background image

Owner’s Manual

Part Number 33CS220-LA

CONTENTS

Page

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

CONFIGURATION

. . . . . . . . . . . . . . . . . . . . . . . . . . 1-4

Thermostat Display

. . . . . . . . . . . . . . . . . . . . . . . .

1

Heat or Cool Indicator

. . . . . . . . . . . . . . . . . . . . .

1

Thermostat Front Panel Buttons

. . . . . . . . . . . .

1

Thermostat Programming Buttons

. . . . . . . . . .

2

Set Clock

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Programming Thermostat Schedules

. . . . . . .

3

OPERATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5

Auto-Changeover

. . . . . . . . . . . . . . . . . . . . . . . . . .

4

Light-Activated Operation

. . . . . . . . . . . . . . . . . .

4

Two-Stage Operation

. . . . . . . . . . . . . . . . . . . . . .

5

Clock Backup

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Fan Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Emergency Heat

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Electric Heat

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Holiday Mode

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

IMPORTANT: Read entire instructions before program-
ming the thermostat.

GENERAL

Carrier’s 7-day, commercial, programmable thermostats

are wall-mounted, low-voltage thermostats which maintain
room temperature by controlling the operation of an HVAC
(heating, cooling and ventilation) system. Separate heating
and cooling set points and auto-changeover capability allow
occupied and unoccupied programming schedules for
energy savings.

All thermostats allow up to 3 occupied and one un-

occupied time/temperature setting to be programmed per
24-hour period. Each thermostat stores programs for
7 independent days. Batteries are not required. During power
interruption the internal NEVERLOST™ memory stores pro-
grams for an unlimited time.

IMPORTANT: The thermostat has a configurable security
level. If certain functions are not available (changing set
points, changing programming schedules), the thermostat
security level may be configured to exclude those func-
tions. Call the installer to reconfigure the security level.

A light sensor is provided on the thermostat for light

activation. When the sensor detects light (the space is
occupied), the thermostat will enter into Occupied 1 mode.
If the room is dark, the thermostat will follow its pro-
grammed schedule.

CONFIGURATION

Thermostat Display —

The thermostat display is

located in the center of the thermostat. See Fig. 1. The fol-
lowing information can be displayed on the screen:
• mode (OFF, HEAT, COOL, AUTO, or PROGRAM ON)
• fan setting (FAN ON or blank)
• override indication
• room temperature
• desired temperature
• service filter indicator
• time of day
• day of the week
• schedule period (Occupied 1, 2, or 3; or Unoccupied)
• setup indicator (programming mode)
• lock indicator
• start/stop indicator (schedule period program mode)

Heat or Cool Indicator —

A Heat or Cool indicator

is located on the bottom left cover of the thermostat. See
Fig. 2. The light will be red if the thermostat is in Heating
mode. The light will be green if the thermostat is in Cooling
mode.

Thermostat Front Panel Buttons —

The thermo-

stat has buttons on the front cover which are used to raise or
lower the desired set point and override the current program.
See Fig. 2.

SET POINT BUTTONS — The UP ARROW and DOWN
ARROW buttons will raise or lower the current desired tem-
perature set point. If the thermostat is in AUTO mode, press-
ing the UP ARROW or DOWN ARROW buttons will adjust

Fig. 1 — Thermostat Display

33CS

Commercial

Programmable Thermostat

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

11a 13a

PC 111

Catalog No. 533-332

Printed in U.S.A.

Form 33CS-6SO

Pg 1

2-98

Replaces: New

Summary of Contents for 33CS220-LA

Page 1: ...d on the thermostat for light activation When the sensor detects light the space is occupied the thermostat will enter into Occupied 1 mode If the room is dark the thermostat will follow its pro grammed schedule CONFIGURATION Thermostat Display The thermostat display is located in the center of the thermostat See Fig 1 The fol lowing information can be displayed on the screen mode OFF HEAT COOL AU...

Page 2: ... the display The thermostat is unlocked by performing the same pro cedure Press and hold the Mode button While holding down the Mode button press the Up and Down Arrow buttons simultaneously The Locked icon will be removed from the display FAN BUTTON OPERATION The Fan button selects fan operation When the fan is set to FAN ON the fan will run continuously for improved air circulation NOTE When the...

Page 3: ...savings with set points of 80 F for cooling and 65 F for heating PROGRAMMING MODE To program the daily sched ules perform the following procedure 1 Enter programming mode by pressing the Program but ton The Occupied 1 annunciator will appear on the ther mostat display See Fig 5 Use the UP ARROW and DOWN ARROW buttons to set the maximum number of Occupied periods available The thermostat can be set...

Page 4: ...rt and stop times are programmed for an occupancy schedule the thermostat will be in Occupied mode for 24 hours If one occupied period starts or stops within another occupied period the lower numbered schedule has pri ority For example if schedule Occupied 3 is running for 24 hours and occupied schedule 2 comes on from 1 to 3 PM the set points from Occupied 2 are in effect from 1 to 3 PM OVERRIDIN...

Page 5: ...at only OFF and HEAT modes are available Electric Heat When the Electric Heat option in the advanced set up is set to ON configured by installer the thermostat will turn on the fan immediately any time there is a heat demand This feature should only be used on elec tric heating applications Do not use with gas heat Holiday Mode When the thermostat is in Holiday mode the thermostat will operate und...

Page 6: ......

Page 7: ...7 ...

Page 8: ...facturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 11a 13a PC 111 Catalog No 533 332 Printed in U S A Form 33CS 6SO Pg 8 2 98 Replaces New ...

Reviews: