background image

38

Normally, a closed system needs to be filled only once. The

actual filling process is generally a fairly simple procedure. All

air should be purged or vented from the system. Thorough

venting at the high points and circulation at room temperature

for several hours is recommended.
NOTE:  Local codes concerning backflow devices and other

protection of the city water system should be consulted and

followed to prevent contamination of the public water

supply. This is especially important when antifreeze is used

in the system.
Set Water Flow Rate through the chiller once the system is

cleaned, pressurized, and filled.
NOTE: Carrier recommends a differential pressure gage when

measuring pressures across the pumps or balancing valves.

This provides for greater accuracy and reduces error build-up

that often occurs when subtracting pressures made by different

gages.

On primary/secondary systems, it is advisable to set the

30MP balancing valve to maintain design flow plus 10%

through the chiller.

A rough estimate of water flow can also be obtained from

measuring the pressure drop across the 30MP heat exchanger.

Figures 30-33 show the relationship between gpm (l/s) and

heat exchanger pressure drop. It should be noted that these

curves are for “clean” heat exchangers with fresh water; they

do not apply to heat exchangers with fouling or glycol. Adjust

the external balancing valve until the correct pressure drop is

obtained for the required gpm.

Step 7  — Make  Electrical  Connections — 

All

field wiring must comply with local code requirements.

Electrical data for the complete unit and for the compressors is

shown in Tables 11-13. See Fig. 39 for field wiring connec-

tions. A field-supplied branch circuit disconnect switch that

can be locked in either OPEN or OFF position 

must

 be in-

stalled.

30MPA, MPW CONTROL BOX

30MPA, MPW Controls Section contains the following com-

ponents:
• main base board (MBB)

• scrolling marquee display

• optional energy management module

• control-circuit breakers for 24-v circuits

• control-circuit ON-OFF switch 

• unit Enable/Off/Remote contact switch

• unit Alarm/Alert indicator light
30MPA, MPW  Control  Wiring   (Factory-Wired) circuit

power is 24 v on all units. Factory-installed control transformer

(TRAN 1) uses line voltage for all units. All control transform-

ers are factory-installed and wired. For 208/230-3-60 units op-

erating at 208-3-60 line voltage, TRAN1 primary connections

must be moved to terminals H3 and H4 for 30MP016-045

units, or terminals H1 and H2 for 30MP050-071 units.

Inside the control box are terminals for field power and

ground (earth) wiring. A ground wire must be installed with

each field power supply. Compressors are wired for across-the-

line start. Refer to Tables 11-13 for electrical data.
30MPA, MPW, Control Wiring (Field-Wired) is found in

the 30MPA, MPW control box which contains the low-voltage,

field-wiring terminal strip (LVT). All low-voltage field-wiring

connections are made to this terminal block, see Fig. 39. Three

7

/

8

-in. (22 mm) knockouts are provided for field wiring in this

section.

Connections for condenser flow switch, chilled fluid pump

interlock, condenser pump interlock, remote alarm output, con-

denser output, and dual chiller thermistor accessory are made at

these locations. Connections for the multi-unit controller ac-

cessory network are made to the BACnet communication

module.

The unit has the capability to control field-supplied devices.

They are: alarm signal, condenser pump or condenser fan out-

put, and chilled water pump output. The unit provides 24-v

power with a maximum 5 va rating per output allowed.
30MPA, MPW Power Section supplies power to the 30MPA,

MPW unit. The electrical power supply is brought in through

the top left-hand side of the control box. Pressure-lug connec-

tions on the terminal blocks are suitable for only for copper

conductors.

The control box power section contains the following

components:
• power terminal block

• optional disconnect switch

• compressor circuit breaker(s)

• compressor contactor(s)

• current sensor boards

• control transformer

• ground lug

• neutral terminal (380-3-60, 380/415-3-50 units only)

• crankcase heater relay (30MPA, all units, 30MPW030 - 071)

• fuses
Flow Switches are provided on all units to provide a cooler

flow and are factory-installed and wired. A condenser flow

switch is available as an accessory for all 30MPW units, and

can be field-installed. The Carrier flow switch accessory (part

no. 30MP-900---004) is available for this purpose. Flow switch

wiring terminals are located in the field wiring compartment of

the control box. The flow switch should be wired between ter-

minals LVT-11 and LVT-17 for all units. Condenser water flow

switch cannot be used if a condenser water regulating valve is

installed.
30MPE DISTRIBUTION PANEL  — Inside  the  panel  are

terminals for field power and ground (earth) wiring. A ground

connection is available, and must be connected, in the 30MPE

panel for each chiller.
30MPE Distribution Panel, Power Section provides power to

the 30MPE distribution panel. The electrical power supply is

brought in through the top of the 30MPE distribution panel.

Pressure-lug connections on the terminal blocks or bus bar are

suitable for copper conductors only. The distribution panel

power section contains the following components:

• power terminal blocks or bus bar

• circuit breakers

• ground lugs

CAUTION

Failure to follow these instructions may result in unit dam-

age. When wiring the 30MP chiller to its associated

30MPE distribution panel, it is important to connect each

chiller to its corresponding circuit breaker in the panel. 
Each circuit breaker has been sized for its particular chiller.

Proper installation is critical to ensure appropriate wire siz-

ing, hazard avoidance, and compliance with local code(s).

Consult submittal information.

Summary of Contents for AquaSnap 30MPA050

Page 1: ...controls The 30MPA units are condenserless units and the 30MPW units are fluid cooled See Fig 1 4 for dif ferent unit configurations See Fig 5 for model number no menclature and Fig 6 19 for unit dim...

Page 2: ...2 Fig 1 30MPA Unit Size 020 045 a30 6023 Fig 2 30MPA Unit Size 050 071 a30 6024 Fig 3 30MPW Unit Size 016 045 a30 6025 Fig 4 30MPW Unit Size 050 071 a30 6026...

Page 3: ...Interrupt High Condensing and Hot Gas Bypass 071 71 250 2 Fused Disconnect Switch selected models 0 Comfort Cooling Duty 32 60 F 0 0 16 5 C Std 1 Water Manifold Piping Includes Combination Valve 2 Wa...

Page 4: ...to the nearest beams Additional weight of factory installed sound enclosure op tion is 75 lb 34 kg Additional operating weight of 30MPA water manifold option is 218 lb 99 kg Additional operating weigh...

Page 5: ...37 48 952 0 mm 30MPA071 1506 683 kg 14 31 363 4 mm 27 30 693 4 mm 38 08 967 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions are shown i...

Page 6: ...59 9 mm 27 39 695 7 mm 37 48 952 0 mm 30MPA071 1506 683 kg 14 31 363 4 mm 27 30 693 4 mm 38 08 967 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3...

Page 7: ...h local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding charge Field removal of tube and reducing coupling is required Consult Installation Instructions for...

Page 8: ...34 42 874 2 mm 30MPA071 1724 782 kg 14 52 368 8 mm 29 96 760 9 mm 35 01 889 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions in are in mi...

Page 9: ...equired Consult Installation Instructions for dis charge and liquid pipe connection sizes UNIT OPERATING WEIGHT lb DIMENSIONS in NUMBER OF COMPRESSORS STANDARD UNIT A B C D E F G H J 30MPW016 671 305...

Page 10: ...and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding charge Field removal of tube and reducing...

Page 11: ...12 58 319 5 27 76 705 1 mm 35 27 895 5 mm 30MPW071 1719 780 kg 12 79 324 9 27 67 702 9 mm 35 02 889 5 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3...

Page 12: ...mm 3 30MPW045 1734 788 kg 12 69 332 mm 29 47 748 mm 32 19 818 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions are shown in inches Dimensi...

Page 13: ...ntrol panel end opposite control panel end and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding...

Page 14: ...13 26 336 8 mm 27 63 701 8 mm 31 36 796 5 mm 30MPW071 2155 977 5 kg 13 42 340 8 mm 27 55 699 8 mm 31 17 791 7 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of...

Page 15: ...CLARITY STYLE B 11 38 in TYPICAL SEE DETAIL A 64 78 in TOP VIEW FRONT VIEW SIDE VIEW 57 00 in UNIT SIZES 016 045 65 05 in UNIT SIZES 050 071 68 81 in a30 6003 NOTE Style B water manifold is used on 30...

Page 16: ...70 63 in TOP VIEW FRONT VIEW SIDE VIEW SEE DETAIL A 6 VICTAULIC CONNECTIONS SPACER PIPE ACCESSORY DETAIL A CORNER POSTS REMOVED FOR CLARITY a30 6004 STYLE B 11 38 in TYPICAL NOTE Style B water manifol...

Page 17: ...3 Minimum Step Capacity 8 15 15 15 10 10 EVAPORATOR Weight lb empty 33 47 92 87 112 158 Net Fluid Volume gal 1 1 1 2 2 8 2 4 3 1 4 7 Maximum Refrigerant Pressure psig 505 505 565 650 565 565 Maximum F...

Page 18: ...PORATOR Weight lb empty 143 143 167 167 190 Net Fluid Volume gal 3 9 3 9 4 7 4 7 5 4 Maximum Refrigerant Pressure psig 650 650 650 650 650 Maximum Fluid Side Pressure psig 300 300 300 300 300 Evaporat...

Page 19: ...Net Fluid Volume L 4 1 4 7 10 5 8 9 11 8 17 9 Maximum Refrigerant Pressure kPa 3482 3482 3896 4479 3896 3896 Maximum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 2068 Evaporator Connections in In...

Page 20: ...14 1 17 0 17 0 19 6 Maximum Refrigerant Pressure kPa 4481 4481 4481 4481 4481 Maximum Fluid Side Pressure kPa 2070 0 2070 0 2070 0 2070 0 2070 0 Water Connections in Inlet and Outlet Victaulic IPS 21...

Page 21: ...70 214 W045 413 256 393 235 W050 484 398 403 317 W055 490 402 407 319 W060 508 424 416 332 W065 519 432 424 337 W071 516 432 427 344 UNIT 30MP WITH MANIFOLD MOUNTING HOLE lb A B C D A020 258 326 134 2...

Page 22: ...9 249 319 259 W050 369 367 310 313 368 311 W055 372 370 312 315 371 313 W060 382 383 324 323 382 323 W065 388 389 328 327 389 327 W071 388 388 331 330 388 330 ESTIMATED WEIGHT DISTRIBUTION AT EACH MOU...

Page 23: ...final position remove the packaging and remove the mobility kit wheels if equipped Remove the 3 8 in wheel nuts to remove the wheels from the unit legs Lev el the unit using a level and bolt the unit...

Page 24: ...pressor mounting rail These RED bolts are for shipping purposes only COMPRESSOR HOLDDOWN BOLTS RED TO BE REMOVED BOTH SIDES COMPRESSOR HOLDDOWN BOLTS TO BE REMOVED BOTH SIDES NOTE For 30MP050 071 unit...

Page 25: ...tem Design Manual or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers handbook for details 5 See product data for minimum system fluid volume This system may...

Page 26: ...not intended for a specific installation Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards 3 All wiring must comply with applicable local...

Page 27: ...e adequate volume 6 Hot gas lines should rise above refrigerant level in condenser circuit With 30MPA 09DP matched condensers this is accomplished internally in the 09DP unit Double riser may be requi...

Page 28: ...piping techniques Refer to Carrier System Design Manual part 3 Carrier E20 II software Refrigerant Piping program or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning E...

Page 29: ...crons or less isolate the vacuum pump from the system Observe the rate of rise of the vacuum in the sys tem If the vacuum rises by more than 50 microns in a 30 min ute time period continue the dehydra...

Page 30: ...s in the line Maintain system pressure by using a pressure tank or a combination of relief and reducing valves For units with water manifold option refer to manifold Victaulic spacer fitting kit acces...

Page 31: ...00 210 220 230 240 4 1 2 3 5 6 7 8 9 Water Pressure Drop GPM LEGEND NOTE Pressure drop curves assume water temperature of 68 F 20 C 1 30MP016 6 30MP045 2 30MP020 7 30MP050 055 3 30MP030 8 30MP060 065...

Page 32: ...30 140 150 160 170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 8 9 Water Pressure Drop kPa Liters Second 1 0 2 3 4 5 6 7 8 9 10 11 12 15 13 14 0 10 20 30 40 50 60 80 90 100 110 120 70 3 1 2 4 5 6 7 8 9...

Page 33: ...30MP045 2 30MP030 6 30MP050 55 3 30MP032 7 30MP060 065 071 4 30MP040 40 35 30 25 20 15 10 5 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 W...

Page 34: ...170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 Water Pressure Drop GPM Water Pressure Drop kPa Liters Second 1 0 2 3 4 5 6 7 8 9 10 11 12 15 13 14 0 10 20 30 40 50 60 80 90 100 110 120 70 3 1 2 4 5 6...

Page 35: ...eaking this is the best place to install an air separator if possible 1 Install automatic air vents at all high points in the system If the 30MP unit is located at the high point of the system a vent...

Page 36: ...ATURE STRAINER 30MP CHILLER CONTROL BOX T SHIELDED GROUNDED WIRE 30MP CHILLER 30MP CHILLER CONTROL BOX CONTROL BOX DISTRIBUTION PUMP EXPANSION TANK S AIR SEPARATOR WITH VENTS DECOUPLER CHILLER 1 CHILL...

Page 37: ...ine water pH of 8 to 9 Avoid a pH greater than 10 since this will adversely affect pump seal components c A side stream filter is recommended see Fig 38 during the cleaning process Filter side flow ra...

Page 38: ...und in the 30MPA MPW control box which contains the low voltage field wiring terminal strip LVT All low voltage field wiring connections are made to this terminal block see Fig 39 Three 7 8 in 22 mm k...

Page 39: ...236 v AC 238 v Average Voltage 243 236 238 3 239 v Determine maximum deviation from average voltage AB 243 239 4 v BC 239 236 3 v AC 239 238 1 v Maximum deviation is 4 v Determine percent voltage imba...

Page 40: ...A EA LRA EA RLA EA LRA EA MCA ICF MOCP REC FUSE 016 208 230 3 60 187 253 24 8 240 0 17 2 164 N A N A 48 2 257 2 70 60 380 3 60 342 418 16 0 134 0 12 2 73 32 2 146 2 45 40 460 3 60 414 508 12 4 130 0 8...

Page 41: ...TS NAMEPLATE VOLTAGE COMPRESSOR A1 COMPRESSOR A2 UNIT RLA LRA RLA LRA MCA ICF MOCP REC FUSE MIN MAX 050 208 230 3 60 187 253 85 1 436 85 1 436 191 5 521 1 250 225 380 3 60 342 418 49 3 252 49 3 252 11...

Page 42: ...NAMEPLATE VOLTAGE COMPRESSOR A1 COMPRESSOR A2 UNIT RLA LRA RLA LRA MCA ICF MOCP REC FUSE MIN MAX 050 208 230 3 60 187 253 79 4 418 79 4 418 178 7 497 1 250 200 380 3 60 342 418 48 1 252 48 1 252 108 2...

Page 43: ...o 90 amps is 6 AWG to 3 0 e Incoming wire size range for non fused disconnect with MCA from 90 1 amps to 250 amps is 4 AWG to 350 kcmil f Incoming wire size range for fused disconnect is 6 AWG to 10 A...

Page 44: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300182 01 Printed in U S A Form 30MP 21SI Pg 44 1118 12 17 Replaces 30M...

Reviews: