Page 1: ...tandby Generators Models ASPASICCA007 6 kW NG 7 kW LP ASPASICCA012 12 kW NG 12 kW LP ASPASICCA015 13 kW NG 15 kW LP Not intended for use as Primary Power in place of utility or in life support applica...

Page 2: ...rsonal safety and or property of others _This symbol points out potential explosion hazard _This symbol points out potential fire hazard Z_ This symbol points out potential electrical shock hazard Car...

Page 3: ...llation 8 1 11 The Battery 8 Section 3 Maintenance 12 3 1 Fuses 12 3 2 Checking the Engine Oil Level 13 3 3 Changing the Engine Oil 13 3 4 Changing the Oil Filter 14 3 5 Changing the Engine Air Cleane...

Page 4: ...ator are rotating and or hot during operation Exercise care near running generators For safety reasons Carrier recommends that the installation initial start up and maintenance of this equipment is ca...

Page 5: ...h Administration OSHA has established Also ensure that the generator is installed in accordance with the manufacturer s instructions and recommendations Following proper installation do nothing that m...

Page 6: ...ns 1 Low Oil Pressure Sensor 3 Overcrank 2 High Temperature Sensor 4 Overspeed There are LED readouts on the control panel to notify personnel that one of these faults has occurred There is also a Sys...

Page 7: ...e Cylinder GH 410 Engine Exhaust Enclosure Oil Data Dipsiick Decal Conirol _0 C GFCI Outlet Fuel Fuel Inlel Oil Filler Battery Composite Base Compadrnant Figure 1 2 12 kW and 15 kW V twin GT 990 Engin...

Page 8: ...rangement Ignition System Recommended Spark Plug Spark Plug Gap Compression Ratio Starter Oil Capacity Including Filter Recommended Oil Filter Recommended Air Filter Operating RPM ASPASICCA007 GH 410...

Page 9: ...power lines _The generator s weight of more than 300 pounds requires proper tools equipment and qualified personnel to be used in all phases of handling and unpacking 1 9 2 GENERATOR _lnstall the gene...

Page 10: ...emove the 7 5A and 15A fuses from the generator control panel Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts...

Page 11: ...h which will allow the transfer switch to transfer back to utility power The unit will continue to run for one minute and then shut down 9 Allow the unit to cool 10 Set the generator s main circuit br...

Page 12: ...ator in manual mode This oultlet does not provide power if the generator is not running This outlet is protected by a 15 amp circuit breaker located in the generator control panel Figure 3 1 2 4 SEQUE...

Page 13: ...two at no load to stabilize the internal temperatures 3 Set the generator s AUTO OFF MANUAL switch to its OFF or open position The engine should shut down 4 Check that utility power supply to the tran...

Page 14: ...crank and rest for a preset time limit Then it will stop cranking and the Over Crank LED on the generator control panel will light indicating an over crank failure The AUTO OFF MANUAL switch will need...

Page 15: ...perate continuously for several days the oil level should be monitored frequently A low oil shutdown can occur Section 2 7 1 causing loss of generator power to emergency circuits Figure 3 2 Oil Dipsti...

Page 16: ...e cover and air filter 3 Wipe away dust or debris from inside of the air box and around edges 4 Install the new air cleaner into the air box 5 Install the cover Turn the two cover screws clockwise to...

Page 17: ...observed Wear full eye protection and protective clothing Where electrolyte contacts the skin wash it off immediately with water Where electrolyte contacts the eyes flush thoroughly and immediately w...

Page 18: ...while utility power is available 6 While the engine is still warm from running drain the oil completely Refill the crankcase with oil See Engine Oil Recommendations Section 3 3 1 7 Attach a tag to the...

Page 19: ...if Repair is Needed FUEL Fuel lines and connections X M LUBRICATION Oil level X M Oil X AFTER BREAK IN AND Y Oil filter X AFTER BREAK IN AND Y COOLING Enclosure louvers X X W BATTERY Remove corrosion...

Page 20: ...fective spark plug s 3 Fuel Regulator not set 4 Fuel Pressure incorrect 1 Check replace air cleaner 2 3 4 Clean re gap or replace plug s Set Fuel Regulator Confirm fuel pressure to regulator is 11 14...

Page 21: ...fluid amounts Failures due but not limited to accident misuse abuse negligence or improper installation As with all mechanical devices the Carrier engines need periodic part s service and replacement...

Page 22: ...ny and or all warranty coverage or responsibility if your engine or a part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications or the use of counterfeit...

Page 23: ...repaired or replaced by Generac according to Subsection 4 below Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Per...