 The mesh size of the filter must be 1.2 mm. If this filter is 
not installed, the plate heat exchanger can quickly become 
contaminated at the first start-up, as it takes on the filter 
function, and correct unit operation is affected (reduced 
water flow due to increased pressure drop).

Before the system start-up verify that the water circuits are 
connected to the appropriate heat exchangers (e.g. no reversal 
between evaporator and condenser).

Do not introduce any significant static or dynamic pressure 
into the heat exchange circuit (with regard to the design 
operating pressures).

Before any start-up verify that the heat exchange fluid is 
compatible with the materials and the water circuit coating.

In case additives or other fluids than those recommended by 
Carrier are used, ensure that the fluids are not considered as a 
gas, and that they belong to class 2, as defined in directive 
97/23/EC.

Carrier recommendations on heat exchange fluids:
1.  No NH

4+

 ammonium ions in the water, they are very 

detrimental for copper. This is one of the most important 
factors for the operating life of copper piping. A 
con-tent of several tenths of mg/l will badly corrode 
the copper over time (the plate heat exchangers used 
for these units have brazed copper joints).

2.  Cl

-

 Chloride ions are detrimental for copper with a risk 

of perforations by corrosion by puncture. If possible 
keep below 10 mg/l.

3.  SO

4

2-

 sulphate ions can cause perforating corrosion, if 

their content is above 30 mg/l.

4.  No fluoride ions (<0.1 mg/l).
5.  No Fe

2+

 and Fe

3+

 ions with non negligible levels of 

dis-solved oxygen must be present. Dissolved iron < 5 
mg/l with dissolved oxygen < 5 mg/l.

6.  Dissolved silicon: silicon is an acid element of water 

and can also lead to corrosion risks. Content < 1mg/l.

7.  Water hardness: > 0.5 mmol/l. Values between 1 and 

2.5 can be recommended. This will facilitate scale 
deposit that can limit corrosion of copper. Values that 
are too high can cause piping blockage over time. A 
total alkalimetric titre (TAC) below 100 is desirable.

8.  Dissolved oxygen: Any sudden change in water oxygena-

tion conditions must be avoided. It is as detrimental to 
deoxygenate the water by mixing it with inert gas as it 
is to over-oxygenate it by mixing it with pure oxygen. 
The disturbance of the oxygenation conditions 
encourages destabilisation of copper hydroxides and 
enlargement of particles.

9.  Specific resistance – electric conductivity: the higher the 

specific resistance, the slower the corrosion tendency. 
Values above 30 Ohm·m are desirable. A neutral 
environment favours maximum specific resistance 
values. For electric conductivity values in the order of 
20-60 mS/m can be recommended.

10.  pH: Ideal case pH neutral at 20-25°C
 

7 < pH < 8

6.4.2 - field control wiring
Refer to the 30RW/RWA Pro-Dialog Plus Controls IOM 
and the certified wiring diagram supplied with the unit for 
the field control wirting of the following features:
• 

Evaporator pump interlock (mandatory). Unit 
without hydronic module

• 

Remote on/off switch

• 

Remote heat/cool switch

• 

Demand limit external switch 1

• 

Remote dual set point

• 

Alarm report by circuit

• 

Evaporator pump control. Unit without hydronic 
module.

• 

Condenser pump control. Unit without hydronic 
module.

7 - WATER CONNECTIONS

For size and position of the heat exchanger water inlet and 
outlet connections refer to the certified dimensional drawings 
supplied with the unit. The water pipes must not transmit 
any radial or axial force to the heat exchangers nor any 
vibration. 

The water supply must be analysed and appropriate filtering, 
treatment, control devices, isolation and bleed valves and 
circuits built in, to prevent corrosion, fouling and deteriora-
tion of the pump fittings. Consult either a water treatment 
specialist or appropriate literature on the subject.

7.1 - Operating precautions

The water circuit should be designed to have the least 
number of elbows and horizontal pipe runs at different levels. 
Below the main points to be checked for the connection:
• 

Comply with the water inlet and outlet connections 
shown on the unit.

• 

Install manual or automatic air purge valves at all high 
points in the circuit(s).

• 

Use a pressure reducer to maintain pressure in the 
circuit(s) and install a safety valve as well as an expan-
sion tank. Units with hydronic module include the 
safety valve and expansion tank.

• 

Install thermometers in both the entering and leaving 
water connections.

• 

Install drain connections at all low points to allow the 
whole circuit to be drained.

• 

Install stop valves, close to the entering and leaving 
water connections.

• 

Use flexible connections to reduce the transmission of 
vibrations.

• 

Insulate all pipework, after testing for leaks, both to 
reduce thermal leaks and to prevent condensation.

• 

Cover the insulation with a vapour barrier. If the 
external water piping to the unit is in an area where 
the ambient temperature can fall below 0°C, it should 
be insulated and an electric heater should be installed 
on the piping.

NOTE: For units without hydronic module a screen filter 
must be installed as close as possible to the heat exchanger 
and in a position that is easily accessible for removal and 
cleaning. Units with a hydronic module are equipped with 
this filter.

Summary of Contents for Aquasnap 30RW

Page 1: ...30RW RWA Water Cooled Condenserless Liquid Chillers with Integrated Hydronic Modules Nominal cooling capacity 20 310 kW 50 Hz Installation operation and maintenance instructions...

Page 2: ...5 5 3 Operating range 30RWA 16 5 4 Minimum chilled water flow 16 5 5 Maximum chilled water flow 16 5 6 Variable flow evaporator 16 5 7 Evaporator flow rate 16 5 8 Condenser water flow rate l s 16 5 9...

Page 3: ...enser model used in the installation 31 12 6 Possible fan arrangements based on the air cooled condenser type used in the installation 32 13 START UP 34 13 1 Preliminary checks 34 13 2 Actual start up...

Page 4: ...erally made of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust buil...

Page 5: ...ituated on the liquid line before the filter drier box Any intervention on the refrigerant circuit including changing of drier blocks is only permitted after the complete removal of the refrigerant ch...

Page 6: ...ant on skin or splashing it into the eyes Use safety goggles and safety gloves Wash any spills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush...

Page 7: ...ersons 2 2 Moving and siting the unit 2 2 1 Moving See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there...

Page 8: ...its B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning o...

Page 9: ...let for 30RW units B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For th...

Page 10: ...ts B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning of...

Page 11: ...ed by frequency converter 48 3 r s Power input kW 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 5 0 5 0 5 0 5 0 5 0 5 0 6 7 6 7 6 7 6 7 Expansion tank volume condenser loop l 8 8 8 8 8 12 12 12 25 25 25 25 25 3...

Page 12: ...r and the pumps the control devices Field connections All connections to the system and the electrical installations must be in full accordance with all applicable local codes The Carrier 30RW and 30R...

Page 13: ...pumps 30RW 30RWA option 116C No Description 30RW 30RWA 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1...

Page 14: ...variable speed pump No Description 30RW 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1 87 6 87 6 87 6...

Page 15: ...low leaving water temperature and use of antifreeze is required 2 30RW units without hydronic module operating below 20 C entering condenser water temperature require the use of a three way valve cont...

Page 16: ...r units without hydronic module that have a fixed condenser flow rate Units with a hydronic module have a variable flow rate and no minimum fixed flow rate The minimum flow rate is optimised by unit c...

Page 17: ...er mixing of the liquid water or brine Refer to the examples below Bad Bad Good Good 5 10 Maximum water loop volume evaporator and condenser side Units with hydronic module incorporate an expansion ta...

Page 18: ...er flow rate l s Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30RW 045 5 30RW 060 6 30RW 070 7 30RW 080 8 30RW 090 9 30RW 110 10 30RW 120 11 30RW 135 12 30RW 150 13 30RW 160 185 14 30RW 210 245 15 30...

Page 19: ...at the main disconnect switch Before connecting electric power cables it is imperative to check the correct order of the 3 phases L1 L2 L3 Non certified drawings Refer to the certified dimensional dr...

Page 20: ...switch are designed for the number and type of wires listed in the table below The calculations are based on the maximum machine current see electrical data tables For the design the following standar...

Page 21: ...0 Ohm m are desirable A neutral environment favours maximum specific resistance values For electric conductivity values in the order of 20 60 mS m can be recommended 10 pH Ideal case pH neutral at 20...

Page 22: ...y Damage due to freezing is not covered by the warranty IMPORTANT Depending on the climatic conditions in your area you must Add ethylene glycol with an adequate concentration to protect the installat...

Page 23: ...Pressure gauge to measure the plate heat exchanger pressure drop to be isolated with valve No 5 if not used 7 Plate heat exchanger Legend Components of unit and hydronic module 1 Victaulic screen filt...

Page 24: ...The air cooled condenser must always be used with a subcooler normally with 8 K subcooling 8 2 General Refrigerant pipe sizing must be carried out taking account of the following constraints Oil retur...

Page 25: ...a saturated suction temperature of 4 C and 8 K subcooling Table 3 shows the correction factors to be applied to the values from Table 2 if the operating conditions are different from those previously...

Page 26: ...ing temperature C Outside pipe diameter inch 1 2 5 8 3 4 7 8 1 1 8 1 3 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 27 0 81 1 48 2 39 3 66 7 14 12 06 18 64 37 21 63 94 99 81 145 60 201 98 32 0 84 1 51 2 46 3...

Page 27: ...the forced start command refer to the controls manual and let the pump run for two con secutive hours to clean the hydronic circuit of the system presence of solid contaminants Read the plate heat ex...

Page 28: ...300 1 2 3 4 0 25 50 75 100 125 150 175 200 2 4 6 8 10 50 100 150 200 250 0 5 10 15 20 25 2 1 4 3 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 9 3 Available static system pressure evaporator side Sing...

Page 29: ...0 50 100 150 200 250 0 5 10 15 20 25 30 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 10 2 Available static system pressure condenser side Single pump Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30R...

Page 30: ...st efficiency with variation of the water flow rate and the number of fans required for any thermal load and outside temperature conditions The electronic board AUX1 integrated in the control box of t...

Page 31: ...This is the first fan to start in each circuit and the last fan to stop A fan configuration with fixed speed fans permits year round system operation down to 0 C outside temperature A fan configurati...

Page 32: ...B from fan 2 of each circuit If fans 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH4 for circuit A and CH5 to CH8 for circuit B from fan 1 Single circuit condenser Circuit Possibl...

Page 33: ...its A and B If fan 1 has variable speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 2 If fan 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 1 Dual circuit...

Page 34: ...at all safety devices are operational especially that the high pressure switches are switched on and that the alarms are acknowledged 13 3 Operation of two units in master slave mode The control of a...

Page 35: ...relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier 14 Major system components and operation data 14 1 Compressors 30...

Page 36: ...ow the regulations on monitoring pressurised equipment It is normally required that the user or operator sets up and maintains a monitoring and maintenance file If there are no regulations or to compl...

Page 37: ...onents that do not comply must be changed Test pressures above the respective component design pressure must not be applied annex B and D After repair or significant modifications or significant syste...

Page 38: ...expansion device must be between 12 and 14 C This corresponds to an actual subcooling temperature of between 6 and 8 K at the condenser outlet depending on the unit type Actual subcooling is equal the...

Page 39: ...the vacuum pump pressure gauge ATTENTION Do not use a megohmmeter and do not place any stress on the compressor motor when the system has been ecacuated There is a risk of internal short circuits bet...

Page 40: ...02 5 23 14 33 89 39 16 23 5 54 64 59 07 4 75 0 34 6 57 14 25 34 54 39 79 23 75 55 1 59 5 5 1 66 7 86 14 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 1...

Page 41: ...tions contactors disconnect switch and transformer Check the status of the contactors and fuses Carry out a quick test refer to the 30RW RWA Pro Dialog Plus controls manual Mechanical checks Verify th...

Page 42: ...ment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has b...

Page 43: ...loop volume litres Calculated volume litres 3 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 020 045 2 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 060 300 Pr...

Page 44: ...tor LWT Condenser EWT Condenser LWT Circuit A suction pressure Circuit B suction pressure Circuit A discharge pressure Circuit B discharge pressure Circuit A suction temperature Circuit B suction temp...

Reviews: