21
LEGEND
* Table 11 illustrates the complete hierarchy. The menu parameters
may be different depending on the configuration. For example, if
there is no DCV (CO
2
) sensor, then none of the DCV parameters
appear.
† When values are displayed, pressing and holding the
▲
or
▼
button
causes the display to automatically increment.
** N/A = Not Applicable.
†† ERV Operation: When in cooling mode AND the conditions are
NOT OK for economizing - the ERV terminal will be energized. In
the Heating mode, the ERV terminal will be energized when the OA
is below the ERV OAT setpoint in the setpoint menu.
Checkout Tests
Use the Checkout menu (see Table 11) to test the damper
operation and any configured outputs. Only items that are
configured are shown in the Checkout menu.
NOTE: See User Interface for information about menu naviga-
tion and use of the keypad.
1. To perform a Checkout test:
2. Scroll to the desired test in the Checkout menu using the
▲
and
▼
buttons.
3. Press the
button to select the item.
4. RUN? appears.
5. Press the
button to start the test.
6. The unit pauses and then displays IN PROGRESS.
7. When the test is complete, DONE appears.
8. When all desired parameters have been tested, press the
(Menu up) button to end the test.
Checkout test can be performed at any time during the op-
eration of the system as a test that the system is operable.
CHECKOUT
DAMPER VMIN-HS
N/A
N/A
Positions OA damper to VMIN High Speed position
DAMPER VMAX-HS
N/A
N/A
Positions OA damper to VMAX High Speed position
DAMPER OPEN
N/A
N/A
Positions OA damper to the full open position.
DAMPER CLOSE
N/A
N/A
Positions damper to the fully closed position
CONNECT Y1-O
N/A
N/A
Closes the Y1—O relay (Y1—O)
CONNECT Y2-O
N/A
N/A
Closes the Y2—O relay (Y2—O)
CONNECT AUX1O
N/A
N/A
Energizes the AUX1O output. If Aux setting is:
• NONE= not action taken
• ERV = 24 Vac out. Turns on or signals an ERV that the conditions are not
good for economizing but are for ERV operation††
• SYS = 24 Vac out. Issues a system alarm
Alarms display only when they are active. The menu title “ALARMS(_)” includes the number of active alarms in parenthesis ( ).
ALARMS(_)
MA T SENS ERR
N/A
N/A
MIXED AIR TEMPERATURE SENSOR ERROR
CO2 SENS ERR
N/A
N/A
CO2 SENSOR ERROR
OA T SENS ERR
N/A
N/A
OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected at input terminals OAT
OA SYLK SENS ERR
N/A
N/A
OUTSIDE AIR ENTHALPY SENSOR ERROR
OAT sensor connected on S—bus
DA T SENS ERR
N/A
N/A
DISCHARGE AIR TEMPERATURE SENSOR ERROR
SYS ALARM
N/A
N/A
When AUX1-0 is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX1-0 terminal has 24 Vac out.
ACT UNDER V
N/A
N/A
ACTUATOR VOLTAGE LOW
Voltage received at actuator is below expected range
ACT OVER V
N/A
N/A
ACTUATOR VOLTAGE HIGH
Voltage received at actuator is above expected range
ACT STALLED
N/A
N/A
ACTUATOR STALLED
Actuator stopped before reaching commanded position.
Table 11 — Menu Structure*(cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT†
NOTES
LCD
— Liquid Crystal Display
MAT
— Mixed Air Temperature
OAT
— Outdoor Air Temperature
OCC
— Occupied
RAT
— Return Air Temperature
RTU
— Rooftop Unit
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to
equipment.
Be sure to allow enough time for compressor startup and
shutdown between checkout tests so that you do not short-
cycle the compressors.