6–1
T-365
SECTION 6
TROUBLESHOOTING
6.1
UNIT WILL NOT START OR STARTS THEN STOPS
Condition
Possible Cause
Remedy/Refer-
ence Section
No power to unit
External power source OFF
Turn On
Start
−
Stop switch OFF or defective
Check
Circuit breaker tripped or OFF
Check
Autotransformer not connected
Loss of control power
Circuit breaker OFF or defective
Check
Control transformer defective
Replace
Fuse (F3A/F3B) blown
Check
Start
−
Stop switch OFF or defective
Check
Component(s) not operating
Evaporator fan motor internal protector open
Condenser fan motor internal protector open
Compressor internal protector open
High pressure switch open
Heat termination thermostat open
Replace
Malfunction of current sensor
Replace
6.2
UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING
Condition
Possible Cause
Remedy/Refer-
ence Section
Container
Hot load
Normal
Defective box insulation or air leak
Repair
Refrigeration system
Shortage of refrigerant
Evaporator coil covered with ice
Evaporator coil plugged with debris
Air bypass around evaporator coil
Check
Controller set too low
Reset
Compressor service valves or liquid line shutoff valve par-
tially closed
Open valves
completely
Dirty condenser
Compressor worn
Current limit (function code Cd32) set to wrong value
Economizer solenoid valve malfunction
Digital unloader valve stuck open
Electronic expansion valve
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......