROUBLESHOOTING

For a list of common operating issues and concerns see Ta-

ble 15.

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restored after any

power loss or interruption, as all settings are stored in the

economizer controller’s non-volatile flash memory.
NOTE: If power goes below 18 Vac, the W7220 module as-

sumes a power loss and the 5-minute power up delay will be-

come functional when power returns above 18 vac.

Alarms

The economizer module provides alarm messages that dis-

play on the 2-line LCD.
NOTE: Upon power up, the module waits several seconds be-

fore checking for alarms. This allows time for all the configured

devices (e.g. sensors, actuator) to become operational.

If one or more alarms are present and there has been no

keypad activity for at least 5 minutes, the Alarms menu dis-

plays and cycles through the active alarms.

The Alarms menus can be navigated at any time. See Ta-

ble 11 for the Alarms menu.

Clearing Alarms

Once the alarm has been identified and the cause has been

removed (e.g. replaced faulty sensor). They can be cleared

from the display.

To clear an alarm, perform the following: 

1. Navigate to the desired alarm. 
2. Press the 

 button. 

3. ERASE? displays. 
4. Press the 

 button. 

5. ALARM ERASED displays. 
6. Press the 

 (Menu Up/Exit) button to complete the

action and return to the previous menu.

NOTE: If the alarm still exists after being cleared, it will redis-

play within 5 seconds.

 

Table 15 — Operating Issues and Concerns

ISSUE OR CONCERN

POSSIBLE CAUSE AND REMEDY

My outdoor temperature reading on the

STATUS menu is not accurate

Check the sensor wiring:

•  Enthalpy sensors are to be wired to the S-Bus terminals.

•  Temperature sensors are to be wired to the OAT and MAT terminals.

If my enthalpy sensor drifts in accuracy over time, can I 

recalibrate it?

The sensor cannot be re-calibrated in the field; however, a menu item under the 

ADVANCED menu allows input of a limited offset in temperature and humidity for each 

sensor connected to the economizer.

Will I be able to see the LCD screen when it is in the unit?

The LCD screen has a backlight that is always illuminated.

What is a good setpoint for the Mixed Air Temperature (MAT)?

The mixed air temperature is the temperature of air to supply to the space. In a 

commercial building, this is between 50 and 55°F (10 to 13°C). The mixed air is the 

mixing of the return air and the outdoor air.

I am using enthalpy sensors. Why did the control ask me to 

input a dry bulb changeover temperature?

In the event the humidity sensor in the enthalpy sensors fails, the backup algorithm in 

the control is to default to the temperature sensor in the enthalpy sensor.

In checkout, the outdoor damper closes when I command it to 

open.

Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper 

should drive open or closed with the return air damper having the opposite effect.

How do I set my minimum position when using a CO

2

 sensor?

The minimum position is set using the VENTMIN and VENTMAX setup in the 

SETPOINTS menu. VENTMIN is the minimum ventilation required when using an 

occupancy sensor and VENTMAX is the minimum ventilation when not using an 

occupancy sensor for Demand Controlled Ventilation. The VENTMAX position is set 

the same as with the potentiometer on the analog economizers and is the output 

voltage to the damper actuator. The range is 2 Vdc closed OA damper and 10 Vdc 

open OA damper.

What if my damper does not go completely closed in the 

checkout operation?

Check the damper linkage or hub to make sure the damper is able to close completely.

Does the economizer save my program values if the unit 

loses power?

Yes, once the changes are stored in the controller they will be stored until they are 

changed by the operator.

If the unit is left in checkout, how long will the unit stay in 

checkout mode without input?

The unit will remain in checkout for 10 minutes, then return to normal operation.

Summary of Contents for CRECOMZR067A01

Page 1: ...safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the poten tial for personal injury Understand the signal words DANGER WARNING CAU TION and NOTE The...

Page 2: ...8 50TC 04 07 CRECOMZR067A01 Large Cabinet 48 50HC 07 12 48 50LC 07 48 50TC 08 14 50HCQ 07 09 50TCQ 08 12 CRECOMZR069A01 Extra Large Cabinet 48 50HC 14 48 50LC 08 12 48 50TC 16 50HCQ 12 50TCQ 14 CRECOM...

Page 3: ...base in the re turn air chamber See Fig 4 Table 5 EconoMi er X Sensor Usage APPLICATION ECONOMI ER X WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required Outdoor Air Dry Bulb HH79AH001 outdoor air dr...

Page 4: ...Harness to Unit PL6 Economizer Harness 8 Remove and save the 12 pin jumper plug from the unit economizer harness located in the upper left corner of the unit Insert the EconoMi er X plug into the unit...

Page 5: ...ee Fig 9 and page 9 Fig 9 Connect 10 pin Plugs Together 13 Connect the 10 pin female plug from the Jade controller harness to ECON on the CTB See Fig 10 and page 9 Fig 10 Connect 10 Pin Jade Plug to C...

Page 6: ...box and the indoor blower section See Fig 14 Fig 14 Route 48TMHSRSE A20 Harness to Indoor Blower Section Some control box configurations may differ 19 Screw the HH79AH001 mixed air MAT sensor Hon eywe...

Page 7: ...ween the filters Fig 17 EconoMi er X Hood Assembly Fig 18 Filter Divider on CRECOMZR071A01 Hood 23 Install aluminum filter s in EconoMi er X hood Clips at top of hood will hold filters in place See Fi...

Page 8: ...2 See base unit installation manual to make adjustments to meet building ventilation requirements See Fig 23 for typi cal EconoMi er X wiring diagram Fig 21 Barometric Relief Flow Capacity Fig 22 Retu...

Page 9: ...RA ORG YEL BLK BRN RED VIO 1 1 2 2 3 3 4 10 6 4 5 9 1 3 8 2 7 1 2 3 4 5 6 7 8 9 10 4 9 3 8 10 2 6 7 5 1 4 10 Pin Female Plug Disconnected from CTB CO2 Optional Ground W1 on CTB W7220 JADE Controller F...

Page 10: ...oller NOTE The 4 wire 48TMHSRSE A20 harness provided with the economizer will also NOT be used on the 48 50LC07 12 units see Fig 25 Fig 25 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units 3 Step LC3 The...

Page 11: ...of Fig 26 on the 48LCHSRADH A00 harness attach to the unit s CSC board Connect J3 and J5 plugs to the CSC board 7 Step LC7 Screw the green wire with yellow stripe in the 48LCHSRADH A00 harness to the...

Page 12: ...d is 48LCHSRADH A00 harness which is shipped in the control box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220...

Page 13: ...wires with a plug from the EconoMi er X har ness in the return chamber plug directly into the HH57AC081 enthalpy sensor See Fig 23 and 28 for wiring Fig 29 Enthalpy Curve Boundaries Fig 30 HH57AC081...

Page 14: ...ive Director At altitudes substantially different than sea level the Fixed Enthalpy limit value shall be set to the enthalpy value at 75 F and 50 rela tive humidity As an example at approximately 6 00...

Page 15: ...acceptable to some codes is an an nunciator light visible by service personnel See Fig 34 for typical wiring to the Jade controller Refer to codes for proper labeling of light Fig 33 Thermostat Wired...

Page 16: ...nt menu parameter 10 Press the Menu Up Exit button to return to the pre vious menu Menu Structure Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi er X system The me...

Page 17: ...10 Standard Jade W7220 Controller Configuration for 1 or 2 Speed Unit CONTROLLER MENU ITEM FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS NOTE DEFAULT SET TO DEFAULT SET TO SETPOINTS MAT SET 53 F 38 to 70 F...

Page 18: ...d displays measured discharge temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMPERATURE Displays m...

Page 19: ...t and 2 cool then set for LOW SPEED COOLING ventilation MIN POS M 5 4V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT MEDIUM SPEED Only displays if unit is set for 3 speed with 1 heat and 2 cool and CO2...

Page 20: ...ON Damper position when freeze protection is active CLO closed MIN MIN POS or VENTMIN CO2 ZERO 0 ppm 0 to 500 ppm increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000 ppm 1000 t...

Page 21: ...A Positions damper to the fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1O N A N A Energizes the AUX1O output If Aux...

Page 22: ...to Minimum Damper po sition if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan motors will be energized by the economizer control as...

Page 23: ...24 V 24 V 0 V Y2 0 V 0 V 0 V 24 V 0 V W1 0 V 0 V 0 V 0 V 24 V SUPPLY FAN MOTOR SPEED SUPPLY FAN MOTOR SPEED OFF LOW LOW HIGH HIGH DAMPER POSITION No CO2 Sensor CLOSED MIN POS L MIN POS L MIN POS H MI...

Page 24: ...ls If my enthalpy sensor drifts in accuracy over time can I recalibrate it The sensor cannot be re calibrated in the field however a menu item under the ADVANCED menu allows input of a limited offset...

Reviews: