915SB: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
20
A11437
Fig. 26 – Optional Media Cabinet Accessory
A150580
NOTE:
Local codes may require a drain pan and condensate trap when
a condensing furnace is installed over a finished ceiling.
Fig. 27 – Working Platform for Attic Installation
A150581
NOTE:
Local codes may require a drain pan and condensate trap when
a condensing furnace is installed over a finished ceiling.
Fig. 28 – Suspended Furnace Installation
14-3/16 and 17-1/2-in.
Furnace
16-in. Media Cabinet
21-in. Furnace
4-Ton or less, AC
capacity airflow
20-in. Media Cabinet
4-in.
Block Off
Plate
1/2-in.
Screws
20- or 24-in. Media
Cabinet
Bottom Return Plenum
21- or 24-1/2-in.
Furnace
Up to 5-Ton AC
capacity airflow
45
°
Transition
20- or 24-in. Media Cabinet
Screw
14-3/16-in. Furnace
Filler plates
Screw
14--3/16-in. Furnace with Filler Plates, Centered
14-3/16-in. Furnace
Filler plate
Screws
14--3/16-in. Furnace with Filler Plates, Off--Set to Right
Media Cabinet Installation Option for
4-Ton or Less A/C Capacity
20- or -24-in. Media Cabinet Installation
with Angled Transition
20- or -24-in. Media Cabinet Installation
for Combination Side and Bottom Return
Media Cabinet Installation
Side Return
21-in. Furnace
up to 5-Ton AC
Capacity
24-1/2-in. Furnace
up to 4-Ton AC
Capacity
2-IN.
(51 mm)
ROLLOUT PROTECTION REQUIRED
Install 12” x 22” (305x559 mm) sheet metal in front of burner compartment
area. The sheet metal MUST extend underneath the furnace casing by 1-in.
(25 mm) with the door removed. The bottom closure panel may be used for
flame roll-out protection when bottom of furnace is used for return air connection.
30 IN. (762 mm)
MIN. WORK AREA
COMBUSTION - AIR PIPE
(SEE VENTING SECTION)
2-IN.
(51 mm)
COMBUSTION-AIR PIPE
(SEE VENTING SECTION)
Install 12” x 22” (204 x 559 mm) sheet metal in front of and above the burner compartment area.
The sheet metal MUST extend above the furnace casing by 1-in. (25 mm with the door removed.
A 1-in. (25 mm) clearance minimum between top of furnace and combustible material is required.
The entire length of furnace must be supported when furnace is used in horizontal position to
ensure proper drainage.
NOTE: FURNACE SHOWN IS A DIRECT-VENT APPLICATION. REFER TO THE VENTING SECTION FOR
ALLOWABLE VENT CONFIGURATIONS.
ROLLOUT PROTECTION REQUIRED