APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
UM VFD Status
LEGEND
CCN TABLE NAME: VFD_STAT
PIC6 PATH: Main Menu
Maintenance Menu
UM VFD Status
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Single Cycle Dropout
cycle_1
NO/YES
NO
RO
2
Line Current Imbalance
lineim_i
NO/YES
NO
RO
3
High Line Voltage
hi_volt
NO/YES
NO
RO
4
Low Line Voltage
low_volt
NO/YES
NO
RO
5
Low DC Bus Voltage
lo_dcbus
NO/YES
NO
RO
6
High DC Bus Voltage
hi_dcbus
NO/YES
NO
RO
7
VFD Power On Reset
vfd_por
NO/YES
NO
RO
8
Ground Fault
grnd_flt
NO/YES
NO
RO
9
Line Phase Reversal
ph_rev
NO/YES
NO
RO
10
Motor Overload Trip
motor_ov
NO/YES
NO
RO
11
Start Complete
start_ok
NO/YES
NO
RO
12
Rectifier Power Fault
rect_pu
NO/YES
NO
RO
13
Invert Power Fault
inv_pu
NO/YES
NO
RO
14
Rectifier Overcurrent
rect_oi
NO/YES
NO
RO
15
Inverter Overcurrent
inv_oi
NO/YES
NO
RO
16
Condenser High Pressure
prs_trip
NO/YES
NO
RO
17
Motor Amps Not Sensed
no_amps
NO/YES
NO
RO
18
Motor Acceleration Fault
accelflt
NO/YES
NO
RO
19
Stop Complete
stop_ok
NO/YES
NO
RO
20
Stop Fault
ampstop
NO/YES
NO
RO
21
Rectifier Overtemp
rect_ot
NO/YES
NO
RO
22
Inverter Overtemp
inv_ot
NO/YES
NO
RO
23
Motor Current Imbalance
motim_i
NO/YES
NO
RO
24
Line Voltage Imbalance
lineim_v
NO/YES
NO
RO
25
Frequency Fault
freqflt
NO/YES
NO
RO
26
VFD Comm Fault
vfd_comm
NO/YES
NO
RO
27
VFD Fault
vfdfault
NO/YES
NO
RO
28
Read Config Complete
readone
NO/YES
NO
RO
29
VFD Start Inhibit
strt_inh
NO/YES
NO
RO
30
VFD Checksum Error
checksum
NO/YES
NO
RO
31
Inductor Overtemp Switch
inot_sw
NO/YES
NO
RO
32
Incompatibility Fault
incomp
NO/YES
NO
RO
RO —
Read Only