42
• If outdoor-air temperature is less than the Compressor
Lockout Temperature (
CA.LO
,
CB.LO
) configuration val-
ue, unit ca not cool.
• If outdoor-air temperature is greater than the Heating
Lockout Temperature (
HT.LO
) configuration value, unit
cannot heat.
Restart Procedure
Before attempting to restart the machine, check the alarm list
to determine the cause of the shut down. If the shutdown alarm
for a particular control function has occurred, determine and
correct the cause before allowing the unit to run under its own
control again. When there is problem, the unit should be diag-
nosed in Service Test mode. The alarms must be reset before
the control function can operate in either Normal mode or Ser-
vice Test mode.
Alarms and Alerts
VIEWING AND CLEARING UNIT ALARMS
Presence of active alarms will be indicated on the scrolling
marquee display by the Alarm Status light turning on and by
the number of active alarms being displayed in the automatic
View of Run Status. Presence of active alarms may also be sig-
naled on the Alarm Output terminals. Each alarm may also be
broadcast on the CCN network. Active alarms and past alarm
history can be reviewed and cleared via the local display or a
CCN device. The following menu locations are used for the lo-
cal display:
Alarms
R.CURR (Reset All Current Alarms)
Change to YES to reset all active alarms. Turning unit power
off will also reset all current alarms.
Alarms
R.HIST (Reset Alarm History)
Change to YES to reset the alarm history. Turning unit power
off will not reset the alarm history.
Alarms
CURR (Currently Active Alarms)
Use the ENTER key, then scroll through any alarm numbers
using the up and down arrow keys. Alarms are displayed in nu-
merical order.
Alarms
HIST (Alarm History)
Use the ENTER key, then scroll through any alarm numbers
using the up and down arrow keys. Up to 20 alarms are dis-
played in order of occurrence, with time and date.
The description for an alarm can be viewed on the scrolling
marquee display by pressing ESCAPE and ENTER keys si-
multaneously while displaying the alarm code number. Be sure
to expand description for each code, because in some cases
there are different possible descriptions and causes for the
same code number.
DIAGNOSTIC ALARM CODES AND POSSIBLE CAUSES
Alert Codes T051 and T055 (without Current Sensors)
These alerts can only be activated if set to Diagnose Compressor
Safety (
Configuration
COOL
D.CMP = Yes
). There are 4
different texts for each alert code. There are two different alerts
which have corresponding test mode alerts indicated with “Ser-
vice Test” in the expanded text. Pressing enter and esc on the
scrolling marquee or Navigator display to expand the T051 and
T055 alert will show you one of the below alerts. Make sure the
expanded text is read correctly before troubleshooting. Alert
codes T051 and T055 are for compressors A1 and B1 respective-
ly.
• Compressor Safety Trip
These alerts occur when the respective compressor has been
running for 25 sec and the Saturated Suction Pressure (
Pres-
sures
SSP.A or SSP.B
) reflects a change in compressor opera-
tion. A change in compressor operation is when the SSP chang-
es more than the Maximum Suction Change configuration
(
Configuration
COOL
MX.SA or MX.SB
) in a two second
window while running the compressor and persists for 40 sec-
onds. This alert can also occur when the respective compressor
is diagnosed with a high pressure switch trip. A high pressure
trip is when the compressor suction rises and falls two times
within 2 minutes.
When this occurs, the control turns off the compressor and logs
a strike for the respective circuit. These alerts reset automati-
cally. The possible causes are: high-pressure switch (HPS)
open, Condensate overflow switch (COFS) open, compressor
internal protection is open, or a wiring error (a wiring error
might not allow the compressor to start). The HPS and optional
COFS are wired in series with compressor relays on the MBB.
If one of these opens during compressor operation, the com-
pressor stops causing the control to activate this alert.
• Compressor Detected After Turnoff
These alerts occur when the respective compressor is turned
off but the Saturated Suction Pressure (
Pressures
SSP.A or
SSP.B
) does not reflect a shutdown. When shutting down a
compressor suction pressure must rise more than Maximum
Suction Change configuration (
Configuration
COOL
MX.SA
or
MX.SB
) within the first 10 seconds and stay above
it. When this occurs, the control turns off all of the compressor
relays, stays in cooling mode and keeps the indoor fan on. Use
the scrolling marquee to reset the alert. The possible causes are
a welded contactor, frozen compressor relay on MBB, or ad-
verse conditions.
Alert Codes T051 and T055 (with Current Sensors)
These alerts can only be activated if Current Sensing A1 or B1 is
enabled (
Configuration
COOL
CS.A1
or
CS.B1 = En-
abled
). There are 4 different texts for each alert code. There are
two different alerts which have corresponding test mode alerts
indicated with “Service Test” in the expanded text. Pressing en-
ter and esc on the scrolling marquee or Navigator display to ex-
pand the T051 and T055 alert will show you one of the below
alerts. Make sure the expanded text is read correctly before trou-
bleshooting. Alert codes T051 and T055 for compressors A1 and
B1 respectively.
• Compressor Safety Trip
These alerts occur when the Current Sensor (CS) does not de-
tect compressor current during compressor operation. When
this occurs, the control turns off the compressor and logs a
strike for the respective circuit. These alerts reset automatical-
ly. The possible causes are: high-pressure switch (HPS) open,
Condensate overflow switch (COFS) open, compressor inter-
nal protection is open, or a wiring error (a wiring error might
not allow the compressor to start). The HPS and optional
COFS are wired in series with compressor relays on the MBB.
If one of these opens during compressor operation, the com-
pressor stops causing the control to activate this alert.
• Compressor Detected After Turnoff
These alerts occur when the Current Sensor (CS) detects cur-
rent when the compressor should be off. When this occurs, the
control turns off all of the compressor relays, stays in cooling
mode and keeps the indoor fan on. Use the scrolling marquee
to reset the alert. The possible causes are a welded contactor,
frozen compressor relay on MBB, or adverse conditions.
Alert Codes T064 and T065 — Circuit Saturated Condensing
Temp Thermistor Failure
Alert codes T064 and T065 are for circuits A and B respective-
ly. These alerts occur when the temperature is outside the range
–40 to 240°F (–40 to 116°C). The cause of the alert is usually a
faulty thermistor, a shorted or open thermistor caused by a wir-
ing error, or a loose connection.
Alert Code T066 and T067 — Circuit Saturated Suction Tem-
perature Thermistor Failure
Alert codes T066 and T067 are for circuits A and B respective-
ly. These alerts occur when the unit’s suction transducers are
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......