139
Table 35 — Electrical Data — Premium Efficiency EISA Compliant Motors
ODP/OPSB T-FRAME MOTORS - 1800 RPM
TEFC T-FRAME MOTORS - 1800 RPM
LEGEND
ODP/OPSB T-FRAME MOTORS - 3600 RPM
TEFC T-FRAME MOTORS - 3600 RPM
NOTES:
1. Approximate motor full load amps listed. Actual motor full load
amps can be found on the motor nameplate.
2. Motor voltage and availability is controlled by
AHU
Builder
®
program.
MOTOR
HP
FLA FOR 3-PHASE, 60 Hz
VOLTAGES
EFF.
(%)
NEMA
FRAME
208
230
460
575
1.0
3.1
2.8
1.4
1.1
85.5
143T
1.5
4.6
4.2
2.1
1.7
86.5
145T
2.0
6.1
5.6
2.8
2.2
86.5
145T
3.0
8.6
7.8
3.9
3.1
89.5
182T
5.0
14.3
13.0
6.5
5.2
89.5
184T
7.5
20.8
18.8
9.4
7.5
91.0
213T
10.0
27.3
24.7
12.4
9.9
91.7
215T
15.0
39.8
36.0
18.0
14.4
93.0
254T
20.0
53.1
48.0
24.0
19.2
93.0
256T
25.0
65.5
59.3
29.6
23.7
93.6
284T
30.0
77.8
70.4
35.2
28.2
94.1
286T
40.0
103.8
93.8
46.9
37.5
94.1
324T
50.0
128.6
116.3
58.2
46.5
94.5
326T
60.0
152.7
138.1
69.1
55.2
95.0
364T
75.0
190.9
172.6
86.3
69.1
95.0
365T
100.0
252.4
228.3
114.1
91.3
95.4
404T
125.0
—
—
142.7
114.1
95.4
405T
150.0
—
—
169.8
135.8
95.8
444T
MOTOR
HP
FLA FOR 3-PHASE, 60 Hz
VOLTAGES
EFF.
(%)
NEMA
FRAME
208
230
460
575
1.0
3.1
2.8
1.4
1.1
85.5
143T
1.5
4.6
4.2
2.1
1.7
86.5
145T
2.0
6.1
5.6
2.8
2.2
86.5
145T
3.0
8.6
7.8
3.9
3.1
89.5
182T
5.0
14.3
13.0
6.5
5.2
89.5
184T
7.5
20.5
18.5
9.3
7.4
91.7
213T
10.0
27.3
24.7
12.4
9.9
91.7
215T
15.0
40.4
36.5
18.2
14.6
92.4
254T
20.0
53.1
48.0
24.0
19.2
93.0
256T
25.0
65.5
59.3
29.6
23.7
93.6
284T
30.0
78.7
71.1
35.6
28.5
93.6
286T
40.0
103.8
93.8
46.9
37.5
94.1
324T
50.0
128.6
116.3
58.2
46.5
94.5
326T
60.0
152.7
138.1
69.1
55.2
95.0
364T
75.0
189.3
171.2
85.6
68.5
95.4
365T
100.0
252.4
228.3
114.1
91.3
95.4
405T
125.0
—
—
142.7
114.1
95.4
444T
150.0
—
—
169.8
135.8
95.8
445T
EFF.
—
Efficiency
EISA
—
Energy Independence and Security Act of 2007
FLA
—
Full Load Amps
NEMA
—
National Electrical Manufacturers Association
ODP
—
Open Drip Proof
OPSB
—
Open Slotted Band
TEFC
—
Totally Enclosed Fan Cooled
MOTOR
HP
FLA FOR 3-PHASE, 60 Hz
VOLTAGES
EFF.
(%)
NEMA
FRAME
208
230
460
575
1.0
3.9
3.5
1.8
1.4
77.0
143T
1.5
4.9
4.4
2.2
1.8
84.0
143T
2.0
6.3
5.7
2.8
2.3
85.5
145T
3.0
9.4
8.5
4.3
3.4
85.5
145T
5.0
15.4
13.9
6.9
5.6
86.5
182T
7.5
22.0
19.9
9.9
8.0
88.5
184T
10.0
28.7
25.9
13.0
10.4
89.5
213T
15.0
42.4
38.3
19.1
15.3
90.2
215T
20.0
55.5
50.2
25.1
20.1
91.0
254T
25.0
68.3
61.8
30.9
24.7
91.7
256T
30.0
82.0
74.1
37.1
29.6
91.7
284T
40.0
107.6
97.3
48.7
38.9
92.4
286T
50.0
132.8
120.1
60.0
48.0
93.0
324T
60.0
157.3
142.3
71.1
56.9
93.6
326T
75.0
196.6
177.8
88.9
71.1
93.6
364T
100.0
262.2
237.1
118.6
94.8
93.6
365T
125.0
—
—
146.6
117.3
94.1
404T
150.0
—
—
176.0
140.8
94.1
405T
MOTOR
HP
FLA FOR 3-PHASE, 60 Hz
VOLTAGES
EFF.
(%)
NEMA
FRAME
208
230
460
575
1.0
3.9
3.5
1.8
1.4
77.0
143T
1.5
4.9
4.4
2.2
1.8
84.0
143T
2.0
6.3
5.7
2.8
2.3
85.5
145T
3.0
9.2
8.3
4.2
3.3
86.5
182T
5.0
14.7
13.3
6.6
5.3
88.5
184T
7.5
21.5
19.5
9.7
7.8
89.5
213T
10.0
28.2
25.5
12.8
10.2
90.2
215T
15.0
41.6
37.6
18.8
15.1
91.0
254T
20.0
55.5
50.2
25.1
20.1
91.0
256T
25.0
68.3
61.8
30.9
24.7
91.7
284T
30.0
82.0
74.1
37.1
29.6
91.7
286T
40.0
107.6
97.3
48.7
38.9
92.4
324T
50.0
132.8
120.1
60.0
48.0
93.0
326T
60.0
157.3
142.3
71.1
56.9
93.6
364T
75.0
196.6
177.8
88.9
71.1
93.6
365T
100.0
259.4
234.6
117.3
93.8
94.1
405T
125.0
—
—
143.9
115.1
95.0
444T
150.0
—
—
172.6
138.1
95.0
445T