INDOOR UNIT DIAGNOSTIC GUIDES
For ease of service, the systems are equipped with diagnostic code display LEDs on the indoor unit. There may be a few error codes displayed in the
indoor unit that might relate to the outdoor unit's problems. If possible, always check the diagnostic codes displayed on the indoor unit first.
Table 4 — Indoor Unit Diagnostic Guides
☆
= Flashing, X = Off
Table 5 — Indoor Unit Diagnostic Guides
O (on
−
light) X (off
−
light)
☆(
flash)
GREEN LED
RED LED
FAILURE MODE
On
X
Standby, normal
X
On
Operation, normal
On
On
High/Low voltage protection on compressor terminal
On
☆
EEPROM error
X
☆
The compressor speed is out of control
☆
On
Zero-crossing signal detection error; lack of phase; synchronization error
☆
X
IGBT or Module protection
☆
☆
Communication error
OPERATION LAMP (TIMES)
TIMER LAMP
DISPLAY
ERROR INFORMATION
☆
1
OFF
EH 00/EH 0A
Indoor unit EEPROM parameter error
☆
2
OFF
EL 01
Indoor/outdoor unit communication error
☆
3
OFF
EH 02
Zero-crossing signal detection error
☆
4
OFF
EH 03
Indoor fan operating outside of the normal range
☆
5
OFF
EC 51
Outdoor unit EEPROM parameter error
☆
5
OFF
EC 52
T3 is in open circuit or has short circuited
☆
5
OFF
EC 53
T4 is in open circuit or has short circuited
☆
5
OFF
EC 54
TP is in open circuit or has short circuited
☆
5
OFF
EC 56
T2B is in open circuit or has short circuited
☆
6
OFF
EH 60
T1 is in open circuit or has short circuited
☆
6
OFF
EH 61
T2 is in open circuit or has short circuited
☆
12
OFF
EC 07
Outdoor fan operating outside of the normal range
☆
9
OFF
EH 0b
Indoor PCB/Display board communication error
☆
8
OFF
EL 0C
Refrigerant leakage detection
☆
7
FLASH
PC 00
IPM malfunction or IGBT OSCP
☆
2
FLASH
PC 01
Over voltage or over low voltage protection
☆
3
FLASH
PC 02
Compressor or IPM high temp/pressure protection
☆
5
FLASH
PC 04
Inverter compressor drive error
☆
1
FLASH
PC 08
Current overload protection
☆
6
FLASH
PC 40
Comm. error between outdoor chip and compressor chip
☆
7
FLASH
PC 03
Low pressure protection
☆
1
ON
--
Indoor units mode conflict
☆
9
OFF
EH b1
Indoor board and Multi-function communication error
☆
11
OFF
FH 0d
Ionizer malfunction