5–1
T-316
SECTION 5
OPERATION
5.1
INSPECTION (BEFORE STARTING)
WARNING
!
Beware of unannounced starting of the evaporator and condenser fans. The unit may cycle the
fans and compressor unexpectedly as control requirements dictate.
a. If container is empty, check inside for the following:
1. Check channels or “T” bar floor for cleanliness. Channels must be free of debris for proper air circulation.
2. Check container panels, insulation and door seals for damage. Effect permanent or temporary repairs.
3. Visually check evaporator fan motor mounting bolts for proper securement (refer to
4. Check for dirt or grease on evaporator fan or fan deck and clean if necessary.
5. Check evaporator coil for cleanliness or obstructions. Wash with fresh water.
6. Check defrost drain pans and drain lines for obstructions and clear if necessary. Wash with fresh water.
7. Check panels on refrigeration unit for loose bolts and condition of panels. Make sure T.I.R. devices are
in place on access panels.
b. Check condenser coil for cleanliness. Wash with fresh water.
c. Open control box door. Check for loose electrical connections or hardware.
d. Check color of moisture-liquid indicator.
e. Check oil level in compressor sight glass.
5.2
CONNECT POWER
WARNING
!
Do not attempt to remove power plug(s) be fore turning OFF start-stop switch (ST), unit circuit
breaker(s) and external power source.
WARNING
!
Make sure the power plugs are clean and dry before connecting to any power receptacle.
5.2.1
Connection To 380/460 vac Power
1. Make sure start-stop switch (ST, on control panel) and circuit breaker (CB-1, in the control box) are in posi-
tion “0” (OFF).
2. Plug the 460 vac (yellow) cable into a de-energized 380/460 vac, 3-phase power source. Energize the
power source. Place circuit breaker (CB-1) in position “I” (ON). Close and secure control box door
5.2.2
Connection to 190/230 vac Power
An autotransformer (
) is required to allow operation on nominal 230 volt power. It is fitted with a 230 vac
cable and a receptacle to accept the standard 460 vac power plug. The 230 volt cable is black in color while the
460 volt cable is yellow. The transformer may also be equipped with a circuit breaker (CB-2). The transformer is a
step up transformer that will provide 380/460 vac, 3-phase, 50/60 hertz power to the unit when the 230 vac power
cable is connected to a 190/230 vac, 3-phase power source.
Summary of Contents for 69NT40-541-001
Page 2: ......
Page 4: ......
Page 10: ...T 316 vi...
Page 14: ......
Page 20: ......
Page 24: ......
Page 36: ......
Page 138: ......
Page 141: ...8 3 T 316 Figure 8 2 SCHEMATIC DIAGRAM...
Page 142: ...T 316 8 4 Figure 8 3 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Page 150: ......
Page 154: ......
Page 155: ......