39
NC Curves
Fig. 23 —38VMA072RDS5-1
Table 30 —38VMA072RDS5-1
Fig. 24 —38VMA072RDS6-1
Table 31 —38VMA072RDS6-1
NOTE:
When silent mode is set, the unit's capacity is limited. The unit will automatically exit silent mode if high pressure exceeds 522
psi. The unit will automatically return to silent mode once high side pressure falls below 479 psi.
38VMA072RDS5-1
63
125
250
500
1000
2000
4000
8000
dB(A)
Standard
60Hz
66.9
66.3
58.5
57.5
50.7
46.3
42.1
36.7
58.8
Low noise mode
60Hz
55.6
51.7
52.4
51.3
45.8
42.0
41.6
37.1
52.4
38VMA072RDS6-1
63
125
250
500
1000
2000
4000
8000
dB(A)
Standard
60Hz
68.5
65.2
57.8
56.4
51.1
45.0
39.0
36.8
57.7
Low noise mode
60Hz
56.3
56.0
51.3
50.0
44.2
42.3
36.0
36.3
51.5