background image

OM-40MBD-04                                                                            Specifications subject to change without notice.                                                                                         

9

CLEANING, MAINTENANCE AND TROUBLESHOOTING

Periodic Maintenance

Periodic maintenance is recommended to ensure proper operation of 
the unit. Recommended maintenance intervals may vary depending on 
the installation environment, e.g., dusty zones, etc. Refer to Table 1 on 
page 11.

Cleaning the Coil

Clean the coil at the beginning of each cooling season, or when 
necessary. Use a vacuum cleaner or a long-bristle brush to avoid 
damage to the coil fins.

Cleaning the Air Filters

Remove and clean the air filters once a month.

NOTE: 

If air filters show signs of excessive wear or are torn, they 

must be replaced. Contact your local dealer for replacement filters.

1. Unscrew filters from the frame.
2. Pull filters down to remove.

Fig. 9 — Remove the filters

3. Vacuum the filters.

Fig. 10 — Vacuum the filters

4. Clean with warm water.

Fig. 11 — Clean filter with warm water

5. Shake the filter to remove excess water and dry thoroughly.
6. Replace the filter by sliding into rack until the filter snaps in place.
7. Close the front panel on the unit.

Preparing for Extended Shutdown Period

Clean the filters and reposition them in the unit. Operate the unit in 

FAN ONLY

 mode for 12 hours to dry all internal parts. Turn the main 

power supply off and remove batteries from the remote control.

ELECTRICAL SHOCK HAZARD

Failure to follow this caution may result in personal injury or death. Always 

turn off power to the system before performing any cleaning or maintenance to 

the system. Turn off the outdoor disconnect switch located near outdoor unit. 
Be sure to disconnect the indoor unit if on a separate switch.

CAUTION

EQUIPMENT DAMAGE/OPERATION HAZARD

Failure to follow this caution may result in equipment damage or improper 

unit operation.
Operating the system with dirty air filters may damage the indoor unit and 

could cause reduced cooling performance, intermittent system operation, 

frost build-up on indoor coil or blown fuses.

CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury. The coil fins are 

very sharp. Use caution when cleaning. Always wear safety protection.

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage. When cleaning 

the front panel, do not use water hotter than 105

°

F (40.6

°

C) and do not pour 

water onto the fan coil. Do not use abrasive or petroleum based cleaners as they 

may damage the front panel.

CAUTION

FAN/SLC

Summary of Contents for 40MBD Series

Page 1: ...ease record the model and serial numbers of your new equipment in the spaces provided This information along with the installation data and dealer contact information will be helpful should your syste...

Page 2: ...according to the user selected set point NOTE AUTO mode is recommended for use on single zone applications ONLY Using AUTO CHANGEOVER on multi zone applications could set an indoor unit to STANDBY mo...

Page 3: ...thout notice 3 PARTS LIST Table 1 Parts List Fig 1 Indoor Unit DISPLAY PANEL Fig 2 IR Receiver Display Panel PART NO PART NAME 1 Air outlet 2 Air inlet 3 Air filter 4 Electric Control Cabinet 5 Wired...

Page 4: ...ases temperature O O in 1 F 1 C increments Max temperatur e is O O 86 F 30 C Set timer to turn unit on or off Saves energy during sleeping hours Selects fan speeds in the following order AUTO LOW MED...

Page 5: ...f flashes Displays when LOCK feature is activated LOW MED HIGH AUTO Lights up when remote sends signal to indoor unit Displays selected fan speed Displays the current including mode This fan speed can...

Page 6: ...audible beep from the indoor unit or if the Transmission Indicator fails to light 5 When batteries are removed the remote control erases all programmed settings The control must be reprogrammed after...

Page 7: ...unction TIMER ON to start the unit and TIMER OFF to stop the unit can be used separately or together Timer ON only This function allows the unit to start automatically at the set time The TIMER ON can...

Page 8: ...s location The remote control sends this signal to the air conditioner every 3 minutes This function is not available for DRY and FAN modes Freeze Protection Mode Press FP for approximately 2 seconds...

Page 9: ...d Clean the filters and reposition them in the unit Operate the unit in FAN ONLY mode for 12 hours to dry all internal parts Turn the main power supply off and remove batteries from the remote control...

Page 10: ...the unit away from direct sunlight and heat as this may interfere with remote control transmissions Do not block air intakes and outlets on the indoor or outdoor units Energy Saving Recommendations T...

Page 11: ...reaker has tripped or a fuse has blown Power failure Diagnostic lights illuminate Voltage is too low Reset the circuit breaker or replace the fuse with the specified replacement fuse Call your service...

Page 12: ...erwood Parkway Atlanta GA 30339 Edition Date 10 20 Catalog No OM 40MBD 04 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incu...

Reviews: