APPENDIX G — MAINTENANCE SUMMARY AND LOG SHEETS
30XV Monthly Maintenance Log
NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
Month
1
2
3
4
5
6
7
8
9
10
11
12
Date
/ / / / / / / / / / / / / / / / / / / / / / / /
Operator
UNIT SECTION
ACTION
UNIT
ENTRY
Compressor
Change Oil Filter (Screw Compressors)
yes/no
Year 1 then As Needed
Send Oil Sample Out for Analysis
yes/no
Annually
Leak Test
yes/no
Check Oil Separator Heater
Every 3 months
Check Oil Filter Pressure Drop
Every 3 months
Check Glycol Concentration
Annually
Evaporator
Inspect and Clean Evaporator Tubes
yes/no
Every 3 - 5 Years
Inspect Evaporator Heater
amps
Annually
Inspect Relief Valves
yes/no
Annually
Leak Test
yes/no
Record Water Pressure Differential (PSI)
PSI
Check glycol concentration
Annually
Eddy Current Test
yes/no
Every 3 - 5 Years
Condenser
Leak Test
yes/no
Inspect and Clean Condenser Coils
yes/no
Check condenser fan operation and condition
Every 3 months
Inspect Relief Valves
yes/no
Controls
General Cleaning and Tightening Connections
yes/no
Annually
Check Pressure Transducers for Accuracy
yes/no
Annually
Verify Flow Switch Operation
yes/no
Every 3 months
Confirm Accuracy of Thermistors
yes/no
Annually
Electrical
General Tightening and Cleaning Connections
yes/no
Annually
Inspect All Contactors
yes/no
Annually
System
Check Refrigerant Charge
yes/no
Annually
Verify Operation of EXVs
yes/no
Check moisture indicating sight glass
Check refrigerant joints and valves for leaks
Every 3 months
Check filter drier for pressure drop
Annually
Check chilled water strainers
Annually
Record System Superheat
deg. F
Compressor VFD
Clean or replace drive filters
yes/no
All VFD
Check cooling fan operation
yes/no
Verify heat sinks are clear of debris
yes/no
Every 3 months
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...