Table 6 —

 

Troubleshooting

LEGEND

Replacement Parts — 

Quote the unit model number

and unit serial number when ordering replacement parts or
contacting the factory about the unit. This information can be
found on the serial plate attached to the unit. See Fig. 41.

ERROR

DESCRIPTION

POSSIBLE CAUSES

POSSIBLE SOLUTIONS

DD

Heating / Cooling Mode Conflict

System is in cooling or fan only mode and 
heating signal is received from a unit on the 
system.

All units should be in cooling mode for system to 
stay in cooling mode.

System is in heating mode and cooling 
signal is received from a unit in the system.

All units should be in heating mode.

E1

Communication Error Between 
Indoor & Outdoor Unit

Signal wires are short-circuited or 
disconnected.

Check or reconnect signal wire.

Signal wire close to electromagnetic 
source.

Distance signal wires from electromagnetic 
source.

PC board fault.

Replace PC board.

E2, E4, 

E5

Check Temperature Sensor

Loose connection at port on PC board.

Tighten the connection at port on PC board.

Sensor is short-circuited.

Using multi-meter, measure resistance of the 
sensor. If the resistance is £ 100 ohms, change 
the sensor.

PC board fault.

Replace PC board.

E6

DC Fan Motor

Operating beyond limits.

Check and correct external static pressure on the 
unit.

DC motor fault.

Replace DC motor.

PC board fault.

Replace PC board.

E7

EEPROM Error (Data Storage)

Chip or PC board fault.

Replace PC board.

E9

Communication Error Between 
Indoor Unit and Controller

Signal wires are short-circuited or 
disconnected.

Check or reconnect signal wires.

Signal wires close to electromagnetic 
source.

Distance signal wires from electromagnetic 
source.

PC board fault.

Replace PC board.

EB

EEV Error

EEV wires are short-circuited or 
disconnected.

Replace EEV wires.

EEV stop.

Replace EEV.

PC board fault.

Replace PC board.

ED

Outdoor Unit Error

Outdoor unit fault.

Refer to outdoor unit troubleshooting guide.

EE

Condensate Error

Loose connection or disconnected.

Tighten the connection or reconnect at port on 
PC board.

Water level float is stuck.

Inspect the slope.

Trap slope is too steep.

Adjust the trap slope.

Drain pipe is too long.

Adjust the length of drain pipe.

Drain pump faulty.

Replace the drain pump.

FE

No Address When Power ON for first 
time

Indoor unit without address.

Run automatic addressing option at the outdoor 
unit.
Use remote wireless or wired controller to 
readdress indoor unit.

UU

MDC Auto System-Check Mode

MDC fault

Refer to MDC troubleshooting guide.

EEV

Electronic Expansion Valve

EEPROM —

Electronically Erasable Programmable Read-only 
Memory

MDC

Multiport Distribution Controller

PC

Process Controller

MODEL

R410A

HIGH

LOW

MEDIUM STATIC DUCT UNIT

15 A

REFRIGERANT

1.25 A

1 A

100W (1/6HP)

40VMM007A--3

320 PSIG

208/230V-1Ph-60Hz

580 PSIG

DESIGN
PRESSURE

POWER SUPPLY

MINIMUM CIRCUIT AMPACITY

FLA

FAN MOTOR

MAX FUSE OR HACR BREAKER

OUTPUT

CONFORMS TO UL STD 1995
CERTIFIED TO CSA STD.
C22. 2 No. 236

3124627

ELECTRIC CHARACTERISTICS ARE
ONLY FOR INDOOR UNIT.

SERIAL NO.

Carrier Corporation

1716V00001

Fig. 41 — Unit Serial Plate (Example)

Summary of Contents for 40VMM

Page 1: ...ectrical Code CSA Canadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or...

Page 2: ...t size Figures 2 and 3 show unit dimensions Figures 4 12 show fan performance curves CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local co...

Page 3: ...Heat insulation Condensate connection 1 For drainage Clamp 1 Connect the drain hose to condensate connection Copper nut 1 Use for pipe connection LED display panel 1 Operation and error display Copper...

Page 4: ...BA Low 31 8 32 7 31 4 31 9 34 2 39 4 40 8 41 2 Medium 32 1 32 4 33 7 32 7 33 6 36 3 42 3 43 8 43 8 High 33 2 32 7 36 8 35 9 38 6 42 0 46 7 47 8 48 0 UNIT Unit Dimensions W x H x D in 39 1 4 x 8 1 4 x...

Page 5: ...w Mounting Brackets 4 Fig 3 40VMM012 048 Dimensions NOTE All dimensions shown in inches 40VMM UNIT SIZE DIMENSION in A B C D E F G H I J K L M 012 36 1 4 10 5 8 25 22 1 2 39 3 4 2 5 8 28 1 3 8 7 10 1...

Page 6: ...M a x E S P Lower Limit of ESP ESP ESP M Speed L Speed Fig 4 Size 007 Fan Curves LEGEND ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max CFM SP in Mid CFM SP...

Page 7: ...r Limit of ESP Min ESP Lower Limit of ESP Rating ESP Lower Limit of ESP Min ESP Fig 6 Size 012 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max CFM...

Page 8: ...mit of ESP Min ESP Lower Limit of ESP Rating ESP Lower Limit of ESP Min ESP Fig 8 Size 018 Fan Curves LEGEND ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max...

Page 9: ...imit of ESP Min ESP Lower Limit of ESP Rating ESP Lower Limit of ESP Min ESP Fig 10 Size 030 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max CFM S...

Page 10: ...Max CFM SP in Mid CFM SP in Min CFM SP in 0 10 H 1509 0 00 1370 0 10 1165 0 20 0 20 H 1576 0 07 1370 0 18 1165 0 28 0 30 H 1576 0 17 1370 0 29 1165 0 36 0 40 H 1576 0 31 1370 0 41 1165 0 47 0 50 H 157...

Page 11: ...ll trades in their parts of the installation Units must be installed in compliance with all applicable local code requirements IDENTIFYING AND PREPARING UNITS Be sure power requirements match availabl...

Page 12: ...ews that secure the filter frame to the rear of the unit 2 Remove the screws that secure the return air cover plate to the bottom of the unit and set the cover plate aside See Fig 15 below Apply Foam...

Page 13: ...unit and ends at the outdoor unit or MDC Multiport Distribution Controller for Heat Recovery systems The refrigerant piping should be dry and free of dust and other impurities The bending angle of the...

Page 14: ...sturbance on the controls side See Fig 22 and 23 for wiring diagrams NOTE The indoor unit requires its own power supply Indoor units are not powered through outdoor units WARNING Electrical shock can...

Page 15: ...XS1 4 XT1 2 Terminal Block Optional Component or Field Wiring Fig 22 40VMM007 009 Typical Wiring Diagram EEV A H B H FM ALARM PUMP CN24 CN2 N3 CN1 C 8 EARTH Y G CN15 CN9 CN17 Y G L1 L2 controller To w...

Page 16: ...t use copper conductors only ACB Auxiliary Control Board ALARM Warning Lamp AUXH Output For Auxiliary Heat CS Condensate Switch CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN DC...

Page 17: ...Fig 30 and 31 for typical communication wiring of the heat pump and the heat recovery systems Fig 25 Shearing Outdoor Connector Fig 26 Stripping The Wire Fig 27 Connecting Communication Wire to Outdoo...

Page 18: ...No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 HA...

Page 19: ...ontroller HA HB L1 L3 L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resisto...

Page 20: ...any water It may take time for the water to travel depending on the length of the drain pipe 4 During this test check any bends or joints for leakage System Operation Check Once the installation and...

Page 21: ...00001 Indoor unit addressing can be performed using the wireless remote controller When using the wireless controller the user must maintain a line of sight with the receiver on the indoor unit See Fi...

Page 22: ...DU ADDRESSING Press MENU OK to access this setting 3 Press TEMP UP or TEMP DOWN to choose the address you want to set see Fig 39 Press MENU OK to send this address to the IDU 4 Press BACK twice or wai...

Page 23: ...one Heating Cooling Mode Conflict E1 None Communication Error Between Indoor and Outdoor Unit E2 None Check Indoor Ambient Temperature Sensor T1 E4 None Check Evaporator Temperature Sensor T2B E5 None...

Page 24: ...on Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal wires from ele...

Page 25: ...cated on the main control board When J1 jumper is not in place Auto Restart function is enabled When J1 jumper is in place Auto Restart function is disabled The default setting for J1 is without the j...

Reviews: