78
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Surge Correction
Maintenance ISM Config
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: MAISURGE
PIC 5 PATH: Main Menu
Maintenance Menu
Surge Correction
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Surge Region
0 = No, 1 = Low, 2 = High,
3 = Deadband, 4 = Noise
act_reg
0 to 2
RO
2
Active Delta Tsat
dts_act
° F
RO
3
Calc Ref Delta Tsat
dts_cal
°F
RO
4
High Eff Delta Tsat
dts_he
°F
RO
5
Amps Change Surge Prot
amps_dta
%
RO
6
Max Amps Change Value
amch_max
%
RO
7
Surge Counts
sc
RO
8
Surge Protection Counts
spc
RO
9
Surge Prevention Active
surg_act
NO/YES
RO
10
Surge Protection Active
surg_pro
NO/YES
RO
11
EC Vlave Change Flag
0 = Close, 1 = Hold, 2 = Open
hgbp_chg
0 to 2
RO
12
Cal Surge Delta Tsmax
dts_maxc
0 to 150.0
°F
RO
13
Cal Surge Delta Tsmin
dts_minc
0 to 150.0
°F
RO
14
Cal Surge Delta Tsmed
dts_medc
0 to 150.0
^F
RO
15
IGV1 Full Load Position
gv1_sful
0 to100.0
%
RO
16
IGV1 Minimum Position
gv1_smin
0.0 to 100.0
%
RO
17
Opti-Sound IGV1 Position
gvi_smed
%
RO
18
Envelop Line Optimized
enlp_opt
NO/YES
RO
CCN TABLE NAME: ISM_MCFG
PIC 5 PATH: Main Menu
Maintenance Menu
Maintenance ISM Config
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
ISM Config Conflict
ism_cflt
NO/YES
—
RO
2
Delete ISM Config
del_ismc
NO/YES
NO
—
RW
3
Communication Timeout
com_tout
0 to 255
sec
RO
High Eff Ref Delta Tsat
dts_he
^F
RO
4
Starter Type
0=Full Volt, 1=Redu Volt
2=Solid State, 3=FS VFD
star_typ
0 to 3
—
RO
5
Single Cycle Dropout
scycd_en
DSABLE/ENABLE
—
RO
6
Motor Rated Load Amps
rla
10 to 5000
amp
RO
7
Motor Locked Rotor Trip
mot_lra
100 to 65535
amp
RO
8
Locked Rotor Start Delay
lrs_del
1 to 10
cycles
RO
9
Starter LRA Rating
str_lra
100 to 65535
amp
RO
10
Motor Rated Line Voltage
rlv
200 to 13800
V
RO
11
Current Imbal Threshold
cu_th
5 to 100
%
RO
12
Voltage Imbal Threshold
vu_th
1 to 10
%
RO
13
Motor Current CT Ratio:1
ct_ratio
3 to 1000
—
RO
14
Volt Transformer Ratio:1
vt_rat
1 to 115
—
RO
15
Current Imbal Persist
cu_per
1 to 10
sec
RO
16
Voltage Imbal Persist
vu_per
1 to 10
sec
RO
17
Line Frequency Faulting
lfref_en
DSABLE/ENABLE
—
RO
18
Frequency (No=50, Y=60Hz)
linefreq
NO/YES
—
RO
19
Ground Fault Protection
gfp_en
DSABLE/ENABLE
—
RO
20
Ground Fault Current
gf_amps
1 to 25
amp
RO
21
Ground Fault Persistence
gfp_pers
1 to 10
cycles
RO
22
Ground Fault Start Delay
gfs_del
1 to 20
cycles
RO
23
Ground Fault CT Ratio:1
gfct_rat
150 to 150
—
RO
24
Overvoltage Threshold
ovvol_th
105 to 115
%
RO
25
Undervoltage Threshold
udvol_th
85 to 95
%
RO
26
Over Under Volt Persist
ovud_per
1 to 10
sec
RO
27
Under Volt Start Delay
uvs_del
1 to 4
sec
RO
RO — Read Only