background image

48LC*04---06

Nominal 3 to 5 Tons

Single Package Rooftop

Gas Heating/Electric Cooling Unit

with Puron

r

(R---410A) Refrigerant

Service and Maintenance Instructions

TABLE OF CONTENTS

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . .

UNIT ARRANGEMENT AND ACCESS

2

. . . . . . . . . . .

SUPPLY FAN (BLOWER) SECTION

4

. . . . . . . . . . . . . .

COOLING

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PURON

R

(R--410A) REFRIGERANT

8

. . . . . . . . . . . . . .

THERMOSTATIC EXPANSION VALVE (TXV)

9

. . . . .

COOLING CHARGING CHARTS

10

. . . . . . . . . . . . . . . .

CONVENIENCE OUTLETS

14

. . . . . . . . . . . . . . . . . . . .

SMOKE DETECTORS

15

. . . . . . . . . . . . . . . . . . . . . . . . .

PROTECTIVE DEVICES

22

. . . . . . . . . . . . . . . . . . . . . . .

GAS HEATING SYSTEM

23

. . . . . . . . . . . . . . . . . . . . . .

ECONOMIZER SYSTEMS

34

. . . . . . . . . . . . . . . . . . . . .

COMFORTLINK (FACTORY OPTION)

34

. . . . . . . . . . .

RTU OPEN CONTROL SYSTEM

34

. . . . . . . . . . . . . . . .

VFD OPERATION WITH REMOTE KEYPAD

34

. . . . .

WIRING DIAGRAMS

35

. . . . . . . . . . . . . . . . . . . . . . . . .

PRE--START--UP

38

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP, GENERAL

38

. . . . . . . . . . . . . . . . . . . . . . . .

FASTENER TORQUE VALUES

40

. . . . . . . . . . . . . . . . .

APPENDIX I. MODEL NUMBER SIGNIFICANCE

41

.

APPENDIX II. PHYSICAL DATA

42

. . . . . . . . . . . . . . . .

APPENDIX III. FAN PERFORMANCE

44

. . . . . . . . . . .

UNIT START-UP CHECKLIST

49

. . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment

can be hazardous due to system pressure and electrical

components. Only trained and qualified service personnel

should install, repair, or service air-conditioning

equipment. Untrained personnel can perform the basic

maintenance functions of replacing filters. Trained service

personnel should perform all other operations.

When working on air-conditioning equipment, observe

precautions in the literature, tags and labels attached to

the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations.

Have fire extinguishers available for all brazing

operations.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for brazing operations. Have

fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions attached to

the unit. Consult local building codes and National

Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety--alert
symbol

. When you see this symbol on the unit and in

instructions or manuals, be alert to the potential for

personal injury.

Understand the signal words DANGER, WARNING, and

CAUTION. These words are used with the safety--alert

symbol. DANGER identifies the most serious hazards

which

will

result in severe personal injury or death.

WARNING signifies a hazard which

could

result in

personal injury or death. CAUTION is used to identify

unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to

highlight suggestions which

will

result in enhanced

installation, reliability, or operation.

Summary of Contents for 48LC 05

Page 1: ...rm all other operations When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire extinguishers available for all brazing operations Follow all safety codes Wear safety glasses and ...

Page 2: ... Tag out this switch if necessary WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury death and or equipment damage Puron R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on Puron refrigerant equipment WARNING FIRE EXPLOSION HAZARD Failure to follow this warning could re...

Page 3: ...cleaned Return Air Filters Return air filters are disposable fiberglass media type Access to the filters is through the small lift out panel located on the rear side of the unit above the evaporator return air access panel See Fig 1 To remove the filters 1 Grasp the bottom flange of the upper panel 2 Lift up and swing the bottom out until the panel dis engages and pulls out 3 Reach inside and extr...

Page 4: ...1 2 in deflection Adjust belt tension by loosening the motor mounting plate front bolts and rear bolt and sliding the plate toward the fan to reduce tension or away from fan to increase tension Ensure the blower shaft and the motor shaft are parallel to each other pulleys aligned Tighten all bolts when finished To replace the belt 1 Use a belt with same section type or similar size Do not substitu...

Page 5: ...ew to 65 70 in lb 7 4 7 9 Nm See Fig 7 C08121 Fig 7 Tightening Locking Collar Motor When replacing the motor also replace the external tooth lock washer star washer under the motor mounting base this is part of the motor grounding system Ensure the teeth on the lock washer are in contact with the motor s painted base Tighten motor mounting bolts to 120 12 in lbs Changing fan wheel speed by changin...

Page 6: ...cult Surface loaded fibers must be completely removed prior to using low velocity clean water rinse Periodic Clean Water Rinse A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments However it is very important that the water rinse is made with a very low velocity water stream to avoid damaging the fin edges Monthly cleaning as described be...

Page 7: ...e is dirt below the surface of the coil use the Totaline environmentally sound coil cleaner CAUTION Totaline Environmentally Sound Coil Cleaner Application Instructions 1 Proper eye protection such as safety glasses is recom mended during mixing and application 2 Remove all surface loaded fibers and dirt with a vacu um cleaner as described above 3 Thoroughly wet finned surfaces with clean water an...

Page 8: ...em Puron R 410A refrigerant is provided in pink rose colored cylinders These cylinders are available with and without dip tubes cylinders with dip tubes will have a label indicating this feature For a cylinder with a dip tube place the cylinder in the upright position access valve at the top when removing liquid refrigerant for charging For a cylinder without a dip tube invert the cylinder access ...

Page 9: ...temperature at the outlet of the evaporator coil Replacing TXV 1 Recover refrigerant 2 Remove TXV support clamp using a 5 l6 in nut driver 3 Remove TXV using a backup wrench on connections to prevent damage to tubing 4 Remove equalizer tube from suction line of coil Use file or tubing cutter to cut brazed equalizer line ap proximately 2 inches above suction tube 5 Remove bulb from vapor tube insid...

Page 10: ...10 COOLING CHARGING CHARTS C14037 Fig 13 Cooling Charging Charts 3 Ton 48LC ...

Page 11: ...11 COOLING CHARGING CHARTS cont C14038 Fig 14 Cooling Charging Charts 4 Ton 48LC ...

Page 12: ...12 COOLING CHARGING CHARTS cont C14039 Fig 15 Cooling Charging Charts 5 Ton 48LC ...

Page 13: ...riction and remove Compressor Operates Continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge Leaking valves in compressor Replace compressor Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil or ...

Page 14: ...ds 7 Reapply power to the compressor The suction and discharge pressure levels should now move to their normal start up levels NOTE When the compressor is rotating in the wrong direction the unit makes an elevated level of noise and does not provide cooling Filter Drier Replace whenever refrigerant system is exposed to atmosphere Only use factory specified liquid line filter driers with working pr...

Page 15: ...t is not intended to provide 15 amps loading for continuous duty loads such as electric heaters for overnight use Observe a 50 limit on circuit loading above 8 amps i e limit loads exceeding 8 amps to 30 minutes of operation every hour Maintenance Periodically test the GFCI receptacle by pressing the TEST button on the face of the receptacle This should cause the internal circuit of the receptacle...

Page 16: ...sor s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a shorter exhaust tube The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber When a sufficient amount of smoke is detected in the sensing chamber the sensor signals an alarm state and the controller automatically tak...

Page 17: ... tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location This sensor is shipped in a flat mounting location Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected See installation steps below Return Air Sampling Tube C08129 Fig 23 Re...

Page 18: ... open on smoke alarm condition de energizing the ORN conductor Highlight C 24 v power signal via ORN lead is removed at Smoke Detector input on CTB all unit operations cease immediately RTU Open Controls Unit operating functions fan cooling and heating are terminated as described above In addition Highlight D On smoke alarm condition the smoke detector NO Alarm contact will close supplying 24 v po...

Page 19: ...tal changes A sensor that can no longer compensate for environmental changes is considered 100 dirty and requires cleaning or replacing You must use a field provided SD MAG test magnet to initiate a sensor dirty test The sensor s Dirty LED indicates the results of the dirty test as shown in Table 2 OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern...

Page 20: ...on relay For more information see Changing sensor dirty test operation OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern If the test reset station s key switch is left in the RESET TEST position for longer than seven seconds the detector will automatically go into the alarm state and activate all automatic alarm responses CAUTION OPERATIONAL TEST ...

Page 21: ... close S The controller s remote alarm LED output is activated turned on S The controller s high impedance multiple fan shutdown control line is pulled to ground Trouble state The SuperDuct duct smoke detector enters the trouble state under the following conditions S A sensor s cover is removed and 20 minutes pass before it is properly secured S A sensor s environmental compensation limit is reach...

Page 22: ...issing repair or replace as required Controller s Power LED is Off 1 Make sure the circuit supplying power to the control ler is operational If not make sure JP2 and JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply input terminals If power is not present replace or re pair wiring as required Remote Test Reset Station s Trouble ...

Page 23: ...Fig 31 INDUCED DRAFT MOTOR MOUNTING PLATE INDUCED DRAFT MOTOR MANIFOLD PRESSURE TAP VESTIBULE PLATE FLUE EXHAUST ROLLOUT SWITCH BLOWER HOUSING GAS VALVE BURNER SECTION C06152 Fig 30 Burner Section Details Limit Switch and Shield C08284 Fig 31 Limit Switch Location Fuel Types and Pressures Natural Gas The 48LC unit is factory equipped for use with Natural Gas fuel at elevation under 2000 ft 610 m S...

Page 24: ...sult in gas with a high concentration of impurities additives and residues that have settled to the bottom of the tank Operation under these conditions can cause harm to the heat exchanger system Contact your fuel supplier if this condition is suspected Flue Gas Passageways To inspect the flue collector box and upper areas of the heat exchanger 1 Remove the combustion blower wheel and motor as sem...

Page 25: ... Seal Strips Sponge Rubber Regulator Gasket Regulator Baffle Assembly Low NOx only Retainer Support Insulation Assembly Wind Cap Assembly shown inverted as shipped Burner Assembly Inducer Fan Motor Assembly C08227 Fig 34 Heat Exchanger Assembly 48LC ...

Page 26: ...n Re moval and Replacement of Gas Train section above 2 Inspect burners if dirty remove burners from rack Mark each burner to identify its position before re moving from the rack 3 Use a soft brush to clean burners and cross over port as required 4 Adjust spark gap See Fig 38 5 If factory orifice has been removed check that each orifice is tight at its threads into the manifold pipe and that orifi...

Page 27: ...if they are blue in appearance and that the flames are approximately the same for each burner 10 Turn off unit remove pressure manometer and re place the 1 8 in pipe fitting on the gas manifold See Fig 35 Limit Switch Remove blower access panel Limit switch is located on the fan deck See Fig 31 Burner Ignition Unit is equipped with a direct spark ignition 100 lockout system Integrated Gas Unit Con...

Page 28: ...codes will be displayed in numerical sequence Indicates a code that is not an error The unit will continue to operate when this code is displayed IMPORTANT Refer to Troubleshooting Table 13 and Table 14 for additional information Orifice Replacement This unit uses orifice type LH32RFnnn where nnn indicates orifice reference size When replacing unit orifices order the necessary parts via Carrier RC...

Page 29: ...Speed sensor gas section analog input J1 1 3 FS T1 Flame sensor gas section switch input W Heat stage 1 CTB 24 VAC J2 2 RS Rollout switch gas section switch input J2 5 6 LS Limit switch fan section switch input J2 7 8 CS Centrifugal switch not used switch input J2 9 10 OUTPUTS L1 CM Induced draft combustion motor gas section line VAC IFO Indoor fan control box relay J2 1 GV Gas valve heat stage 1 ...

Page 30: ...m 72 000 BTUH Nominal 115 000 BTUH Nominal 150 000 BTUH Nominal NG Orifice Size LP Orifice Size NG Orifice Size LP Orifice Size NG Orifice Size LP Orifice Size 0 2000 610 331 514 331 503 30 463 2000 610 351 514 351 514 30 473 3000 914 351 524 351 514 311 473 4000 1219 361 524 361 514 311 483 5000 1524 361 524 361 514 311 483 6000 1829 372 524 372 524 311 483 7000 2134 382 534 382 524 321 493 8000 ...

Page 31: ...is 50_F continuous and 45_F intermittent for standard heat exchangers and 40_F continuous and 35_F intermittent for stainless steel heat exchangers To operate at lower mixed air temperatures a field supplied outdoor air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation Wire the outdoor air thermostat...

Page 32: ...s pressure at manifold Clock gas meter for input If too low increase manifold pressure or replace with correct orifices Unit undersized for application Replace with proper unit or add additional unit Restricted airflow Clean filter replace filter or remove any restrictions Blower speed too low Use high speed tap increase fan speed or install optional blower as suitable for individual units Limit s...

Page 33: ...inutes Check igniter and flame sen sor electrode spacing gaps etc Check flame sense and igniter wiring Check gas valve operation and gas supply Check gas valve connections to IGC terminals BRN lead must be on Pin 11 6 Flashes Induced Draft Motor Fault If heat off no gas heating If heat on gas valve Off and inducer On Inducer sense nor mal or heat call W Off Inducer sense On when heat call Off or i...

Page 34: ...BLUE RED WHITE 24 VAC 4 20mA SIGNAL YELLOW ECONOMI ER2 PLUG 4 3 5 2 8 7 1 10 11 9 12 6 C14042 Fig 43 EconoMi er2 with 4 to 20 mA Control Wiring ComfortLINK Factory Option For details on operating 48LC 04 06 units equipped with the factory installed ComfortLINK option refer to Controls Start Up Operation and Troubleshooting for 48 50LC 04 06 Single Package Rooftop Unit with ComfortLINK Controls Cat...

Page 35: ...35 WIRING DIAGRAMS C14043 Fig 44 Unit Wiring Diagram Power 208 230V 460V 3 Phase 48LC ...

Page 36: ...36 C14044 Fig 45 Unit Wiring Diagram Power 575V 3 Phase 48LC ...

Page 37: ...37 C14045 Fig 46 Unit Wiring Diagram Control 48LC ...

Page 38: ...it for initial start up 1 Remove all access panels 2 Read and follow instructions on all WARNING CAUTION and INFORMATION labels attached to or shipped with unit PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Wear safety glasses and gloves when h...

Page 39: ...not provide cooling Cooling Set space thermostat to OFF position To start unit turn on main power supply Set system selector switch at COOL position and fan switch at AUTO position Adjust thermostat to a setting approximately 5_F 3_C below room temperature Both compressors start on closure of contactors Check unit charge Refer to Refrigerant Charge section Reset thermostat at a position above room...

Page 40: ...the evaporator fan off delay to 180 seconds To restore the original default value reset the power to the unit To shut off unit set system selector switch at OFF position Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting Ventilation Continuous Fan Set fan and system selector switches at ON and OFF positions ...

Page 41: ...cooling capacity Air Intake Exhaust Options Nominal Cooling Tons A None 04 3 Ton B Temp econo w baro relief 05 4 Ton E Enthalpy econo w baro relief 06 5 Ton N Ultra Low Leak temp econo w baro relief Sensor Options R Ultra Low Leak Enthalpy econo w A None baro relief B RA smoke detector C SA smoke detector D RA SA smoke detector Base Unit Controls E CO2 sensor 0 Electromechanical F RA smoke detecto...

Page 42: ...meter in 10 x 10 10 x 10 11 x 10 Medium Static Motor Qty Drive type 1 Belt w VFD 1 Belt w VFD 1 Belt w VFD Max BHP 1 7 1 7 2 4 RPM range 770 1175 920 1303 1035 1466 Motor Frame Size 56 56 56 Fan Qty Type 1 Centrifugal 1 Centrifugal 1 Centrifugal Fan Diameter in 10 x 10 10 x 10 10 x 10 High Static Motor Qty Drive type 1 Belt w VFD 1 Belt w VFD 1 Belt w VFD Max BHP 2 4 2 9 2 9 RPM range 1035 1466 12...

Page 43: ...size 1 2 in NPT 1 2 in NPT 1 2 in NPT Rollout switch opens closes 195 115 195 115 195 115 Temperature rise range F 55 85 35 65 30 65 of stages of burners total 1 or 2 3 1 or 2 3 HIGH Connection size 1 2 in NPT 1 2 in NPT Rollout switch opens closes 195 115 195 115 Temperature rise range F 50 80 40 80 Low NOx Gas Heat of stages of burners total 1 2 1 2 1 2 LOW Connection size 1 2 in NPT 1 2 in NPT ...

Page 44: ...tes field supplied drive is required Medium static 770 1175 RPM 1 2 BHP max High static 1035 1466 RPM 2 4 BHP max Table 17 48LC 004 3 phase 3 ton horizontal supply CFM Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 900 582 0 14 715 0 24 825 0 35 921 0 48 1007 0 63 975 606 0 16 735 0 26 843 0 38 938 0 51 1023 0 66 1050 630 0 18 756 0 29 862 0 41...

Page 45: ...icates field supplied drive is required Medium static 920 1303 RPM 1 7 BHP max High static 1208 1639 RPM 2 9 BHP max Table 19 48LC 005 3 phase 4 ton horizontal supply CFM Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1200 681 0 24 800 0 35 902 0 48 992 0 63 1074 0 78 1300 717 0 29 831 0 41 930 0 54 1019 0 69 1099 0 85 1400 753 0 34 863 0 46 95...

Page 46: ...icates field supplied drive is required Medium static 1035 1466 RPM 2 4 BHP max High static 1303 1687 RPM 2 9 BHP max Table 21 48LC 006 3 phase 5 ton horizontal supply CFM Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1500 798 0 41 906 0 55 1002 0 71 1088 0 87 1167 1 05 1625 845 0 50 949 0 65 1041 0 81 1125 0 98 1202 1 17 1750 893 0 60 993 0 7...

Page 47: ...47 48LC ...

Page 48: ...rp D 7310 W Morris St D Indianapolis IN 46231 Edition Date 01 14 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48LC 04 06 01SM Replaces New 48LC ...

Page 49: ...N IS LEVEL j CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS j CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES OR SHARP METAL EDGES j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS III START UP REFER TO UNIT SERVICE MAINTENANCE MANUAL FOR START UP INSTRUCTIONS ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 CI...

Page 50: ...ET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS IF EQUIPPED Copyright 2014 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Edition Date 01 14 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48LC 04 06 01SM Replaces New 48LC ...