4.10 CONTROLLER FUNCTION CODES
CnF64
Enable Fan Pulsing Logic
0-in
1-out
CnF66
High Speed Evaporator Fan Option
0-off
1-on
CnF67
Air Heaters
0-out
1-in
CnF68
Enable Default Pulsing Temperature
0-out
1-in
CnF70
Enable XtendFRESH Logic
0-out
1-in
CnF71
XtendFRESH Pretrip/Trip Start Default State
OFF
On
CnF72
Enhance Economy Mode
OFF
On
CnF73
Custom Defrost Mode
0-out
1-in
Table 4–3 Controller Function Codes
CODE #
TITLE
DESCRIPTION
NOTICE
If the function is not applicable, the display will read “-----”
Display Only Functions - Cd01 through Cd26 are display only functions.
Display Only Functions
Cd01
Digital Unloader Valve
Closed (%)
Displays the DUV percent closed. The right display reads 100% when
the valve is fully closed. The valve will usually be at 10% on start up of
the unit except in very high ambient temperatures.
Cd03
Compressor Motor Current
The current sensor measures current draw in lines L1 & L2 by all of the
high voltage components. It also measures current draw in compres-
sor motor leg T3. The compressor leg T3 current is displayed.
Cd04
Cd05
Cd06
Line Current,
Phase A
Line Current,
Phase B
Line Current,
Phase C
The current sensor measures current on two legs. The third unmea-
sured leg is calculated based on a current algorithm. The current mea-
sured is used for control and diagnostic purposes. For control
processing, the highest of the Phase A and B current values is used for
current limiting purposes. For diagnostic processing, the current draws
are used to monitor component energization. Whenever a heater or a
motor is turned ON or OFF, the current draw increase/reduction for that
activity is measured. The current draw is then tested to determine if it
falls within the expected range of values for the component. Failure of
this test will result in a Pre-trip failure or a control alarm indication.
Cd07
Main Power Voltage
The main supply voltage is displayed.
Cd08
Main Power Frequency
The value of the main power frequency is displayed in Hertz. The fre-
quency displayed will be halved if either fuse F1 or F2 is bad (alarm
code AL21).
Cd09
Ambient Temperature
The ambient sensor reading is displayed.
Cd10
Evaporator Temperature
Sensor
Evaporator temperature sensor reading is shown on the right display.
Cd11
Compressor Discharge Tem-
perature
Compressor discharge temperature sensor reading, using compressor
dome temperature, is displayed.
Table 4–2 Controller Configuration Variables (Continued)
CONFIG. #
TITLE
DEFAULT
OPTION
Note: Configuration numbers not listed are not used in this application. These items may appear when loading T-365
3-20 configuration software to the controller but changes will not be recognized by the controller programming.
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......