Table 8 — Control Manual Graphics
HUMIDITY OPTIONS #1
Determine what humidity sensors the 62X supply control will
look for. Common configurations include:
• OARH, SARH - for units without ECW. Unit will have
outdoor air and supply air relative humidity sensors
• OARH, ECRH, SARH - for units with ECW. Unit will
have outdoor air, entering coil (after ECW), and supply air
relative humidity sensors
• All others - not used with 62X.
AIR PRESSURE OPTIONS
Determine what DPT sensors the 62X control will look for. Com
-
mon configurations include:
• SF DPT - supply fan differential pressure transmitter
(duct)
• ZN DPT - zone (building) differential pressure transducer.
Can be used with supply fan or exhaust fan (not both)
• EF DPT - exhaust fan differential pressure transmitter
(duct), not used with 62X.
Archive Program
The program archive screen (
Home
Setup
isc Settings
Archive
) displays the control program archive status, archive
date, current time and date, and update archive option. See
Fig. 52. The controller can store two program archives in memo
-
ry. One slot is filled upon program installation, which usually oc
-
curs in the factory. The second can be filled by a field-initiated ar
-
chive. Use the Archive screen to check current archive status, cur
-
rent archive date, current archive number, and to archive the
program.
OPTION
STATUS
OPTION
STATUS
VALUE
DISPLAY
VALUE
DISPLAY
SF Option
1
None
Cooling Enabled By
1
OAE
2
Included
2
OAT
3
SFVFD AMS
3
OAT and OADP
4
SFVFD CAV
4
OAT or OAE
5
SFVFD DPT (ZN, Bldg)
5
OAT/SAT vs SAT
6
SFVFD DPT (Duct)
6
RAT
7
SFVFD ZAT
7
ZAT
EF Option
1
None
8
None
2
Included
Heating Enabled By
1
OAT
3
EFVFD AMS
2
OAT/SAT vs SAT
4
EFVFD CAV
3
RAT
5
EFVFD DPT (ZN, Bldg)
4
ZAT
6
EFVFD DPT (Duct)
5
None
7
EFVFD ZAT
Temp Option #1
1
None
HGRH Option
1
Lead On-Off
2
ECAT
2
Lead On-Off, SC
3
OAT
3
Lead Mod.
4
SAT ECAT, OAT
4
Lead Mod., SC
5
ECAT, SAT
5
Both On-Off
6
OAT, SAT
6
Both Mod.
7
ECAT, OAT, SAT
7
By Heating Only
Temp Option #2
1
None
Dehum Option
1
None
2
RAT
2
ECPD VS SADP SP
3
WExAT
3
ECAE
4
RAT, WExAT
4
MADP
Humidity Option #1
1
None
5
MAE
2
ECRH
6
OADP vs SADP SP
3
OARH
7
OAE
4
SARH
8
RARH
5
ECRH, OARH
9
SARH
6
ECRH, SARH
10
ZADP
7
OARH, SARH
11
Z-RH
8
ECRH, OARH, SARH
Heating Option
1
None
Humidity Option #2
1
None
2
Elec., 1 Stg
2
RARH
3
Elec., 2 Stg
Air Pressure Options
1
None
4
Elec., 3 Stg
2
EF-DPT
5
Elec., 4 Stg
3
SF-DPT
6
Elec., SCR
4
ZN-DPT
7
Gas, 2 STG
5
EF-DPT, SF-DPT
8
Gas, 4 Stg
6
EF-DPT, ZN-DPT
9
Gas, 8 Stg
7
SF-DPT, ZN-DPT
10
Gas, Mod
8
EF, SF, ZN-DPT
11
Hot Water
12
Steam