ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
30
Wiring and DIP switch configurations 13 to 16 – AC systems
Outputs
Config. 13:
HC21
2/3 Speeds fan
(1)
Humidifier, Dehum/
Reheat for Dehumidif
Config. 14:
HP21
2/3 Speeds fan
(1)
,
Humidifier, Dehum/
Reheat for Dehumidif
Config. 15:
HC22
1 Speed fan, Economizer,
Humid, Dehum/ Reheat
for Dehum
Config. 16:
HP32
1 Speed fan, Economizer,
Humid, Dehum / Reheat
for Dehum
11
Fan high
Fan high
Heat element 2
(2nd stage heat)
Heat element
(3rd stage heat)
12
Fan medium
(or Economizer
(5)
)
Fan medium
(or Economizer
(5)
)
Economizer
Economizer
13
Fan low
Fan low
Fan (1 speed)
Fan (1 speed)
14
Heat element 2
(2nd stage heat)
Heat element
(2nd stage heat)
Compressor 2
(3)
Compressor 2
(3)
15
Compressor
(3)
Compressor
(3)
Compressor 1
(3)
Compressor 1
(3)
16
Heat element 1
(2)
(1st stage heat)
Heat pump
(2)
Heat element 1
(2)
(1st stage heat)
Heat pump
(2)
AO1
Humidifier
Humidifier
Humidifier
Humidifier
AO2
Dehumidifier
(4)
(option - See SW2.3)
Dehumidifier
(4)
(option - See SW2.3)
Dehumidifier
(4)
(option - See SW2.3)
Dehumidifier
(4)
(option - See SW2.3)
SW1
SW2
(1)
SW1.1, SW1.2 – Fan speeds:
2 speeds (Low and High):
3 speeds (Low, Med., and High):
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 – HP (Heat pump):
HC (not heat pump):
ON = Heat pump active in cool, OFF = Heat pump active in heat
ON = Electrical heater, OFF = Oil/Gas heater (no fan)
(3)
SW1.5 – Compressor delay:
ON = Disable, OFF = Enable
(4)
SW2.3 – Dehumidification:
ON = Use dehumidifier
OFF = Use reheat for dehumidification
(5)
SW2.6 – Terminal 12 operation: ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
See drawing in
Wiring terminals and DIP switches
(page 23) for DIP switch locations.
Fan on/off: 110-230 Vac, 2.5A max.
Humidifier, Dehumidifier: 0-10 Vdc, 0.5 mA Not isolated
Control – Heat elements, Heat pump, Compressors, Economizer: 110-230 Vac, 0.3A max.
Summary of Contents for ComfortVu Plus TBPL-H
Page 70: ......
Page 71: ...CARRIER CORPORATION 2020 Catalog No 11 808 706 01 4 7 2020 ...