Service manual
20
If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor On, the
unit stops and LED displays failure information and can’t returns to normal operation automatically.
8.4 Fan-only mode
Fan speed is high/mid/low/ Auto
8.5 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:(T=indoor temperature)
0
T-Ts
Room temp. up
Room temp. down
1
Compressor on
outdoor fan on
Compressor off
outdoor fan off
Auto fan at cooling mode: