48
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
NOTE: This software is shared between multiple product families
and therefore not all points indicated in the tables are applicable to
19DV or 19XR as configured. For instance 19DV is not an oil lu-
bricated machine, so any reference to oil in the software tables
would not be applicable for 19DV.
General Parameters
LEGEND
* Default value is shown only if configurable in this table.
† 0 = OFF
9 = AUTORST
1 = CTLTEST
10 = RAMPING
2 = PUMPDOWN
11 = RUNNING
3 = LOCKOUT
12 = OVERRIDE
4 = RECYCLE
13 = DEMAND
5 = TRIPOUT
14 = SHUTDOWN
6 = TIMEOUT
15 = FREECOOL
7 = PRESTART
16 = CONDFLSH
8 = STARTUP
** RW from network.
NOTE: The PIC6 controls platform is utilized across multiple product
lines. In this appendix, all PIC6 software lines are shown; as configured
for 19DV in v2.1 software. Not all lines may be applicable for the 19DV
product.
CCN TABLE NAME: GENUNIT
PIC6 PATH: Main Menu
General Parameters
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Control Mode
0 = Local, 1 = Network
2 = Remote, 3 = Local Sched
ctl_mode
0 to 3
RO
2
Compressor1 Run Status
cm_stas1
0 to 16†
RO
3
Deter Start Stop Command
stop/start
RO
4
Network: Cmd Start/Stop
CHIL_S_S
NO/YES
RW**
5
Network:Cmd Occupied
CHIL_OCC
NO/YES
RW**
6
Cooling / Heating Select
HC_SEL
COOL/HEAT
COOL
RW
7
Control Point
CTRL_PNT
10.0 to 160.0
°F
RW**
8
Control Point Reset
reset
–30.00 to 30.00
°F
RO
9
Actual Setpoint
setpoint
10.0 to 150.0
°F
RO
10
Percent Current
AMPS_P
0.0 to 999.0
%
RO
11
Motor Percent Kilowatts
KW_P
0 to 100
%
RO
12
Calculated Capacity
cal_capa
0 to 100
%
RO
13
Actual Demand Limit
DEM_LIM
10.0 to 100.0
100
%
RW**
14
Emergency Stop
EMSTOP
NO/YES
0
RW**
15
Chiller Status Number
ch_state
0 to 500
RO
16
Local Schedule Occupied
oc_occ
NO/YES
RO
17
Ice Schedule Occupied
ice_occ
NO/YES
RO
18
Master Slave Start Stop
ms_stsp
STOP/START
RO
19
Remote Reset Alarm
REM_RST
NO/YES
RO
20
Stop Override
STP_OVER
NO/YES
NO
RW
21
Start Condenser Flush
CF_START
NO/YES
NO
RW
22
BACnet Occupied
BAC_OCC
NO/YES
RO
RO —
Read Only
RW —