Small Packaged Products

Standard Altitude Only 0–2000 ft

Accessory LP Conversion Kit

Installation Instructions

60,000–130,000 Btu/hr

Part Number: CPLPCONV006A00 2 to 5 Tons

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

SAFETY CONSIDERATIONS

Installing and servicing air conditioning equipment can be hazard-
ous due to system fuels. Only trained and qualified personnel
should install, service, or repair air conditioning equipment.

Untrained personnel can perform basic maintenance functions
such as cleaning coils, or cleaning and replacing filters. All other
operations should be performed by trained service personnel.
When working on air conditioning equipment, observe precautions
in the literature, on tags, and on labels attached to the unit.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.

Follow all safety codes. Wear safety glasses and work gloves.
Have a fire extinguisher available.

Before converting a unit to LP, remove the burner assembly
and inspect the heat exchanger tubes. If there are V-shaped
NOx baffles installed in the firing tubes (See Fig. 1). THEY
MUST BE REMOVED PRIOR TO CONVERTING
THIS UNIT TO LP. 
Discard the baffles after removal.

This conversion kit is to be installed by qualified service
personnel in accordance with these instructions and all codes
and requirements of the authority having jurisdiction, and in
Canada, in accordance with the requirements of the
CAN/CGA (Canadian Gas Association) B149.2 Installation
Code. Failure to follow these instructions could result in
serious injury, property damage or death. The qualified
agency performing this work assumes responsibility for this
conversion.

This unit is designed to operate at 3.5 in. wg (±0.3 in. wg) of
manifold pressure with liquid propane (LP) gas. Exceeding
this pressure may result in explosion, injury or death.

INTRODUCTION

These instructions cover the installation of a liquid propane
conversion kit on models 48GS, 582A, PY1P-B, 48GX, 583A,
PY2P-B, 48GP, and 583B that are equipped with a White Rodgers
combination automatic gas valve regulator.

DESCRIPTION AND USAGE

This kit is applicable to units with heating inputs from 60,000 to
130,000 Btu/hrinstalled at standard altitudes from 0 ft to 2000 ft.
It cannot be used for high altitude installations or on units with
heating inputs of 40,000 Btu/hr. High altitude conversions
(2001–6000 ft) should use kit #CPLPCONV007A00. All conver-
sions

of

40,000

Btu/hr

units

should

use

Kit

#CPCLPCONV008A00 (applicable for any altitude from 0 ft to
6000 ft).

INSTALLATION

Before performing service or maintenance operations on unit,
turn off gas supply first, then the main power switch to unit.
Electrical shock could cause serious injury or death. TAG
DISCONNECT SWITCH WITH SUITABLE WARNING
LABEL.

1. Turn off gas supply first, then power to unit.

2. Remove the front access panel from unit.

3. Disconnect the gas pipe from the gas valve.

4. Disconnect orange sparker cable at the ignition control.

Fig. 1–Low NOx Baffle Location

C00151

Firing Tube

NOx Baffle

Cancels: IIK 582A-18-6

IIK 582A-18-7

1-01

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

1a 1a

PC 101

Catalog No. 534-80021

Printed in U.S.A.

Form 48-15SI

Pg 1

1-01

Replaces: 48-14SI

Summary of Contents for CPLPCONV006A00

Page 1: ...t is to be installed by qualified service personnel in accordance with these instructions and all codes and requirements of the authority having jurisdiction and in Canada in accordance with the requirements of the CAN CGA Canadian Gas Association B149 2 Installation Code Failure to follow these instructions could result in serious injury property damage or death The qualified agency performing th...

Page 2: ... valve Reconnect the brown wire to terminal 2 C2 on the main gas valve 15 Reconnect orange sparker cable and the yellow flame sensor wires at the ignition control 16 Slide burner rack assembly into basepan Align burner rack with screws on sheet metal partition and slide assembly back tight to the partition Replace the screw attaching the burner rack to the basepan removed in Step 8 17 Reconnect th...

Page 3: ...TO MODELS WITH HEATING INPUT OF 57 000 BTUH AND HIGHER FOR 40 000 BTUH MODELS USE KIT CPLPCONV008A00 024060 030060 036060 042060 57 000 2 4 0 13 0 3 5 LH32RF080 No 46 THIS KIT APPLIES TO STANDARD ALTITUDE INSTALLATIONS ONLY ABOVE 2000 FT USE HIGH ALTITUDE LP CONVERSION KIT CPLPCONV007A00 036090 042090 048090 060090 85 500 3 4 0 13 0 3 5 LH32RF080 No 46 048115 060115 115 000 3 4 0 13 0 3 5 LH32RF09...

Page 4: ...URNER 2 BURNER RACK SPARKER GAS VALVE ORIFICE 2 FLAME SENSOR MANIFOLD 57 000 BTUH UNITS CLOSED END PIPE PLUG CLOSED END BURNER 3 BURNER RACK SPARKER GAS VALVE FLAME SENSOR ORIFICE 3 MANIFOLD 85 500 BTUH TO 127 000 BTUH UNITS PIPE PLUG CLOSED END 4 ...

Page 5: ...APPLIANCE HAS BEEN CONVERTED TO LP GAS KIT NO _______________________ BY _______________________ DATE ________ WHO ACCEPTS THE RESPONSIBILITY FOR THE CORRECTNESS OF THIS CONVERSION 48SS500283 Fig 4 Burner Bracket C00150 ROLLOUT SWITCH BURNER BRACKET 5 ...

Page 6: ...6 ...

Page 7: ...7 ...

Page 8: ...Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 1a 1a PC 101 Catalog No 534 80021 Printed in U S A Form 48 15SI Pg 8 1 01 Replaces 48 14SI ...

Reviews: