background image

20

ACB Interface

 — 

The ACB interface is a dry contact

board that can output up to four signal controlling devices.
Refer to Fig. 22, 23, and 32 for connecting the ACB interface
board and devices.

START-UP

Pre-Start Check — 

Once installation is complete, make

the following pre-start checks:

1.

All indoor and outdoor units are properly installed.

2.

All piping and insulation is complete.

3.

All electrical connections (both power and control) are
properly terminated.

4.

All condensate drains are installed correctly.

5.

The power supply is the right voltage and frequency. 

6.

The units are properly grounded in accordance with
current electrical codes. 

7.

Suction and liquid line service valves are in the open
position.

Drain Pump and Drainage Test  — 

 

Follow these

steps to perform the test:

1.

Remove the test cover by rotating it counter-clockwise as
shown in Fig. 33.

2.

Use a piece of tubing or pipe to fill the drain pump
reservoir with 70 oz. of water. See Fig. 34 below.

3.

Turn the unit ON in cooling mode. The pump comes on.
Watch the end of the drain pipe for any water. It may take
time for the water to travel depending on the length of the
drain pipe.

4.

During this test, check any bends or joints for leakage.

System Operation Check

 — 

Once the installation

and pre-start checks are complete, perform the following steps:

1.

Using the remote controller, select cooling or heating
mode to check the operation of the system.

2.

While the system is in operation, check the following on
indoor unit:

a. Switches or buttons on the remote controller are

easy to push.

b. Indicator light is showing normal operation and no

error is indicated.

c. Swing mode of air louvers is working (if applica-

ble to unit).

d. Drain pump operation is normal (if applicable).
e. No abnormal vibration or noise.

IMPORTANT: The system can connect 64 indoor units,
with different system addresses. If two indoor units in the
same system have identical addresses, abnormal operation
will occur.

LEGEND

ACB

Auxiliary Control Board

FAN

Output for fan Operation

CTON

Output for Cooling Operation

HTON

Output for Heating Operation

AUXH

Output for Auxiliary Heat

Fig. 32 — ACB Interface

MAX AMPS

1A

MAX VOLTAGE

24V

CN50

CN51

ACB interface 

FAN CTON HTON AUXH

Fig. 33 — Test Cover

  C

L O   

S ED 

 

O

P

 E 

E

 D

 

O

  O

 CSL

 

 P E N 

Test Cover

Fig. 34 — Tube/Pipe Insert

Tube/Pipe

 

Summary of Contents for 40VMM

Page 1: ...ectrical Code CSA Canadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or...

Page 2: ...t size Figures 2 and 3 show unit dimensions Figures 4 12 show fan performance curves CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local co...

Page 3: ...Heat insulation Condensate connection 1 For drainage Clamp 1 Connect the drain hose to condensate connection Copper nut 1 Use for pipe connection LED display panel 1 Operation and error display Copper...

Page 4: ...BA Low 31 8 32 7 31 4 31 9 34 2 39 4 40 8 41 2 Medium 32 1 32 4 33 7 32 7 33 6 36 3 42 3 43 8 43 8 High 33 2 32 7 36 8 35 9 38 6 42 0 46 7 47 8 48 0 UNIT Unit Dimensions W x H x D in 39 1 4 x 8 1 4 x...

Page 5: ...w Mounting Brackets 4 Fig 3 40VMM012 048 Dimensions NOTE All dimensions shown in inches 40VMM UNIT SIZE DIMENSION in A B C D E F G H I J K L M 012 36 1 4 10 5 8 25 22 1 2 39 3 4 2 5 8 28 1 3 8 7 10 1...

Page 6: ...M a x E S P Lower Limit of ESP ESP ESP M Speed L Speed Fig 4 Size 007 Fan Curves LEGEND ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max CFM SP in Mid CFM SP...

Page 7: ...r Limit of ESP Min ESP Lower Limit of ESP Rating ESP Lower Limit of ESP Min ESP Fig 6 Size 012 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max CFM...

Page 8: ...mit of ESP Min ESP Lower Limit of ESP Rating ESP Lower Limit of ESP Min ESP Fig 8 Size 018 Fan Curves LEGEND ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max...

Page 9: ...imit of ESP Min ESP Lower Limit of ESP Rating ESP Lower Limit of ESP Min ESP Fig 10 Size 030 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Point Min Point Max CFM S...

Page 10: ...Max CFM SP in Mid CFM SP in Min CFM SP in 0 10 H 1509 0 00 1370 0 10 1165 0 20 0 20 H 1576 0 07 1370 0 18 1165 0 28 0 30 H 1576 0 17 1370 0 29 1165 0 36 0 40 H 1576 0 31 1370 0 41 1165 0 47 0 50 H 157...

Page 11: ...ll trades in their parts of the installation Units must be installed in compliance with all applicable local code requirements IDENTIFYING AND PREPARING UNITS Be sure power requirements match availabl...

Page 12: ...ews that secure the filter frame to the rear of the unit 2 Remove the screws that secure the return air cover plate to the bottom of the unit and set the cover plate aside See Fig 15 below Apply Foam...

Page 13: ...unit and ends at the outdoor unit or MDC Multiport Distribution Controller for Heat Recovery systems The refrigerant piping should be dry and free of dust and other impurities The bending angle of the...

Page 14: ...sturbance on the controls side See Fig 22 and 23 for wiring diagrams NOTE The indoor unit requires its own power supply Indoor units are not powered through outdoor units WARNING Electrical shock can...

Page 15: ...XS1 4 XT1 2 Terminal Block Optional Component or Field Wiring Fig 22 40VMM007 009 Typical Wiring Diagram EEV A H B H FM ALARM PUMP CN24 CN2 N3 CN1 C 8 EARTH Y G CN15 CN9 CN17 Y G L1 L2 controller To w...

Page 16: ...t use copper conductors only ACB Auxiliary Control Board ALARM Warning Lamp AUXH Output For Auxiliary Heat CS Condensate Switch CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN DC...

Page 17: ...Fig 30 and 31 for typical communication wiring of the heat pump and the heat recovery systems Fig 25 Shearing Outdoor Connector Fig 26 Stripping The Wire Fig 27 Connecting Communication Wire to Outdoo...

Page 18: ...No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 HA...

Page 19: ...ontroller HA HB L1 L3 L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resisto...

Page 20: ...any water It may take time for the water to travel depending on the length of the drain pipe 4 During this test check any bends or joints for leakage System Operation Check Once the installation and...

Page 21: ...00001 Indoor unit addressing can be performed using the wireless remote controller When using the wireless controller the user must maintain a line of sight with the receiver on the indoor unit See Fi...

Page 22: ...DU ADDRESSING Press MENU OK to access this setting 3 Press TEMP UP or TEMP DOWN to choose the address you want to set see Fig 39 Press MENU OK to send this address to the IDU 4 Press BACK twice or wai...

Page 23: ...one Heating Cooling Mode Conflict E1 None Communication Error Between Indoor and Outdoor Unit E2 None Check Indoor Ambient Temperature Sensor T1 E4 None Check Evaporator Temperature Sensor T2B E5 None...

Page 24: ...on Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal wires from ele...

Page 25: ...cated on the main control board When J1 jumper is not in place Auto Restart function is enabled When J1 jumper is in place Auto Restart function is disabled The default setting for J1 is without the j...

Reviews: