Fig. 31 —
WSHP Open DDC Wiring Diagram
1
UNIT TERMINAL BLOCK (TB1) CLASS II VOLTAGE
STANDARD COMPONENTS:
DATS - DISCHARGE AIR TEMP SENSOR
LWTS - LEAVING WATER TEMP SENSOR
OPTIONAL WIRING
J1-9 USED TO CONNECT FIRE ALARM RELAY OR PHASE MONITOR OPTIONS
1
2
2
FACTORY JUMPER IS INSTALLED ON J5-5 AND J5-6 IF CONDENSATE FLOAT
SWITCH (NC) IS NOT PRESENT
3
3
FOR 2-STAGE UNITS, CONNECT CMR CONN ACROSS PINS 4 AND 6 OF CMR1
WITH SIGNAL CMR-4 GOING TO PIN 4 AND SIGNAL CMR-2 GOING TO PIN 6.