APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Option
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: CONF_OPT
PIC6 PATH: Main Menu
Configuration Menu
Option
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Auto Restart Option
astart
DISABLE/ENABLE
DISABLE
RW
2
Common Sensor Option
commsens
DISABLE/ENABLE
DISABLE
RW
3
EC Valve Option
0 = No, 1= Cont
2 = On/Off, 3 = 4-20 mA
hgbp_opt
0 to 3
0
RW
4
EC Selection
0 = Disable, 1 = Surge
2 = Low Load, 3 = Comb
hgbp_sel
0 to 3
0
RW
5
ECV Open IGV1 Position
hpop_gv1
0.5 to 10
5.0
%
RW
6
ECV Close IGV1 Position
hgcl_gv1
1.5 to 20
10.0
%
RW
7
ECV Off DT for Low Load
hgb_toff
0.5 to 10.0
4.0
^F
RW
8
ECV On DT for Low Load
hgb_ton
0.5 to 10.0
2.0
^F
RW
9
ECV Low Load DB
hgbp_ldb
0.5 to 2.0
1.0
^F
RW
10
Head Pres Valve Option
hdpv_opt
DISABLE/ENABLE
DISABLE
RW
11
Head Pres Delta P 0
%
hdp_0
0 to 85.0
25.0
psid
RW
12
Head Pres Delta P 100
%
hdp_100
0 to 85.0
50.0
psid
RW
13
Head Pressure Min Output
hdpv_min
0.0 to 100.0
0.0
%
RW
14
Head Pressure Deadband
hdpv_db
0 to 10
1
°F
RW
15
Tower Fan High set point
tfh_sp
55 to 105
75
RW
16
Refrigerant Leak Option
leak_en
DISABLE/ENABLE
DISABLE
RW
17
Refrig Leakage Alarm mA
exv_opt
4 to 20
20
RW
18
Gas Torque Factor
gt_fact
0.25 to 3.0
1
°F
RW
19
Guide Vane/SRD Factor
gv_srd_f
0.7 to 1.20
0.95
RW
20
Power Recovery Timeout
pd_tcfg
0 to 60
15
min
RW
21
Customer Alert Option
cusa_opt
DISABLE/ENABLE
DISABLE
RW
22
Ice Build Option
ice_opt
DISABLE/ENABLE
DISABLE
RW
23
Ice Build Recycle
ice_recy
DISABLE/ENABLE
DISABLE
RW
24
Ice Build Termin Source
0 = Temp, 1 = Contact, 2 = Both
ice_term
0 to 2
0
RW
25
Water Pressure Option
wp_opt
DISABLE/ENABLE
DISABLE
RW
26
Water Flow Measurement
0 = No, 1 = Digital, 2 = Analog
wfm_opt
0 to 2
0
RW
27
Water Flow Determination
0=Sat Temp, 1= Flow Switch
fs_opt
0 to 1
0
RW
28
Water Flow at 4 mA
flow4ma
0 to 200
0.00
GPS
RW
29
Water Flow at 20mA
flow20ma
0 to 200
0.00
GPS
RW
30
Evap Flow Rate Baseline
chwf_bas
0 to 150
0.00
GPS
RW
31
Evap Pres Drop Baseline
evpd_bas
0 to 20
0.00
PSI
RW
32
Cond Flow Rate Baseline
cdwf_bas
0 to 150
0.00
PSI
RW
33
Cond Pres Drop Baseline
cdpd_bas
0 to 20
0.00
PSI
RW
34
Water Pres Drop @ 20mA
wpd_20ma
0 to 40
10.00
PSI
RW
35
Evap Liquid Temp Opt
evap_ref
DISABLE/ENABLE
ENABLE
RW
36
Evap App Calc Selection
Sat Temp = 0, Ref Temp = 1
evap_ref
0/1
1
RW
37
Remote Stop Contact
rem_stop
DISABLE/ENABLE
DISABLE
RW
RW —