CASSETTE TYPE AIR CONDITIONER

INSTALLATION MANUAL

G B

ENGLISH

INSTALLATION MANUAL

I

ITALIANO

MANUALE DI INSTALLAZIONE

F

MANUEL D'INSTALLATION

D E

INSTALLATIONSHANDBUCH

DEUTSCH

E

MANUAL DE INSTALACIÓN

N L

INSTALLATIEHANDLEIDING
NEDERLANDS

FRANÇAIS

ESPAÑOL

P L

POLSKI

INSTRUKCJA MONTA

Ż

U

Summary of Contents for 38QUS024DS Series

Page 1: ...MANUAL G B ENGLISH INSTALLATION MANUAL I ITALIANO MANUALE DI INSTALLAZIONE F MANUEL D INSTALLATION D E INSTALLATIONSHANDBUCH DEUTSCH E MANUAL DE INSTALACI N N L INSTALLATIEHANDLEIDING NEDERLANDS FRAN...

Page 2: ...uct the retailer will take back the old product at least free of charge 3 The manufacture will take back the old appliance for disposal at least free of charge to the user 4 As old products contain va...

Page 3: ...stall The Panel 3 OUTDOOR UNIT INSTALLATION 3 1 Installation Site Choosing 3 2 Outdoor Unit Mounting Dimension 3 3 Space Requirement For Outdoor Unit 3 4 Install The Outdoor Unit 3 5 Install The Drain...

Page 4: ...or cooking device Exposure to this gas could cause severe injury or death Disconnect from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting...

Page 5: ...in a location with special environmental conditions Do not install in a place that can amplify the noise level of the unit or where noise and discharged air might disturb neighbors Perform the draina...

Page 6: ...to prevent the screen from being distorted or noise from being generated Install the indoor unit as far away as possible from fluorescent and incandescent lights so that the remote control can be ope...

Page 7: ...ALLATION Clearance from the wall or other obstacles Connecting port of refrigerant pipe Connecting port of drain pipe Connecting port of drain pipe Connecting port of refrigerant pipe Dimension 287 31...

Page 8: ...4 Adjust level of the unit by using level vial to make sure horizontal level of the main body within 1 It is recommended to install the Y joint before installing the indoor unit When moving the unit...

Page 9: ...00 or more and fix it by hanger space of 1 0 1 5m The flexible hose should not be installed upward position it may cause water flow back to the indoor unit Lean over 1 100 1 0 1 5m Max 750mm Stow tube...

Page 10: ...ked with the piping side and drain side with piping interface and drainage interface of the main body Hang the panel to the hooks on the main body Tighten the screw evenly under the panel hook until t...

Page 11: ...the piping between the indoor and outdoor units is within the allowable limits In regions with snowfall and cold temperatures avoid installing the outdoor unit in areas where it can be covered by snow...

Page 12: ...the fixing leg that is in contact with the bottom plate of the outdoor unit 3 4 INSTALL THE OUTDOOR UNIT 100mm 100 300mm Outdoor unit Vibration proof rubber Anchor bolt M10 Drainage Wide 100mm x Dept...

Page 13: ...7 N m 65 67 N m 6 35mm 9 52mm 12 7mm 15 88mm 19 05mm Use separate thermal insulation pipes for gas liquid pipes The thickness above is a standard of the indoor temperature of 27 C and humidity of 80 I...

Page 14: ...38QUS024 38QUS036 48 9 52mm 9 52mm 9 52mm 15 88mm 15 88mm 5 5 5 25 30 30 20 15 10 30 g m 30 g m 30 g m NOTE When the pipe length is over 5m the additional refrigerant should be added according to the...

Page 15: ...n safety checked A main switch and circuit breaker or fuse must be installed the capacity should be above 1 5 times of maximum current in circuit An individual branch circuit and single socket used on...

Page 16: ...ing Field Supply Indoor Phase 1 Phase 220 240V 50Hz Frequency and volt 1 8A Rated Current Fuse Rating Field Supply 16A Shielded cable 2 0 2mm2 QUS048 H05VV F 3 1 0mm2 1 Phase 220 240V 50Hz 1 2A 16A QU...

Page 17: ...the same place together Proximity may cause electrical interference malfunctions and breakage CAUTION 60mm 40mm 10mm Power input cord Single phase GND 60mm 40mm 10mm GND L N S1 S2 Outdoor Unit QUS036...

Page 18: ...ther the buttons such as ON OFF MODE TEMPERATURE FAN SPEED etc on the remote controller work well Whether the louver moves normally Whether the room temperature is adjusted well Whether the indicator...