4.2 - Electrical data, units without options 150, 5 and 6
Standard-efficiency units
30XW--/30XWH
254
304
354
402
452
552
602
652
702
802
852
1002 1052 1154 1252 1352 1452 1552 1652 1702
Power circuit
Nom. power supply V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit
24 V via the built-in transformer
Nominal start-up current*
Circuit A
A
233
233
303
414
414
414
414
587
587
587
587
414
414
414
587
587
587
587
587
587
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
414
414
414
414
587
587
587
587
587
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
558
574
574
747
780
801
819
819
819
Maximum start-up current**
Circuit A
A
233
233
303
414
414
414
414
587
587
587
587
414
414
414
587
587
587
587
587
587
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
414
414
414
414
587
587
587
587
587
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
631
656
656
829
882
904
938
938
938
Cosine phi
Nominal***
0.83 0.85 0.83 0.87 0.88 0.89 0.89 0.88 0.89 0.90 0.90 0.88 0.89 0.89 0.88 0.88 0.89 0.90 0.90 0.90
Maximum****
0.89 0.89 0.88 0.90 0.90 0.91 0.91 0.90 0.91 0.92 0.92 0.90 0.91 0.91 0.90 0.90 0.91 0.92 0.92 0.92
Total harmonic
distortion****
%
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Maximum power input†
Circuit A
kW
76
89
97
128
135
151
151
184
200
223
223
150
151
151
184
184
200
223
223
223
Circuit B
kW
-
-
-
-
-
-
-
-
-
-
-
135
151
151
151
184
200
223
202
223
Option 81
kW
-
-
-
-
-
-
-
-
-
-
-
284
301
301
334
367
399
447
425
447
Nominal current drawn***
Circuit A
A
84
96
113
136
144
162
162
193
214
232
232
162
162
162
193
193
214
232
232
232
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
144
162
162
162
193
214
232
214
232
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
306
324
324
355
386
427
464
446
464
Maximum current drawn (Un)†
Circuit A
A
123
145
160
206
217
242
242
295
317
351
351
242
242
242
295
295
317
351
351
351
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
217
242
242
242
295
317
351
317
351
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
459
484
484
537
590
634
702
668
702
Maximum current drawn (Un -10%)****
Circuit A
A
138
162
178
218
230
260
260
304
340
358
358
260
260
260
304
304
340
358
358
358
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
230
260
260
260
304
340
358
340
358
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
490
520
520
564
608
680
716
698
716
Maximum power input with option 150B†
Circuit A
kW
67
79
87
114
118
133
134
173
183
205
205
133
133
133
173
173
183
207
207
207
Circuit B
kW
-
-
-
-
-
-
-
-
-
-
-
118
133
133
133
173
183
207
185
207
Option 81
kW
-
-
-
-
-
-
-
-
-
-
-
251
265
265
305
346
365
414
391
414
Maximum current drawn (Un) with option 150B†
Circuit A
A
109
129
142
183
191
212
212
278
290
325
325
212
212
212
278
278
290
325
325
325
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
191
212
212
212
278
290
325
290
325
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
403
424
424
490
556
580
650
615
650
High-efficiency units
30XW-P/30XWHP
512
562
712
812
862
1012
1162
1314
1464
1612
1762
Power circuit
Nominal power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit
24 V via the built-in transformer
Nominal start-up current*
Circuit A
A
414
414
587
587
587
414
414
587
587
587
587
Circuit B
A
-
-
-
-
-
414
414
414
587
587
587
Option 81
A
-
-
-
-
-
556
574
747
780
801
819
Maximum start-up current**
Circuit A
A
414
414
587
587
587
414
414
587
587
587
587
Circuit B
A
-
-
-
-
-
414
414
414
587
587
587
Option 81
A
-
-
-
-
-
631
656
829
882
904
938
Cosine phi
Nominal***
0.88
0.89
0.88
0.89
0.90
0.86
0.87
0.88
0.88
0.89
0.90
Maximum****
0.90
0.90
0.90
0.91
0.92
0.89
0.90
0.90
0.90
0.91
0.92
Total harmonic distortion****
%
0
0
0
0
0
0
0
0
0
0
0
Maximum power input†
Circuit A
kW
135
151
184
200
223
134
151
184
184
200
223
Circuit B
kW
-
-
-
-
-
134
151
151
184
200
223
Option 81
kW
-
-
-
-
-
267
301
334
367
399
447
Nominal current drawn***
Circuit A
A
144
162
193
214
232
144
162
193
193
214
232
Circuit B
A
-
-
-
-
-
144
162
162
193
214
232
Option 81
A
-
-
-
-
-
288
324
355
386
427
464
Maximum current drawn (Un)†
Circuit A
A
217
242
295
317
351
217
242
295
295
317
351
Circuit B
A
-
-
-
-
-
217
242
242
295
317
351
Option 81
A
-
-
-
-
-
434
484
537
590
634
702
Maximum current drawn (Un -10%)****
Circuit A
A
230
260
304
340
358
230
260
304
304
340
358
Circuit B
A
-
-
-
-
-
230
260
260
304
340
358
Option 81
A
-
-
-
-
-
460
520
564
608
680
716
Maximum power input with option 150B†
Circuit A
kW
118
133
173
183
207
118
133
173
173
183
207
Circuit B
kW
-
-
-
-
-
118
133
133
173
183
207
Option 81
kW
235
265
305
346
365
414
Maximum current drawn (Un) with option 150B†
Circuit A
A
191
212
278
290
325
191
212
278
278
290
325
Circuit B
A
-
-
-
-
-
191
212
212
278
290
325
Option 81
A
-
-
-
-
-
382
424
490
556
580
650
* Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor).
Values obtained at standard Eurovent conditions: evaporator entering/leaving water temp. = 12°C/7°C, condenser entering/leaving water temp. = 30°C/35°C.
** Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor).
Values obtained at operation with maximum unit power input.
*** Values obtained at standard Eurovent conditions: evaporator entering/leaving water temp. = 12°C/7°C, condenser entering/leaving water temp. = 30°C/35°C
**** Values obtained at operation with maximum unit power input.
† Values obtained at operation with maximum unit power input. Values given on the unit name plate.