background image

24ACC6

Comfort

t

Series Air Conditioner

1 1/2 To 5 Nominal Tons

Wiring Diagrams

334024-101 REV. B

CONNECTION  DIAGRAM

COMP

OFM

S

C

R

BLU

BRN

BLK

YEL

BLK

YEL

RED or BLK

208/230 1Ø

POWER

SUPPLY

EQUIP  GND

L1

L2

BLU

CAP

H

C

F

YEL

*ST

+t

BLU

YEL

YEL

*SC

*CHS

*SR

(NOTE #8)

1

2

5

*CH

BLK

BLK

or

RED

BLK

BRN

(NOTE #9)

BLK

CONDENSING UNIT CHARGING INSTRUCTIONS

For use with units using R-410A refrigerant

INDOOR BLOWER MOTOR

EXTERNAL

POWER

SUPPLY

24 V

(NOTE #3)

INDOOR THERMOSTAT  (NOTE #6)

R

G

Y

*LLS

BLK

BLK

C
R

VIO

BRN/YEL

*LPS

*HPS

LOGIC

T1

*CTD

BLK

 BLU/PNK

T3

T2

NOTES:

1.  Symbols are electrical 
     representation only.
2.  Compressor and fan motor 
     furnished with inherent thermal 
     protection.
3.  To be wired in accordance with 
     National Electric N.E.C. 
     and local codes.
4.  N.E.C. class 2, 24V circuit, min.  
     40 VA required, 60 VA on units 
     installed with LLS.
5.  Use copper conductors only.  
     Use conductors suitable for at 
     least 75ºC (167ºF).
6.  Connection for typical cooling 
     only thermostat.  For other 
     arrangements see installation 
     instructions.
7.  If indoor section has a 
     transformer with a grounded 
     secondary, connect the 
     grounded side to the BRN/YEL
     lead.
8.  When start relay and start 
     capacitor are installed, start 
     thermistor is not used.
9.  CH not used on all units.
10.  If any of the original wire, as 
       supplied must be replaced, 
       use the same or equivalent 
       wire.
11.  Check all electrical 
       connections inside control 
       box for tightness.
12.  Do not attempt to operate unit 
       until service valves have 
       been opened.
13.  Do not rapid cycle 
       compressor.
       Compressor must be off 3 
       minutes to allow 
       pressures to equalize 
       between high and low 
       side before starting.

 * MAY BE FACTORY INSTALLED

LEGEND

FACTORY POWER WIRING

FACTORY CONTROL WIRING

FIELD CONTROL WIRING

FIELD POWER WIRING

COMPONENT CONNECTION

FIELD SPLICE

JUNCTION

PLUG RECEPTACLE

CONT

CAP

*CH

*CHS

COMP

*CTD

*DTS

*HPS

IFR

*LLS

*LPS

OFM

*SC

*SR

*ST

CONTACTOR

CAPACITOR (DUAL RUN)

CRANKCASE HEATER

CRANKCASE HEATER SWITCH

COMPRESSOR

COMPRESSOR TIME DELAY

DISCHARGE TEMP SWITCH

HIGH PRESSURE SWITCH

INDOOR FAN RELAY

LIQ LINE SOLENOID VALVE

LOW PRESSURE SWITCH

OUTDOOR FAN MOTOR

START CAPICATOR

START RELAY

START THERMISTOR

CAUTION

1.  Compressor damage may occur if system is
      over charged.
2.  This unit is factory charged with R-410A in
      accordance with the amount shown on the
     rating plate.  The charge is adequate for most
      systems using matched coils and tubing not
      over 15 feet long.  Check refrigerant charge
      for maximum efficiency.  See Product Data
      Literature for required Indoor air Flow Rates
      and for use of line lengths over 15 feet.
3.  Relieve pressure and recover all refrigerant
     before system repair or final disposal.  Use all
     service ports and open all flow-control devices,
      including solenoid valves.
4.  Never vent refrigerant to atmosphere.  Use
      approved recovery equipment.

SCHEMATIC DIAGRAM  (LADDER FORM)

L1

*CH

EQUIP

GND

*SR

*SC

H

*ST

C

F

CAP

OFM

L2

5

2

1

*HPS

* CTD

*LLS

IFR

INDOOR THERMOSTAT

Y

G

R

C

R

EXTERNAL POWER SUPPLY 24 V

+

t

LOGIC

T1

T3

T2

CONT

COMP

S

C

R

*CHS

*LPS

CONT

11

21

23

23

11

21

CONT

CONT

23

23

YEL/ PNK

YEL/ PNK

 BLU/PNK

COOLING ONLY 

CHARGING PROCEDURE

1.  Only use sub cooling charging method
     when OD ambient is greater than 70ºF 
     and less than 100ºF, indoor temp is 
     greater than 70ºF and less than 80ºF, 
     and line set is less than 80 ft.
2.  Operate unit a minimum of 15 minutes 
     before checking the charge.
3.  Measure liquid service valve pressure
     by attaching an accurate gauge to the 
     service port.
4.  Measure the liquid line temperature by 
     attaching an accurate thermistor type 
     or electronic thermometer to the liquid
     line near the outdoor coil.
5.  Refer to unit rating plate for required 
     subcooling temperature.
6.  Find the point where the required sub-
     cooling temperature intersects the 
     measured liquid service valve pressure.
7.  To obtain the required subcooling 
     temperature at specific liquid line 
     pressure, add refrigerant if liquid line 
     temperature is higher than indicated. 
     When adding refrigerant, charge in 
     liquid form using a flow restricting 
     device into suction service port.  
     Recover refrigerant if temperature is
     lower. Allow a tolerance of +/- 3ºF.

REQUIRED LIQUID LINE TEMPERATURE

Required Subcooling

Temperature  (ºF)

Liquid Pressure

at Service

Valve (psig)

6

8

10 12 14 16

251

259
266
274
283
291
299

308
317
326
335
345
354
364
374

76

74

72

70

68

78

76

74

72

70

80

78

76

74

72

82

80

78

76

74

84

82

80

78

76

86

84

82

80

78

88

86

84

82

80

90

88

86

84

82

92

90

88

86

84

94

92

90

88

86

96

94

92

90

88

98

96

94

92

90

100

98

96

94

92

102 100

98

96

94

104 102 100

98

96

384
395
406
416
427

439
450

462

474

106 104 102 100

98

108 106 104 102 100
110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110

120 118 116 114 112

122 120 118 116 114

78

80
82
84
86
88
90

92
94
96
98

100
102
104
106

108
110
112
114
116
118
120

122

124

Fig. 1 – Wiring Diagram — Model sizes 1--1/2 -- 5 tons, 208/230--1

Reviews: