88
16.2 Outdoor unit error display
For 18K-24K outdoor unit:
No.
Problems
LED2
(Green)
LED1
(Red)
IU display
1
standby for normal
O
X
2
Operation normally
X
O
3
Compressor drive board EEPROM error
O
☆
E5
4
IPM malfunction or IGBT over-strong current protection
☆
X
P0
5
Over voltage or too low voltage protection
O
O
P1
6
Inverter compressor drive error
X
☆
P4
7
Inverter compressor drive error
☆
O
P4
8
Communication malfunction between main control board
and driver board
☆
☆
P4
For 36K-60K Outdoor Unit
No
Problems
Error Code
1
Communication malfunction between indoor and outdoor units
E1
2
Current overload protection
F0
3
Outdoor ambient temperature sensor (T4 ) malfunction
F1
4
Condenser coil temperature sensor (T3) malfunction
F2
5
Compressor discharge temperature sensor (T5) malfunction
F3
6
Outdoor unit EEPROM parameter error
F4
7
Outdoor fan speed malfunction
F5
8
Inverter module (IPM) malfunction
P0
9
Over-voltage or under-voltage protection
P1
10
Compressor top high temperature protection (OLP)
P2
11
Low ambient temperature cut off in heating
P3
12
Compressor drive malfunction
P4
13
High temperature protection of indoor coil in heating
J0
14
Outdoor temperature protection of outdoor coil in cooling
J1
15
Temperature protection of compressor discharge
J2
16
PFC module protection
J3
17
Communication malfunction between control board and IPM board
J4
18
High pressure protection
J5
19
Low pressure protection
J6
20
Outdoor IPM module temperature sensor malfunction
P7
21
AC voltage protection
J8
Summary of Contents for 38QUA009DS
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Page 9: ...6 A5 Ducted Units A6 Ducted Units...
Page 10: ...7 Floor ceiling Units...
Page 11: ...8 HESP DUCTED Units...
Page 35: ...32 6 Wiring Diagram 6 1 Indoor Unit 40QTD018DS 40QTD024DS 40QTD036DS 40QTD048DS...
Page 36: ...33 40QSM018DS 40QSM024DS 40QSM036DS 40QSM048DS...
Page 37: ...34 40QZL018DS 40QZL024DS 40QZL036DS...
Page 38: ...35 40QZL048DS 40QZL060DS...
Page 40: ...37 6 2 Outdoor Unit 38QUA018DS 38QUA024DS...
Page 41: ...38 38QUA036DS...
Page 42: ...39 38QUA048DS 38QUA060DS...
Page 44: ...41 40QSM018DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 45: ...42 40QSM024DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 46: ...43 40QSM036DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 47: ...44 40QSM048DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 60: ...57 12 Field Wiring 18K 24K 36K 48K...
Page 61: ...58 60K...
Page 104: ...101 P U P V...
Page 105: ...102 P W P N...