9 - HEAT RECLAIM CONDENSER OPTION (OPTION 50)
9.1 - Physical data, 30XA units with heat reclaim condenser option
30XA heat reclaim mode
252
302
352
402
452
502
602
702
752
802
852
902
1002
Operating weight*
kg
3920
3960
3970
4930
5050
5550
6670
6730
7130
7350
7890
8340
8950
Condenser diameter
in
10
10
10
12
14
14
12+12 12+12 14+12 14+12 14+12 14+14 14+14
Refrigerant charge
Circuit A
kg
37
35
35
51
52
59
58
58
65
69
72
69
91
Circuit B
kg
39
37
37
37
37
36
59
62
58
65
63
76
89
Heat reclaim condenser
Flooded multi-pipe condenser
Water volume
l
38
38
38
55
68
68
55 + 55 55 + 55 68 + 55 68+55 68+55 68 + 68 68 + 68
Water connections
Victaulic
Nominal diameter
in
3
3
3
4
4
4
4
4
4
4
4
4
4
Actual outside diameter
mm
88.9
88.9
88.9
114.3
114.3
114.3
114.3
114.3
114.3
114.3
114.3
114.3
114.3
* Weights are for guidance only.
9.2 - Dimensions, clearances
9.2.1 - 30XA 252-352 - heat reclaim option
ATTENTION: The condenser connection sleeves are not
installed, but supplied with the unit. The sealing joints are
in the control box. The temperature sensors and the
condenser flow switch are wired and fixed in the machine.
They must be installed as described in the chapter
“Condenser water connections”.
Legend
All dimensions are given in mm.
Required clearances for maintenance (see note)
Recommended space for evaporator tube removal
Water inlet for standard unit
For options 5, 6, 100A, 100C, 107 refer to the certified drawing.
Water outlet for standard unit
For options 5, 6, 100A, 100C, 107 refer to the certified drawing.
Air outlet – do not obstruct
Power supply and control connection
Control circuit connection for option 158
Heat reclaim condenser
C
NOTES:
-
Drawings are not contractually binding.
-
Before designing an installation, consult the certified
dimensional drawings, available on request.
-
For the positioning of the fixing points, weight
distribution and centre of gravity coordinates please
refer to the dimensional drawings.
-
If the installation includes several units or if this
(these) is (are) close to walls, please refer to chapters
3.11 - “Multiple chiller installation” and 3.12 -
“Distance to the wall” of this document to determine
the space required.