APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Quick Calibration Menu
Navigation: MAIN MENU
QUICK Calibration
Quick Calibration
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: QCK_CALI
PIC6 PATH: Main Menu
Quick calibration
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Quick Test Enable
QCK_TEST
DISABLE/ENABLE
DISABLE
RW
2
GV1 Calibration Enable
GV1_CAL
DISABLE/ENABLE
DISABLE
RW
3
GV1 Calibration Status
4
0 = no calibration/Failure, 1= in progress,
2= completed
GV1_STAT
RO
5
Guide Vane 1 Actual Ohms
GV1_OHM
0 to 12000
Ohms
RO
6
Guide Vane 1 Ohms 100
%
GV1_MAXO
0 to 12000
Ohms
RO
7
Guide Vane 1 Ohms 0
%
GV1_MINO
0 to 12000
Ohms
RO
8
Guide Vane 1 Actual mA
GV1_MAF
0 to 20.80
mA
RO
9
Guide Vane 1 mA 100
%
GV1_MAXA
0 to 20.80
mA
RO
10
Guide Vane 1 mA 0
%
GV1_MINA
0 to 20.80
mA
RO
11
GV2 Calibration Enable
GV2_CAL
DISABLE/ENABLE
DISABLE
RW
12
GV2 Calibration Status
13
0 = no calibration/Failure, 1= in progress,
2= completed
GV2_STAT
RO
14
Guide Vane 2 Actual mA
GV2_MAF
0 to 20.80
mA
RO
15
Guide Vane 2 mA 100
%
GV2_MAXA
0 to 20.80
mA
RO
16
Guide Vane 2 mA 0
%
GV2_MINA
0 to 20.80
mA
RO
17
EC Valve Calib Enable
HGBP_CAL
DISABLE/ENABLE
DISABLE
RW
18
EC Valve Calib Status
19
0 = no calibration/Failure, 1= in progress,
2= completed
HGBP_ST
RO
20
EC Valve Actual mA
HGBP_AMA
0 to 20.80
mA
RO
21
EC Valve mA 100
%
HBP_MAXA
0 to 20.80
mA
RO
22
EC Valve mA 0
%
HBP_MINA
0 to 20.80
mA
RO
23
Ref Lub 1st Test, Disable
RL1TEST
RO
24
Ref Lub 1st Test Time
RL1TIME
min
RO
25
Ref Lub 1st Test Status
RL1STAT
RO
RO —
Read Only
RW —
Read/Write