background image

GB - 13

61 AF

E N G L I S H

General maintenance, maintenance and final recommendations

General maintenance

ATTENTION:

 Before starting any servicing or maintenance operation on 

the unit, make sure that the power supply has been disconnected.
A current discharge could cause personal injury.

In order to obtain maximum performance from the unit special 
attention should be paid to the following points.

- Electrical connections:

The supply voltage should be within the limits indicated in Table II. 
Ensure that no faulty contacts exist in the terminal blocks, contactor 
boards, etc.
Make sure that all the electrical connections are properly tightened, 
and that all the electrical components (contactors, relays, etc) are 
firmly secured to the corresponding rails. Pay special attention to the 
condition of the connecting cables between the control elements and 
the electrical box, and to that of the unit power supply cable. They 
should not be twisted and there should be no slits or notches in the 
insulation. Check that the starting and running consumptions are within 
the limits specified in Table II.

- Water connections:

Make sure there are no water leaks from the system. Should the unit 
be shutdown for long periods, open the drain valve installed on the 
hydronic module and partially drain the pump and the water pipes 
as well as the drain valve on the plate-type exchanger, which must 
be installed on the hydraulic circuit. This operation is essential if 
temperatures are expected to drop below freezing. If the unit is not 
drained, the main switch should remain connected so that the defrost 
thermostat can operate. 

 

Carefully clean the system water filter.

- Plate heat exchanger cleaning:

In some applications, for example when very hard water is used, there 
is an increased tendency for fouling. In these cases the installation of 
a descaling filter is recommended. The heat exchanger can always be 
cleaned by circulating a cleaning fluid.

A weak acid solution should be used (5% phosphoric acid or, if 
frequently cleaned 5% oxalic acid), and the cleaning fluid should be 
pumped through the exchanger. The tank installation can be permanent 
or, alternatively, the connections can be prepared and, at any given 
time, a portable cleaning device can be connected. To achieve optimum 
cleaning the acid solution should be circulated at a minimum of 1.5 
times the normal operational flow speed, and preferably in reverse 
direction. The installation should then be flushed with large amounts of 
water to totally remove the acid before the system is started up.

Cleaning should be done at regular intervals and should never be left 
until the unit has become blocked. The time intervals between cleaning 
depend on the quality of the water used, but as a general rule it is 
advisable to clean it at least once a year.

- Refrigerant circuit:

Ensure that there is no leakage of refrigerant or oil from the compressor.
Check that the high and low side operating pressures are normal. Check 
the cleanliness of the refrigerant-water heat exchangers by checking the 
pressure drop across them.

- Controls:

Check the operation of all the electrical components, the high 
pressurestat and of the high and low pressure transducers and the 
water, air and defrost temperature detector.

Maintenance

Servicing recommendations

-  Maintenance of the unit must be carried out by skilled personnel 

only. Nevertheless, the easiest operations, such as cleaning of the 
battery and the unit external parts can be carried out by non-skilled 
personnel.

-  For any operation on the unit follow thoroughly the instructions 

shown in the manual and on the unit labels as well as the Safety 
Standards. 
Always wear the protective gloves and safety glasses. Pay attention to 
burns when brazing.

-  Use only Carrier Original Spare Parts when repair is required. Always 

make sure the spare parts are installed correctly. Always install the 
spare parts in the original position. 

-  Before replacing any of the elements in the refrigerating circuit, 

ensure that the entire refrigerant charge is removed from both the 
high and low pressure sides of the unit.

-  The control elements of the refrigerating system are highly sensitive. If 

they need to be replaced, care should be taken not to overheat them 
with blowlamps whilst soldering. A damp cloth should be wrapped 
around the component to be soldered, and the flame directed away 
from the component body.

-  Silver alloy soldering rods should always be used.
-  If the total unit gas charge has to be replaced, the quantity should be 

as given on the nameplate and the unit should be properly evacuated 
beforehand.

-  During unit operation all panels should be in place, including the 

electrical box access panel.

-  If it is necessary to cut the lines of the refrigerant circuit, tube cutters 

should always be used and never tools which produce burrs. All 
refrigerant circuit tubing should be of copper, specially made for 
refrigeration purposes.

Final recommendations

The unit you have purchased has undergone strict quality control 
procedures before leaving the factory.
All components, including the control systems and electrical equipment, 
etc., are certified by our Quality Control Department, and tested 
under the harshest possible operating conditions in our laboratories. 
However, after leaving the factory, it is possible that one or more of 
these elements may be damaged due to causes beyond our control. 
In such an event, 

the user should not work on any of the internal 

components, or subject the unit to operating conditions which are 
not specified in this manual

, since serious damage may result and the 

guarantee would be invalidated. Repair and maintenance work should 
always be left to the installer. All recommendations concerning unit 
installation are intended as a guideline. The installer should carry out 
the installation according to the design conditions and should comply 
with all applicable regulations for air conditioning and refrigeration 
installations.

NOTE: 

The manufacturer does not accept responsibility for any 

malfunctions resulting from misuse of the equipment.

Tank installation

Summary of Contents for AquaSnap 61AF-A

Page 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS 61AF A Nominal cooling capacity 14 20 kW 50 Hz High temperature heat pumps Original document ...

Page 2: ......

Page 3: ...trol circuit fuse_________________________A Main circuit breaker rating______________________________________________________________________________________ PHYSICAL DATA Coil Plate heat exchanger Entering air temp ___________________________ C Entering water temp ____________________ C Leaving air temp ___________________________ C Leaving water temp _____________________ C Pressure drop water _...

Page 4: ...0µPa A weighting Declared dualnumber noise emission values in accordance with ISO 4871 with an associated uncertainty of 3dB A For information calculated from the sound power level Lw A 61AF standard unit Without PUMP With PUMP 014X7 014X9 019X9 014H7 014H9 019H9 Power circuit Nominal power supply V ph Hz 230 1 50 400 3 50 400 3 50 230 1 50 400 3 50 400 3 50 Voltage range V 207 253 360 440 360 440...

Page 5: ...tion of connections mm 1 water outlet 2 water inlet 3 relief valve outlet 4 electrical connections 1 2 3 4 61AF019 Fixing Holes Fixing Holes Fixing Holes 0 10 Fixing Holes 0 10 1 water outlet 2 water inlet 3 relief valve outlet 4 electrical connections ...

Page 6: ... protected as described in section Electronic control 61AF014 61AF019 Minimum Clearances mm B B C A D E E B F C C C G G A B 61AF 014 019 A 100 300 B 250 200 C 500 400 D 100 200 E 670 700 F 400 500 G 670 1000 User Interface User Interface Disconnector Service Door Service Door ...

Page 7: ...cted by access panels In case of any malfunctioning turn the unit off disconnect the mains power supply and contact a qualified service engineer All of the manufacturing and packaging materials used for your new appliance are compatible with the environment and can be recycled Dispose of the packaging material in accordance with local requirements This equipment contains refrigerant R 407C that mu...

Page 8: ...h 7 water drain 1 shut off valve 2 line filter for water 10 mesh cm 3 pressure gauges 4 filling valve 5 system drain valve at the lowest points of the circuit 6 air flushing valve in the highest parts of the circuit 7 3 way valve 8 sanitary water accumulation tank 9 inside system 10 water circulation pump 11 expansion vessel Typical water circuit diagram for units without hydronic module 014P 019P...

Page 9: ...e adequately insulated and supported Installation of the following components is obligatory 1 The presence of particles in the water can lead to obstructions in the heat exchanger It is therefore necessary to protect the heat exchanger inlet with an extractable mesh filter The filter mesh gauge must be at least 10 mesh cm2 The equipment standard version with hydronic module is equipped with mesh f...

Page 10: ...a 1 61AF 014 2 61AF 019 Outlet available static pressure of the unit with hydronic module Water pressure drop of the unit without hydronic module 1 2 3 2 1 3 2 1 10 20 30 40 50 60 70 80 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 Water flow rate l s 014 100 014 80 014 50 10 20 30 40 50 60 70 80 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 Water flow rate l s 019 100 019 80 019 50 ...

Page 11: ...ecommended to pressurise the hydronic circuit between 1 and 3 bars maximum to clean the hydronic circuit before charging water see chapter after to regularly clean the screen filter ATTENTION The use of integrated hydronic kits in the open loop is not permitted Water flow control procedure fixed speed Hydronic circuit cleaning procedure Open the valve fully item 21 if present Start up the system o...

Page 12: ... all connections re install the protection box by fixing the two screws which were previously removed Liquid refrigerant charge Checking the charge WARNING When adjusting the refrigerant charge always ensure that water is circulating in the heat exchanger to prevent any possibility of freezing up Damage caused by freezing is not covered by the product warranty 61AF units are shipped with a full op...

Page 13: ... e g unoccupied mode and operation at low fan speed e g during the night This option also permits cascade operation of two units and remote control via communication bus RS 485 serial port Unit start up is done by the electronic control described above and must always be carried out under the supervision of a qualified air conditioning engineer This appliance is not intended for use by persons inc...

Page 14: ...ovided based on the water loop volume the fluid used and its concentration Expansion Tank Volume required of water loop volume pure water 3 10 ethylene glicol 3 20 ethylene glicol 3 5 30 ethylene glicol 3 8 40 ethylene glicol 4 2 70 70 70 70 70 70 65 70 65 70 65 70 65 70 65 70 65 70 60 65 70 60 65 70 60 65 70 60 65 70 60 65 70 60 65 70 60 65 70 55 60 65 70 55 60 65 70 55 60 65 70 55 60 65 70 50 55...

Page 15: ...g pressures are normal Check the cleanliness of the refrigerant water heat exchangers by checking the pressure drop across them Controls Check the operation of all the electrical components the high pressurestat and of the high and low pressure transducers and the water air and defrost temperature detector Maintenance Servicing recommendations Maintenance of the unit must be carried out by skilled...

Page 16: ...uously cuts out at low pressure Refrigerant losses CHECK AND ADD THE NECESSARY QUANTITY Low water flow in the exchanger CHECK WATER PUMP Unit start up delay WAIT UNTIL THE SYSTEM HAS STABILISED Unit continuously cuts out at high pressure Defective high pressurestat CHECK AND IF NECESSARY REPLACE PRESSURESTAT Blocked expansion valve CHECK AND REPLACE IF NECESSARY Blocked filter drier CHECK AND IF N...

Page 17: ...GB 15 ...

Page 18: ...003 05 2016 Manufacturer CARRIER SCS MontluelFrance The manufacturer reserves the right to change the specification without prior notice Printed in the European Union www eurovent certification com www certiflash com www ecodesign hvac carrier com ...

Reviews: