Table 3B — Fan Performance Data, 48HJ015, 575-V Units
AIRFLOW
(CFM)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
3750
741
510
0.58
854
715
0.82
952
921
1.05
1041
1030
1.29
1124
1344
1.53
4000
773
647
0.74
882
859
0.98
978
1071
1.22
1064
1285
1.46
1145
1502
1.71
4250
806
796
0.91
912
1015
1.16
1004
1233
1.40
1089
1452
1.65
1167
1674
1.91
4500
839
958
1.09
942
1183
1.35
1032
1407
1.60
1114
1632
1.86
1191
1859
2.12
4750
873
1134
1.29
972
1365
1.56
1060
1595
1.82
1140
1825
2.08
1215
2056
2.34
5000
908
1323
1.51
1003
1560
1.78
1089
1796
2.05
1167
2032
2.32
1241
2268
2.58
5250
942
1527
1.74
1035
1769
2.02
1118
2011
2.29
1195
2252
2.57
1267
2494
2.84
5500
978
1745
1.99
1067
1992
2.27
1148
2240
2.55
1223
2487
2.83
1293
2733
3.11
5750
1013
1978
2.25
1099
2230
2.54
1179
2484
2.83
1252
2736
3.12
1321
2988
3.40
6000
1049
2227
2.54
1132
2483
2.83
1210
2742
3.12
1282
2999
3.42
1349
3257
3.71
6250
1085
2491
2.84
1166
2751
3.13
1241
3015
3.44
1312
3279
3.74
1378
3541
4.03
AIRFLOW
(CFM)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
3750
1203
1562
1.78
1277
1784
2.03
1349
2010
2.29
1417
2240
2.55
1483
2473
2.82
4000
1222
1724
1.96
1294
1950
2.22
1364
2180
2.48
1431
2413
2.75
1495
2650
3.02
4250
1242
1900
2.16
1313
2129
2.43
1381
2362
2.69
1446
2599
2.96
1509
2839
3.23
4500
1264
2089
2.38
1333
2322
2.65
1399
2558
2.91
1463
2799
3.19
1525
3042
3.47
4750
1286
2290
2.61
1354
2528
2.88
1419
2769
3.15
1482
3012
3.43
1542
3259
3.71
5000
1310
2507
2.86
1376
2748
3.13
1440
2992
3.41
1501
3240
3.69
1560
3489
3.98
5250
1335
2737
3.12
1399
2983
3.40
1461
3230
3.68
1522
3481
3.97
—
—
—
5500
1360
2981
3.40
1423
3231
3.68
1484
3483
3.97
1543
3737
4.26
—
—
—
5750
1386
3241
3.69
1448
3495
3.98
1508
3750
4.27
—
—
—
—
—
—
6000
1413
3514
4.00
1474
3773
4.30
1532
4032
4.59
—
—
—
—
—
—
6250
1440
3803
4.33
1500
4066
4.63
1558
4330
4.93
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates standard operating range.
2.
indicates field-supplied motor and drive required.
3. All other numbers indicate field-supplied drive required.
4. Factory shipped motor drive range is 1201 to 1462 rpm. Other rpms
require a field-supplied drive.
5. Static pressure losses (i.e., economizer) must be added to exter-
nal static pressure before entering Fan Performance table. See
Table 7 for accessory/FIOP static pressure information.
6. Interpolation is permissible. Do not extrapolate.
7. Maximum continuous bhp is 3.45 and the maximum continuous
watts are 3065. Extensive motor and drive testing on these units
ensures that the full horsepower range of the motor can be uti-
lized with confidence. Using your fan motors up to the watts rating
shown will not result in nuisance tripping or premature motor fail-
ure. Unit warranty will not be affected.
14
Summary of Contents for 48EJ
Page 24: ...Fig 38 Typical Wiring Schematic 48HJ025 Shown 24 ...
Page 25: ...Fig 38 Typical Wiring Schematic 48HJ025 Shown cont 25 ...
Page 26: ...Fig 39 Typical Component Arrangement 48HJ025 Shown 26 ...
Page 28: ......
Page 29: ......
Page 31: ......